Abstract
Grid-forming (GFM) converters are recognized for their stabilizing effects in renewable energy systems. Integrating GFM converters into high-voltage direct current (HVDC) systems requires DC voltage control. However, there can be a conflict between GFM converter and DC voltage control when they are used in combination. This paper presents a rigorous control design for a GFM converter that connects the DC-link voltage to the power angle of the converter, thereby integrating DC voltage control with GFM capability. The proposed control is validated through small-signal and transient-stability analyses on a modular multilevel converter (MMC)-based HVDC system with a point-to-point (P2P) GFM-GFM configuration. The results demonstrate that employing a GFM-GFM configuration with the proposed control enhances the stability of the AC system to which it is connected. The system exhibits low sensitivity to grid strength and can sustain islanding conditions. The high stability limit of the system with varying grid strength using the proposed control is validated using a system with four voltage source converters.
TO mitigate the effects of climate change, a substantial shift towards the adoption of renewable energy sources has occurred. This shift has led to a considerable increase in the use of power electronic converters for integrating renewable energy sources into power transmission and distribution grids. The predominant method for managing these converters is the widely known and standardized grid-following (GFL) control, which relies on a phase-locked loop (PLL) for synchronization. However, an increase in GFL-controlled sources contributes to the destabilization of power grids, particularly due to their instability under weak grid conditions [
Recent advancements have highlighted grid-forming (GFM) control as a promising solution for addressing the stability challenges that hinder the widespread adoption of converter-interfaced resources. For example, the GFM control exhibits more stable behavior than the GFL control, particularly in weak AC grids [
In a point-to-point (P2P) high-voltage direct current (HVDC) link with voltage source converters (VSCs), as shown in

Fig. 1 P2P HVDC link with VSCs. (a) GFM-GFL configuration. (b) GFM-GFM configuration.
In addition, in a P2P HVDC link with GFM-GFL configuration, as illustrated in
DC voltage control with GFL converters is well known in the literature [
The first method is to cascade an external DC bus voltage control loop into a classical GFM control [
The second method is to control the dynamics of the DC-link voltage directly using the converter angle, omitting the use of active power feedback control. Several studies have proposed solutions to this dynamic control issue. Reference [
The control is applied to a modular multilevel converter (MMC)-based HVDC system with a GFM-GFM configuration to simulate a real application. Reference [
These improvements can be considered extensions of previously proposed control methods. The main novelty of this paper lies in showing the significant advantages of employing this type of control for AC grids to which it is connected. Specifically, an enhancement to small-signal stability is demonstrated for an AC grid with a high penetration of power electronic converters, and the islanding capability provided by the proposed GFM control is significantly improved.
The remainder of this paper is organized as follows. Section II describes the development of the proposed control and validation through an electromagnetic transient (EMT) analysis of a P2P HVDC link with GFM-GFM configuration. Section III highlights the stability advantages of the P2P HVDC link with GFM-GFM configuration using the proposed control as compared with the GFM-GFL configuration using a classical DC voltage control. Section IV extends the findings for a more complex four-VSC system. Finally, conclusions are given in Section V.
This section proposes the DC voltage control while retaining the GFM capability of the converter. Time-domain validation of the proposed control is also conducted through EMT analysis.
To design a system that offers DC voltage control with GFM capabilities, it is first necessary to define a system model.

Fig. 2 Simplified system model.
The primary role of the VSC is to modulate the DC bus voltage to produce a set of three-phase voltage . Based on the average model, the converter can be approximated as an ideal three-phase voltage source, the values of which depend on the control system of the converter. The transformer is represented by a leakage reactance , which maintains a lossless connection with the converter side.
In the steady state, each AC voltage and current can be expressed in phasor form (denoted by “”):
(1) |
where represents different voltages such as and , which are the steady-state values of and , respectively; is the phasor angle between and ; and and are the corresponding phasor angles to the voltages and , respectively. In addition, the virtual inductance is used to reduce the effects of phase shifts on power fluctuations in the converter [
Thus, the system can be represented by the electrical circuit shown in

