Abstract
In this study, a novel parallel converter-based hybrid high-voltage direct current (HVDC) system is proposed for the integration and delivery of large-scale renewable energy. The rectifier uses the line commutated converter (LCC) and low-capacity modular multilevel converter (MMC) in parallel, while the inverter uses MMC. This configuration combines the economic advantages of LCC with the flexibility of MMC. Firstly, the steady-state control strategies are elaborated. The low-capacity MMC operates in the grid-forming mode to offer AC voltage support. It also provides active filtering for the LCC and maintains the reactive power balance of the sending-end system. The LCC efficiently transmits all active power at the rectifier side, fully exploiting its bulk-power transmission capability. Secondly, the fault ride-through strategies of both the AC faults at two terminals and the DC fault are proposed, in which the MMCs at both terminals can remain unblocked under various faults. Thus, the proposed system can mitigate the impact of the faults and ensure continuous voltage support for the sending-end system. Finally, simulations in PSCAD/EMTDC verify the effectiveness and performance of the proposed system.
IN response to the challenges of climate change and ever-increasing energy demand, China has strategically planned several large-scale renewable energy bases (REBs) in its western regions. Given that load centers in China are predominantly situated in the eastern regions, the high-voltage direct current (HVDC) technology is envisioned to play a pivotal role in the long-distance and bulk-capacity transmission for these REBs [
Presently, two collection schemes are available for REBs: AC collection [
In terminal-based hybrid schemes, LCC and MMC are used at different terminals [
The pole-based hybrid scheme uses LCC and MMC in different poles. A typical application is the Skagerrak HVDC project connecting the Norwegian grid and the Danish grid [
In the converter-based hybrid scheme, LCC and MMC are combined in the same pole of the same converter station, which can be connected in series or in parallel. The series converter-based hybrid scheme has been studied widely [
The static synchronous compensator (STATCOM) may also be used in cooperation with the LCC for the integration of REBs. But it also has difficulties in the black start. Besides, the STATCOM needs to adopt the grid-forming control mode on the AC side and the DC voltage (submodule capacitor voltage) control mode on the DC side, which is more complex, and the performance under large disturbances has yet to be evaluated. By contrast, the parallel converter-based hybrid system allows LCC and MMC to flow different DC currents. Therefore, the black start can easily be realized by making the MMC at the sending-end operate in the inverter mode. It can enhance the flexibility of the HVDC system while fully utilizing the transmission capability of the LCC [
1) For the scenario where the sending-end system is pure REB, a parallel converter-based hybrid HVDC system is proposed. Its rectifier uses LCC and low-capacity MMC in parallel, while its inverter uses MMC. Fixed capacitors are also equipped on the AC side of the rectifier to provide partial reactive power compensation for the LCC. This configuration combines the technical and economic advantages of LCC and MMC, demonstrating potential feasibility for engineering implementation under current technological conditions. Besides, the selection method of the rated capacity of the converter is elaborated.
2) The steady-state and fault ride-through control strategies are designed for this system. In the steady state, the LCC efficiently transmits all active power on the rectifier side, since its manufacturing cost and power losses are lower than the MMC; the MMC in the rectifier station offers AC voltage support for the sending-end system. Under AC or DC temporary faults, the MMCs at both terminals can remain unblocked, which reduces the impacts of faults and ensures continuous voltage support.
The rest of this paper is structured as follows. Section II introduces the basics of the proposed system, including the system topology and the rated capacity selection of converters. Section III proposes the control strategies of the proposed system. In Section IV, case studies are conducted based on PSCAD/EMTDC. Section V draws the conclusions.