Fig. 3 Static model of converter that includes virtual inductance. (a) Electrical circuit. (b) Phasor diagram.
With this circuit, the active power P can be derived in terms of the phase angle as:
(2) |
where is the phasor angle of the voltage .
From this, it can be deduced that active power control can be designed with different angles. In the time domain, each angle in the phasor corresponds to a time-varying angle as:
(3) |
where is the angular frequency.
Thus, and can be substituted with their corresponding time-domain angles and , respectively, and (2) can be rewritten as [
(4) |
Including the virtual inductance, the active power P can be defined as:
(5) |
where V is the virtual voltage; and is the corresponding time-domain angle of .
As this angle difference is very small, (5) can be written as:
(6) |
(7) |
Thus, in the steady state, using (6), a block of the converter model in the frequency domain is obtained, as shown in

Fig. 4 Model representation in frequency domain. (a) Static model of converter. (b) Static model of DC link. (c) Combined system model.
For simplicity, the DC cable is represented by a capacitor. The dynamics of the capacitor are given by (8), as shown in
(8) |
(9) |
(10) |
where and are the DC currents of the primary source and converter, respectively; is the DC power from the primary source; is the DC power of the converter; and and are the nominal power and DC voltage reference, respectively. Through (9), a block of the power dynamics of the DC link in the frequency domain is presented in
Given that there are no losses in the converter, the AC active power is equal to the DC power of the converter. Thus, when the block diagrams in
Based on the system model as shown in
The structure of the - controller is presented in Fig. , where and are the proportional and derivative gains of the controller, respectively; and is the estimated angular frequency. An angle reference is generated by the controller depending on the DC voltage deviation . This relationship can be derived from the structure presented in Fig. . Thus, is expressed as:
(11) |
As the real implementation of a derivative action can be sensitive to noise, a simple rearrangement of the control structure is performed to avoid the need for a derivative action of the signal. The modified structure of the - controller is shown in
(12) |

Fig. 5 Structure of - controller. (a) With derivative action. (b) With proportional action.
The combined system and control scheme is presented in
(13) |

Fig. 6 Closed-loop DC voltage-power angle control.
The DC voltage control is achieved by controlling the angle of the converter. In addition, synchronization of the converter to the grid is achieved using the proposed control.
The generalized transfer function of a second-order system without zeroes can be written as:
(14) |
where and are the oscillation frequency and damping ratio, respectively.
The control parameters are designed using the pole placement method. As the resulting system (13) is a second-order system, the tuning of gains and is performed by comparing the transfer function with the generalized second-order transfer function (14) based on the chosen damping ratio and oscillation frequency. These values can be obtained by assuming the values of V and Ve to be approximate 1. In addition, the transfer function indicates the need for the grid impedance value. A strong grid is assumed to tune the controller by setting .
The next subsection analyzes the dynamics of the system using the proposed control through EMT analysis.
To validate the proposed control, EMT analysis is performed on a P2P HVDC link with GFM-GFM configuration, as shown in
Parameter | Value | Parameter | Value |
---|---|---|---|
, | 1.044 GVA, 1.044 GVA | 400 kV, 400 kV | |
1 GW | 640 kV | ||
0.2 p.u. | 0.1 p.u. | ||
0.15 p.u. | 100 ms |
Accordingly, the proposed control is implemented using VSC 1. The parameters of the controller and Kd are calculated to correspond to the desired time response and damping ratio . This system is studied for several disturbance events.
At s, a p.u. step on the power reference is applied at the VSC 2 converter station. A time response of ms is chosen for the - controller. The resulting DC voltage and power at both stations are presented in

Fig. 7 Dynamic responses of P2P HVDC link after disturbances. (a) Case 1. (b) Case 2. (c) Case 3.
In this case, a phase jump is introduced at the voltage source of the Thevenin equivalent AC grid 1 at s. A time response of ms is chosen for the - controller, and the inertia value of s is chosen for VC-GFM control of the VSC 2. In
In this case, the response of the DC voltage is compared with various response time of the - controller. The response time and their corresponding and values are given in
(ms) | |||
---|---|---|---|
100 | 1 | 0.2387 | 0.0095 |
200 | 1 | 0.0597 | 0.0048 |
300 | 1 | 0.0265 | 0.0032 |
In this case, the behavior of the - controller is compared with that of an existing controller in the literature, wherein the DC grid voltage is controlled via the angle of the converter, referred to as the DC-link voltage synchronization control (DVSC) [