Fig. 1 Topology of proposed system.
Also, because of the requirements for bulk capacity and high-voltage level, each converter in
1) The AC voltage of the sending-end AC grid is controlled by the parallel MMC. Therefore, the commutation voltage for the LCC is available, and the grid-following converters with high technological maturity can be applied in the REB.
2) The reactive power balance of the sending-end AC grid is maintained by the parallel MMC. Specific capacity selection methods are described in the next subsection.
3) The parallel MMC also behaves as an active power filter on the AC side, and the AC harmonic currents generated by the LCC are filtered by it. As a result, the bulky AC filter banks can be eliminated.
Additionally, for fault ride-through purposes, DC braking resistors and AC braking resistors are installed at the DC side of the inverter and the AC side of the rectifier, respectively. Specific configuration principles and control strategies for these braking resistors are introduced in Section III-C and Section III-D.
The LCC rectifier and MMC inverter are required to transmit the full active power, and their rated capacities are selected as the rated capacity of the REB.
The rated capacity of the parallel MMC can be expressed as:
(1) |
where SQ and Sh are the capacities for reactive power balance and harmonic suppression, respectively; and denotes the capacity margin using the capacity of the LCC SLCC as the reference, and the margin coefficient k can be taken as 0.1.
In the sending-end system, the reactive power is mainly consumed by the LCC. As a compromise, and considering that the MMC can both supply or consume the reactive power, SQ is designed based on the principle that the maximum reactive power consumption of the LCC is supplied by half of the parallel MMC and half of the fixed capacitors. In this way, the capacity of the parallel MMC can be reduced and the reactive power balance of the system can be achieved flexibly at different power levels. For example, when the reactive power consumption is low, the parallel MMC can also absorb reactive power to achieve balance. Note that although the AC lines may also consume or generate reactive power, it is not very high and there is sufficient capacity margin left for the parallel MMC. Therefore, the reactive power balance can still be achieved.
The reactive power consumption of the LCC rectifier QLCC is:
(2) |
where Ur is the root mean square value of the sending-end AC voltage; XT and T are the leakage reactance and the transformer ratio of the LCC converter transformer, respectively; and and are the firing angle and overlap angle of the LCC, respectively, and can be calculated by:
(3) |
where Id is the DC current flowing through the LCC; and is the line-to-line voltage of the sending-end AC bus.
The analysis results in [
Take a bipolar HVDC system with the rated capacity of 10000 MW as an example. Its basic parameters are listed in
Parameter | Value |
---|---|
DC voltage | ±800 kV |
AC voltage | 500 kV |
Capacity of transformer | 1500 MW (for each 6-pulse LCC) |
Transformer ratio | 500 kV/165 kV |
Transformer leakage reactance | 0.15 p.u. |
Assume that is set to be 15°. In this case, the active power transmitted is approximated to be 10000 MW. According to (2) and (3), the total reactive power consumed by LCCs in the positive and negative poles is 4895 Mvar, which is about 50% of the system capacity. Therefore, SQ is about 0.25SLCC and SMMC can be selected as 0.4SLCC in this example.
The control block diagram of the LCC rectifier is shown in

Fig. 2 Control block diagram of LCC rectifier.

Fig. 3 Control block diagram of power balance control.

Fig. 4 Control block diagram of parallel MMC.
On the one hand, the AC voltage control and the output current control compose the dual closed-loop control to establish the voltage amplitude and frequency of the sending-end AC grid.
On the other hand, the harmonic current control is designed to make the total output current of the rectifier station irec free of harmonics.

Fig. 5 Mechanism of harmonic current control.
Besides, sequences of the (3k-2
(4) |
After the transformation in (4), the
Other basic controllers for MMC, such as the circulating current control, are omitted in
When a short-circuit fault occurs at the sending-end AC grid, the AC voltage of the rectifier station drops rapidly. This leads to a drop in the DC voltage of the LCC, as well as a reduction in its power transmission capability.
On the one hand, the drop in the DC voltage of the LCC may cause a drop in the DC current or even a reversal of its direction. The power transmitted from the sending-end to the receiving end can thus be reduced or even reversed. To avoid reverse power transmission as much as possible and mitigate the impact on the receiving end, the backup DC current control shown in

Fig. 6 Backup DC current control of MMC inverter.
On the other hand, the surplus power will cause the DC voltage of the grid-connected inverters in the REB to increase. However, the PV units can reduce their output power quickly in response to changes of the DC voltage, so that severe overvoltage will not occur. In view of this, no additional power dissipation measures are needed.
When a short-circuit fault occurs at the receiving-end AC grid, the AC voltage of the MMC inverter drops rapidly which impedes its power output to the AC side. The surplus power results in the increase of the DC voltage. Given the inevitable long delay in the long-distance transmission of the fault detection signal, it is challenging to coordinate the sending-end system to reduce the power, resulting in a constrained performance. Therefore, the chopper-controlled braking resistor, with a total capacity equal to the rated DC power of the system, is installed at the DC side of the MMC inverter. It is inserted to dissipate the surplus power when the DC voltage exceeds the preset upper threshold, and is blocked when the DC voltage drops below the preset lower threshold.
For the DC fault, two issues need to be addressed. On the one hand, the power delivery capability of the HVDC system is degraded and the surplus power of the sending-end AC grid needs to be dissipated. On the other hand, the control strategies of the converters need to be designed to achieve DC fault clearing and system recovery. For the first issue, braking resistors are installed at the AC side of the rectifier, which are set in groups with a total capacity equal to that of the REB. They are inserted and blocked according to the DC fault detection signal. For the second issue, the fault ride-through strategies are as follows.
Both the LCC and the parallel MMC that consists of hybrid-submodules can generate negative DC voltages to clear DC fault currents. However, due to their different control mechanisms and schemes, it is difficult to coordinate them to output the same DC voltage during the fault. In view of this, this paper adopts the strategy of blocking the LCC during the DC fault and clearing fault currents only with the parallel MMC.
For the LCC, it is immediately blocked when the DC fault is detected. After the fault has been cleared, it remains blocked for another 200 ms waiting for the deionization. Then, it is unlocked and the firing angle is controlled to decrease linearly from 45° to 15° within 200 ms. Finally, it is switched to the steady-state control strategy. The fault occurrence is judged by detecting the DC current exceeding 1.5 p.u..
As for the parallel MMC, its fault ride-through strategy under DC fault is shown in

Fig. 7 Fault ride-through strategy of parallel MMC under DC fault.
In addition, to maintain the submodule capacitor voltage of the parallel MMC in the fault pole during the fault, one group of AC braking resistors is selected for control according to the average voltage of the submodule capacitors ucave, which is calculated by:
(5) |
where is the voltage of the
The MMC inverter also adopts the DC current control shown in

Fig. 8 Ride-through strategy of MMC inverter under DC fault.
To verify the effectiveness and performance of the proposed system, a simulation case is established in PSCAD/EMTDC. In the case system, the PV-based REB is rated at 10000 MW and the HVDC system is a 10000 MW/±800 kV symmetrical bipolar system. Each pole of the rectifier station consists of two series 12-pulse LCCs and two series hybrid-submodule MMCs, while each pole of the inverter station consists of two series hybrid-submodule MMCs. Note that with the maximum capability of insulated gate bipolar transistor (IGBT) in existing projects, each pole of the inverter station requires two series 1250 MW/400 kV MMCs (as a set) and then two sets in parallel. Since the MMCs at the receiving end are located in the same inverter station and share the same AC bus of the inverter station (joint station construction scheme), each pole is represented by two equivalent series 2500 MW/400 kV MMCs in the simulation to improve the simulation efficiency. The length of DC overhead lines is 2000 km and the frequency-dependent (phase) model is adopted in the simulation. Other main parameters of the simulation system are listed in Table II.
Item | Parameter | Value |
---|---|---|
LCC rectifier (each 6-pulse LCC) | Rated capacity of transformer | 1500 MVA |
Transformer ratio | 500 kV/165 kV | |
Transformer leakage inductance | 0.15 p.u. | |
Parallel MMC (one of the series MMCs) | Rated capacity of converter | 1000 MVA |
Rated capacity of transformer | 1200 MVA | |
Rated DC voltage | 400 kV | |
Transformer ratio | 500 kV/210 kV | |
Transformer leakage inductance | 0.15 p.u. | |
Number of full-bridge submodules per arm | 140 | |
Number of half-bridge submodules per arm | 60 | |
Submodule capacitor | 16.7 mF | |
Arm inductance | 30.4 mH | |
DC inductor | 0.3 H | |
MMC inverter one of the series MMCs) | Rated capacity of converter | 2500 MVA |
Rated capacity of transformer | 3000 MVA | |
Rated DC voltage | 400 kV | |
Transformer ratio | 500 kV/210 kV | |
Transformer leakage inductance | 0.15 p.u. | |
Number of full-bridge submodules per arm | 140 | |
Number of half-bridge submodules per arm | 60 | |
Submodule capacitor | 41.7 mF | |
Arm inductance | 12.2 mH | |
Sending-end AC grid | Rated AC voltage | 500 kV |
Capacity of compensation capacitor banks | 2500 Mvar | |
Length of AC lines | 50 km | |
Receiving-end AC grid | Rated AC voltage | 500 kV |
Short-circuit ratio | 5 | |
Impedance angle | 80° |