Fig. 8 Dynamic responses of P2P HVDC link after disturbances in Case 4. (a) Power of VSC 1. (b) Power of VSC 2. (c) DC voltage.
This validates the effectiveness of the proposed DC voltage control, which is successfully implemented in a P2P HVDC link with GFM-GFM configuration, achieving system stability without any conflicts with DC voltage control.
This section describes the advantages of an HVDC with GFM-GFM configuration with the proposed control as compared with that of the GFM-GFL configuration under the classical master-slave control in terms of stability, grid strength, and system islanding.
The studied system is an MMC-based HVDC system, as shown in

Fig. 9 Case study of MMC-based HVDC system.
The system includes two AC grid setups. On the AC grid 1 side, two MMCs are used, where operates under GFL control mode, whereas alternates between GFL and GFM control modes. Both MMCs are connected to the Thevenin equivalent via an overhead line. On the AC grid 2 side, operates in GFM control mode with VC-GFM control using the virtual synchronous machine (VSM) scheme [
The DC link is modeled using a DC capacitor at ms. The MMC-based HVDC system parameters are listed in
Component | Parameter | Value |
---|---|---|
MMC | 1.044 GVA, 1.044 GVA | |
400 kV, 400 kV | ||
1 GW | ||
640 kV | ||
Overhead line | Line impedance | 0.144 p.u. |
Line resistance | 0.0072 p.u. | |
Grid | 0.1 p.u. | |
10 | ||
DC link | 100 ms | |
- controller | 100 ms | |
1 | ||
VC-GFM controller | 5 s | |
1 |
Parameter | Value |
---|---|
Arm inductance | 0.18 p.u. |
Arm resistance | 0.005 p.u. |
Connection impedance | 0.15 p.u. |
Connection resistance | 0.005 p.u. |
Virtual impedance | 0.06 p.u. |
Energy in converter capacitance | 40 ms |
Energy control parameters , | 3 Hz, 1 |
PLL parameters , | 50 Hz, 1 |
The power flow is configured such that injects power, which is absorbed by the passive load and converter station.
This arrangement limits the power flowing through the impedance of AC grid 1. The grid impedance can be increased with limited reactive power requirements, thereby rendering the system suitable for sensitivity analysis.
The grid strength is expressed by the grid impedance . The test system is studied for different grid strengths on the AC grid 1 side by varying the grid inductance and resistance parameters and , while maintaining an ratio of . The analysis is first performed through an EMT simulation in MATLAB, and then a small-signal analysis is conducted to determine the system stability limit.
The behavior of the system is next described, in which AC grid 1 is considered a strong grid with p.u.. Two cases are analyzed. In one case, operates in GFL control mode, and therefore, the P2P HVDC link has a GFM-GFL configuration. In the second case, operates in GFM control mode with the - controller, creating a GFM-GFM configuration. Disturbances are introduced into the system, and the behavior of the system is analyzed in the two cases.
At s, a power variation of p.u. is applied at the converter station, and at s, a phase jump of is introduced at AC grid 1. The resulting active power at each converter station and the DC voltage are obtained, as shown in

Fig. 10 Dynamic response in the case of a strong grid with p.u.. (a) Power of MMC11. (b) Power of MMC2. (c) Power of MMC12. (d) DC voltage.
Next, is increased to p.u. () to consider AC grid 1 as a weak grid. When operates in GFL control mode, the AC system becomes unstable, as shown in

Fig. 11 Dynamic responses in the case of a weak grid with p.u.. (a) MMC11 in GFL control mode. (b) MMC11 in GFM control mode.
Thus, as expected, utilizing a GFM-GFL configuration makes the system more sensitive to grid strength. By contrast, employing a GFM-GFM configuration with the proposed control enhances the stability of the system in terms of grid sensitivity.
To analyze the stability limit when employing the GFM-GFM and GFM-GFL configurations, a parametric sensitivity analysis is next performed under a small-signal stability analysis.
The small-signal stability limit is next examined for various grid strengths in the cases of GFM-GFL and GFM-GFM configurations.
To deepen the small-signal stability analysis of the system, a linearized state-space model is created. The state-space model of the system is developed by associating the state-space models of different subsystems, which are three MMCs, a DC cable, and two AC grids. The methodology presented in [
The system is linearized around the same operating point, as shown in
The stability limit of the system is explored by varying the grid impedance parameter , thereby varying the grid strength. The stability limit is recognized as the foremost operating point, where at least one eigenvalue of the linearized system exhibits a positive real part.
In the first case of the GFM-GFL configuration, the grid inductance of the system varies from to p.u., and the resulting eigenvalue trajectories are obtained, as shown in

Fig. 12 Parametric sweep for change in grid strength in the case of with GFL control.