Fig. 9 System response to output power fluctuation of REB. (a) Sending-end AC voltage. (b) Receiving-end AC voltage. (c) DC voltage. (d) DC current. (e) Active power of positive-pole rectifier. (f) Reactive power of positive-pole rectifier.
According to
The AC harmonic currents generated by the 12-pulse LCC are mainly of the 1

Fig. 10 Harmonic characteristics of positive-pole rectifier without and with application of harmonic current control. (a) Without application of harmonic current control. (b) With application of harmonic current control.
Without the application of the harmonic current control, the AC current of the rectifier station is severely distorted. In the IEEE Std 519, the maximum distortion limit is ranged from 0.5% to 1.5% for the 1

Fig. 11 Harmonic characteristic of positive-pole parallel MMC with application of harmonic current control. (a) AC current waveform of positive-pole parallel MMC. (b) Harmonic distortion rate.
In conclusion, the proposed harmonic current control for the parallel MMC is effective and can compensate for the harmonic currents output from the LCC well.
The sending-end AC faults, including balanced and unbalanced faults, are assumed to occur on the AC side of the rectifier and the AC side of the PV inverter. The system responses are shown in

Fig. 12 System responses to AC faults at AC side of rectifier. (a) Scenario 1: phase-a-to-ground fault. (b) Scenario 2: three-phase-to-ground fault.

Fig. 13 System responses to AC faults on AC side of PV inverter. (a) Scenario 1: phase-a-to-ground fault. (b) Scenario 2: three-phase-to-ground fault.
Based on
The system responses to receiving-end AC faults, including balanced and unbalanced faults, are illustrated in

Fig. 14 System responses to receiving-end AC faults. (a) Scenario 1: phase-a-to-ground fault. (b) Scenario 2: three-phase-to-ground fault.
According to
The DC faults are assumed to occur at the DC side of the rectifier, the midpoint of the DC lines and the DC side of the inverter, and the system responses are shown in

Fig. 15 System responses to positive-pole DC faults. (a) Scenario 1: fault at DC side of positive rectifier. (b) Scenario 2: fault at midpoint of positive DC lines. (c) Scenario 3: fault at DC side of positive inverter.
According to
This paper proposes a novel parallel converter-based hybrid HVDC system for the integration and delivery of large-scale renewable energy. The main conclusions are summarized as follows.
1) By paralleling the low-capacity MMC at the rectifier side, the system can provide voltage support for the sending-end AC grid. This feature makes the proposed system suitable for the integration and delivery of pure REBs.
2) The active power control of the LCC enables it to undertake all the active power transmission on the rectifier side and to absorb the fluctuating active power, thereby fully utilizing its bulk-power transmission capability.
3) The parallel MMC can maintain the reactive power balance of the sending-end AC grid. Besides, it can compensate for harmonic currents of the LCC with the harmonic current control, significantly reducing the harmonic currents injected into the REB from the rectifier station.
4) The effectiveness of the proposed fault ride-through strategies is verified by the simulations. No severe overvoltage or overcurrent occurs during these processes. Besides, the MMCs at both terminals can remain unlocked under various faults, which mitigates the impacts of the faults and ensures continuous voltage support for the REB.
The proposed system also has some limitations. Firstly, although the capacity of the sending-end MMC is significantly reduced, the number of its submodules is still high to withstand the DC voltage. In addition, this paper only discusses the basic operating principles and designs the steady-state and fault ride-through strategies. The stability characteristics of the system under small and large disturbances still need to be further investigated. These issues will be studied in our future work.
References
W. Wang, G. Li, and J. Guo, “Large-scale renewable energy transmission by HVDC: challenges and proposals,” Engineering, vol. 19, pp. 252-267, Dec. 2022. [Baidu Scholar]
J. M. Maza-Ortega, E. Acha, S. García et al., “Overview of power electronics technology and applications in power generation transmission and distribution,” Journal of Modern Power Systems and Clean Energy, vol. 5, no. 4, pp. 499-514, Jul. 2017. [Baidu Scholar]
X. Cai, W. Huang, G. Li et al., “Research on operation control strategy of large-scale photovoltaic cluster transmission via grid-forming VSC-HVDC,” Proceedings of the CSEE, vol. 43, no. 22, pp. 8734-8745, Nov. 2023. [Baidu Scholar]
S. Chuangpishit, A. Tabesh, Z. Moradi-Sharbabk et al., “Topology design for collector systems of offshore wind farms with pure DC power systems,” IEEE Transactions on Industrial Electronics, vol. 61, no. 1, pp. 320-328, Jan. 2014. [Baidu Scholar]
R. Zhu, X. Zhou, S. Luo et al., “DC current order optimization based strategy for recovery performance improvement of LCC-HVDC transmission systems,” Journal of Modern Power Systems and Clean Energy, vol. 11, no. 3, pp. 1020-1026, May 2023. [Baidu Scholar]
X. Li, Z. Xu, and Z. Zhang, “Application of MMC with embedded energy storage for overvoltage suppression and fault ride-through improvement in series LCC-MMC hybrid HVDC system,” Journal of Modern Power Systems and Clean Energy, vol. 11, no. 3, pp. 1001-1013, May 2023. [Baidu Scholar]
R. Rosso, X. Wang, M. Liserre et al., “Grid-forming converters: control approaches, grid-synchronization, and future trends – a review,” IEEE Open Journal of Industry Applications, vol. 2, pp. 93-109, Apr. 2021. [Baidu Scholar]
Y. Jin, Z. Zhang, Y. Huang et al., “Harmonic filtering and fault ride-through of diode rectifier unit and modular multilevel converter based offshore wind power integration,” IET Renewable Power Generation, vol. 17, no. 14, pp. 3554-3567, Oct. 2023. [Baidu Scholar]