Fig. 13 Participation factors of different states contributing to eigenvalues with p.u..
Next, the analysis of the stability limit of GFM-GFM configuration with the proposed control is conducted. The grid impedance varies from to p.u., and the resulting eigenvalues are obtained, as shown in

Fig. 14 Parametric sweep for change of grid strength in the case of with GFM control.
The participation factors of different states contributing to the most oscillatory pole/eigenvalue with p.u. are presented in

Fig. 15 Participation factors of different states contributing to the most oscillatory pole/eigenvalue with p.u..
As observed, the dominant states are primarily associated with , indicating less interaction between the converters and grids. In fact, the GFM-GFM setup with the proposed control exhibits minimal sensitivity to grid strength and represents a highly stable configuration.
Thus far, the stability with respect to grid strength has been discussed. The stability of the system is next analyzed in the case of an islanding situation with loss of AC grid 1. Both AC grid impedances are low, i.e., p.u..
In the first case, operates in GFL control mode. At s, a power disturbance of p.u. is applied at the converter station. As a result, as shown in

Fig. 16 Dynamic response in the case of loss of AC grid 1. (a) MMC11 in GFL control mode. (b) MMC11 in GFM control mode.
In the second case, the operates in GFM control mode, resulting in a GFM-GFM configuration with the proposed control. During the same islanding event at s, the behavior of the GFM control significantly differs from that of the GFL control. Due to the voltage source characteristics, the GFM control instantaneously adjusts its power to match the power required by the remaining AC grid 1. This leads to an imbalance in the DC bus power between the two stations, resulting in fast DC bus voltage variation. Once the DC voltage reaches its lower limit of , the proposed control is shifted to the converter station [
Therefore, we can conclude that in the event of a large transient loss of an AC grid, the system is stable under the GFM-GFM configuration with the proposed control. Thus, the overall stability of the system is enhanced.
A four-VSC system is next introduced to demonstrate previous findings. A single-line diagram of the system is presented in

Fig. 17 Four-VSC system.
WP 1 and WP 2 are consolidated representations of numerous generators and are GFL-controlled. HVDC 1 consists of two VSCs connected through a DC cable. VSC 2 is in GFM control mode, and VSC 1 is in GFM control mode with the proposed control or GFL control mode with classical master-slave control. However, the HVDC 2 is assumed to have a constant DC voltage with a GFL-controlled VSC.
The converter parameters are listed in
Component | (MVA) | (MW) |
---|---|---|
WP 1 | 2400 | 2300 |
WP 2 | 2400 | 2300 |
HVDC 1 | 1200 | 1150 |
HVDC 2 | 1700 | 1630 |
Both WPs are connected to the grid radially using six 225 kV cables of 50 km in length and six parallel transformers to handle the maximum output of each WP. The cables represent the AC connections of the offshore wind farms. The 400 kV segment of the transmission grid is interconnected in a meshed configuration, enhancing its reliability and flexibility. The system electrically incorporates multiple closely spaced VSCs to account for potential interactions.
The system is connected to an external grid via the Thevenin equivalent at bus C. The Thevenin voltage source stabilizes the system frequency to its nominal value under steady-state conditions. In addition, the strength of the external grid is adjustable in terms of short-circuit power.
The purpose of this paper is to examine and verify the stabilizing effects in GFM control mode with the proposed control. The system stability is evaluated based on the minimum short-circuit power of the external grid. The corresponding Thevenin reactance can be adjusted accordingly.
The operating points of the converters are listed in
Component | Injected power (MW) |
---|---|
WP 1 | 1500 |
WP 2 | 1500 |
HVDC 1 | -1120 |
HVDC 2 | -1600 |
When the short-circuit power from the external Thevenin equivalent at bus C is set to be 17.78 GVA, the system is found to be unstable when the VSC 1 is controlled in GFL control mode with the classical master-slave DC voltage control. This is demonstrated by applying a phase jump of at the Thevenin equivalent voltage source. The resulting power at all the converter stations and the DC voltage of HVDC 1 are obtained, as shown in