Z. Xu, Y. Jin, Z. Zhang et al., “Eight typical schemes of offshore wind power transmission and their key technical problems,” Energies, vol. 16, no. 2, p. 658, Jan. 2023. [Baidu Scholar]
H. Yang, Z. Cai, X. Li et al., “Assessment of commutation failure in HVDC systems considering spatial-temporal discreteness of AC system faults,” Journal of Modern Power Systems and Clean Energy, vol. 6, no. 5, pp. 1055-1065, Sept. 2018. [Baidu Scholar]
M. A. Perez, S. Ceballos, G. Konstantinou et al., “Modular multilevel converters: recent achievements and challenges,” IEEE Open Journal of the Industrial Electronics Society, vol. 2, pp. 224-239, Feb. 2021. [Baidu Scholar]
H. Xiao, K. Sun, J. Pan et al., “Review of hybrid HVDC systems combining line communicated converter and voltage source converter,” International Journal of Electrical Power & Energy Systems, vol. 129, p. 106713, Jul. 2021. [Baidu Scholar]
P. Bakas, L. Harnefors, S. Norrga et al., “A review of hybrid topologies combining line-commutated and cascaded full-bridge converters,” IEEE Transactions on Power Electronics, vol. 32, no. 10, pp. 7435-7448, Oct. 2017. [Baidu Scholar]
K. Sun, H. Xiao, J. Pan et al., “A station-hybrid HVDC system structure and control strategies for cross-seam power transmission,” IEEE Transactions on Power Systems, vol. 36, no. 1, pp. 379-388, Jan. 2021. [Baidu Scholar]
W. Xiang, R. Yang, C. Lin et al., “A cascaded converter interfacing long-distance HVDC and back-to-back HVDC systems,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 8, no. 4, pp. 4109-4121, Dec. 2020. [Baidu Scholar]
Y. Huang, W. Huang, M. Li et al., “Steady-state control strategy of multi-terminal hybrid UHVDC,” in Proceeding of 2017 19th European Conference on Power Electronics and Applications, Warsaw, Poland, Sept. 2017, pp. 1-10. [Baidu Scholar]
G. Andersson and M. Hyttinen, “Skagerrak the next generation,” in Proceedings of CIGRE, Paris, France, Jul. 2015, pp. 1-9. [Baidu Scholar]
Z. Xu, S. Wang, and H. Xiao, “Hybrid high-voltage direct current topology with line commutated converter and modular multilevel converter in series connection suitable for bulk power overhead line transmission,” IET Power Electronics, vol. 9, no. 12, pp. 2307-2317, Oct. 2016. [Baidu Scholar]
Z. Xu, Z. Zhang, and W. Xu, “Research on application of LCC-MMC series hybrid HVDC topology for large scale clean energy base integration,” Power Capacitor & Reactive Power Compensation, vol. 43, no. 3, pp. 119-126, Jun. 2022. [Baidu Scholar]
W. Xu, Z. Zhang, and Z. Xu, “A hybrid HVDC topology suitable for large-scale pure clean energy power base transmission,” Electric Power, vol. 56, no. 4, pp. 17-27, Apr. 2023. [Baidu Scholar]
W. Liu, Z. Zhang, and Z. Xu, “Hybrid HVDC transmission scheme of pure renewable energy base,” Acta Energiae Solaris Sinica, vol. 44, no. 12, pp. 533-543, Dec. 2023. [Baidu Scholar]
X. Li, Z. Xu, and Z. Zhang, “Enhanced ride-through capability under rectifier-side AC fault for series LCC-MMC hybrid HVDC system,” IEEE Access, vol. 9, pp. 153050-153057, Nov. 2021. [Baidu Scholar]
N. Zhang, X. Li, Z. Zhang et al., “Overcurrent mechanism and suppression control for MMC arms in hybrid cascaded HVDC system,” CSEE Journal of Power and Energy Systems, doi: 10.17775/CSEEJPES.2022.00460 [Baidu Scholar]
Y. Chen and K. M. Smedley, “A cost-effective single-stage inverter with maximum power point tracking,” IEEE Transactions on Power Electronics, vol. 19, no. 5, pp. 1289-1294, Sept. 2004. [Baidu Scholar]
H. Gan, H. Xiao, and Y. Huang, “Control strategy and capacity selection of DRU-MMC hybrid converter for large-scale offshore wind power,” Automation of Electric Power Systems, doi: 10.7500/AEPS20230509003 [Baidu Scholar]
M. Szechtman, T. Wess, C. V. Thio et al., “First benchmark model for HVDC control studies,” Electra, vol. 135, no. 4, pp. 54-73, Apr. 1991. [Baidu Scholar]
IEEE Standard for Harmonic Control in Electric Power Systems, IEEE Standard 519-2022, pp. 1-31, Aug. 2022. [Baidu Scholar]