Fig. 18 Dynamic response of 4-VSC system after phase jump. (a) VSC 1 in GFL control mode. (b) VSC 1 in GFM control mode.
However, under the same conditions, the system remains stable when VSC 1 of HVDC 1 is controlled in GFM control mode with the - controller. As Fig. shows, the DC voltage of HVDC 1 is maintained at its reference value at a steady state, and the power at all stations returns to its initial value after the phase jump.
This further confirms the previous findings regarding the stabilizing property of GFM control mode with the proposed control. Thus, an HVDC link with GFM-GFM configuration using the proposed control enhances the stability of the system and offers an overall more stable system.
This paper proposes a rigorous DC voltage control design for GFM converters and validates its performance in a P2P HVDC link with GFM-GFM configuration. The proposed control is an extension of the GFM principle. It has two aims: controlling the DC bus voltage and synchronizing the converter with the grid. Thus, both DC voltage control and GFM capabilities are provided. The stabilizing effects and additional benefits of the proposed control are demonstrated through a comparison of the GFM-GFM and GFL-GFM configurations under complex case studies. The results indicate that the GFM-GFM configuration with the proposed control achieves a higher stability limit in weak AC grids. In addition, an eigenvalue analysis highlights that the proposed control brings stability and avoids unwanted interactions between the converter and AC power system. Furthermore, the system remains stable in islanded scenarios with AC grid loss when using a GFM-controlled converter with the proposed control.
Further analysis is required to examine the behavior of the system under large disturbances such as multiple fault scenarios. Moreover, the proposed control for integrating the GFM control with DC voltage control is easily adaptable for MTDC systems. The proposed control can be extended to a master-slave MTDC system, where accounts for all the energy stored within the MTDC system. It is expected to enhance the overall stability of MTDC system to a significant degree but requires further investigation.
References
A. Gole and J. Zhou, “VSC transmission limitations imposed by AC system strength and AC impedance characteristics,” in Proceedings of 10th IET International Conference on AC and DC Power Transmission (ACDC 2012), Birmingham, UK, Dec. 2012, pp. 1-6. [Baidu Scholar]
C. Cardozo, T. Prevost, S.-H. Huang et al., “Promises and challenges of grid forming: transmission system operator, manufacturer and academic view points,” Electric Power Systems Research, vol. 235, p. 110855, Oct. 2024. [Baidu Scholar]
X. Wang, M. G. Taul, H. Wu et al., “Grid-synchronization stability of converter-based resources – an overview,” IEEE Open Journal of Industry Applications, vol. 1, pp. 115-134, Aug. 2020. [Baidu Scholar]
T. K. Vrana, J. Beerten, R. Belmans et al., “A classification of DC node voltage control methods for HVDC grids,” Electric Power Systems Research, vol. 103, pp. 137-144, Oct. 2013. [Baidu Scholar]
Y. J. Hafner, A. Abdalrahman, M. Monge et al., “Operating experiences and insights in future applications of grid forming capability of VSC HVDC,” in Proceedings of 2023 8th IEEE Workshop on the Electronic Grid (eGRID), Karlsruhe, Germany, Oct. 2023, pp. 1-8. [Baidu Scholar]
S. S. Sayed and A. M. Massoud, “General classification and comprehensive performance assessment of multi-objective DC voltage control in multi-terminal HVDC networks,” IEEE Access, vol. 9, pp. 34454-34474, Feb. 2021. [Baidu Scholar]
P. Rault, “Dynamic modeling and control of multi-terminal HVDC grids,” Ph.D. dissertation, Ecole Centrale de Lille, Lille, France, 2014. [Baidu Scholar]
R. Rosso, X. Wang, M. Liserre et al., “Grid-forming converters: control approaches, grid-synchronization, and future trends – a review,” IEEE Open Journal of Industry Applications, vol. 2, pp. 93-109, Apr. 2021. [Baidu Scholar]
L. Zhao, Z. Jin, and X. Wang, “Transient performance evaluation of grid-forming control for railway traction converters considering inter-phase operation,” in Proceedings of 2021 IEEE Energy Conversion Congress and Exposition (ECCE), Vancouver, Canada, Oct. 2021, pp. 2958-2963. [Baidu Scholar]
J. Guo, Y. Chen, W. Wu et al., “Wideband dq-frame impedance modeling of load-side virtual synchronous machine and its stability analysis in comparison with conventional PWM rectifier in weak grid,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 9, pp. 2440-2451, Apr. 2021. [Baidu Scholar]
L. Harnefors, M. Hinkkanen, U. Riaz et al., “Robust analytic design of power-synchronization control,” IEEE Transactions on Industrial Electronics, vol. 66, pp. 5810-5819, Aug. 2019. [Baidu Scholar]
L. Zhang, L. Harnefors, and H.-P. Nee, “Power-synchronization control of grid-connected voltage-source converters,” IEEE Transactions on Power Systems, vol. 25, pp. 809-820, May 2010. [Baidu Scholar]
R. Wang, L. Chen, T. Zheng et al., “VSG-based adaptive droop control for frequency and active power regulation in the MTDC system,” CSEE Journal of Power and Energy Systems, vol. 3, no. 3, pp. 260-268, Oct. 2017. [Baidu Scholar]
E. Rokrok, T. Qoria, A. Bruyere et al., “Integration of a storage device to the DC bus of a grid-forming controlled HVDC interconnection,” Electric Power Systems Research, vol. 212, p. 108601, Nov. 2022. [Baidu Scholar]
A. E. Leon and J. M. Mauricio, “Virtual synchronous generator for VSC-HVDC stations with DC voltage control,” IEEE Transactions on Power Systems, vol. 38, pp. 728-738, Jan. 2023. [Baidu Scholar]
L. Huang, H. Xin, Z. Wang et al., “A virtual synchronous control for voltage-source converters utilizing dynamics of DC-link capacitor to realize self-synchronization,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 5, pp. 1565-1577, Dec. 2017. [Baidu Scholar]
G. Li, F. Ma, Y. Wang et al., “Design and operation analysis of virtual synchronous compensator,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 8, pp. 3835-3845, Dec. 2020. [Baidu Scholar]
L. Zhao, Z. Jin, and X. Wang, “Small-signal synchronization stability of grid-forming converters with regulated DC-link dynamics,” IEEE Transactions on Industrial Electronics, vol. 70, pp. 12399-12409, Dec. 2023. [Baidu Scholar]
L. Zhao, Z. Jin, and X. Wang, “Analysis and damping of low-frequency oscillation for DC-link voltage-synchronized VSCs,” IEEE Transactions on Power Electronics, vol. 38, pp. 8177-8189, July 2023. [Baidu Scholar]
L. Zhao, Z. Jin, and X. Wang, “Transient stability of grid-forming converters with flexible DC-link voltage control,” in Proceedings of 2022 International Power Electronics Conference, Himeji, Japan, May 2022, pp. 1648-1653. [Baidu Scholar]
X. Fan, Y. Chi, and Z. Wang, “Frequency support scheme of grid-forming based hybrid cascaded HVDC integrated wind farms,” IET Generation, Transmission & Distribution, vol. 18, pp. 446-459, Feb. 2024. [Baidu Scholar]
K. Shinoda, A. Benchaib, J. Dai et al., “Virtual capacitor control: mitigation of DC voltage fluctuations in MMC-based HVDC systems,” IEEE Transactions on Power Delivery, vol. 33, pp. 455-465, Feb. 2018. [Baidu Scholar]
S. Samimi, “Modular multilevel converter model and control for the integration to the grid system,” Ph.D. dissertation, Ecole Centrale de Lille, Lille, France, 2016. [Baidu Scholar]
T. Qoria, “Grid-forming control to achieve a 100% power electronics interfaced power transmission systems,” Ph.D. dissertation, Ecole Nationale Supérieure d’Arts et Métiers, Lille, France, 2020. [Baidu Scholar]
S. Samimi, F. Gruson, P. Delarue et al., “MMC stored energy participation to the DC bus voltage control in an HVDC link,” IEEE Transactions on Power Delivery, vol. 31, pp. 1710-1718, Aug. 2016. [Baidu Scholar]
J. Freytes, S. Akkari, J. Dai et al., “Small-signal state-space modeling of an HVDC link with modular multilevel converters,” in Proceddigns of 2016 IEEE 17th Workshop on Control and Modeling for Power Electronics (COMPEL), Trondheim, Norway, Jun. 2016, pp. 1-8. [Baidu Scholar]
CIGRE, “Control methodologies for direct voltage and power flow an a meshed HVDC grid,” Tech. Rep., CIGRE WG B4.58, 2017. [Baidu Scholar]