Abstract
Fault currents emanating from inverter-based resources (IBRs) are controlled to follow specific references to support the power grid during faults. However, these fault currents differ from the typical fault currents fed by synchronous generators, resulting in an improper operation of conventional phase selection methods (PSMs). In this paper, the relative angles between sequence voltages measured at the relay location are determined analytically in two stages
① a short-circuit analysis is performed at the fault location to determine the relative angles between sequence voltages; and ② an analysis of the impact of transmission line on the phase difference between the sequence voltages of relay and fault is conducted for different IBR controllers. Consequently, new PSM zones based on relative angles between sequence voltages are devised to facilitate accurate PSM regardless of the fault currents, resistances, or locations of IBR. Comprehensive time-domain simulations confirm the accuracy of the proposed PSM with different fault locations, resistances, types, and currents.
THE penetration of renewable energy sources (RESs) is increasing in both transmission and distribution networks due to their merits in reducing fuel consumption and greenhouse gas emission [
Phase selection is an essential protection function that determines the faulty phase(s). PSM is considered as an imperative protection function in transmission systems as it is a prerequisite function for distance, single-pole tripping, and fault location [
Some researchers pursue solving the phase selection problem by controlling the IBR to inject adequate fault current. In [
On the other hand, other researchers attempt to modify conventional PSMs to enhance their security and dependability during faults that emerge from IBRs. Reference [
1) The practical range for relative angles is elucidated between sequence voltages calculated at the fault location.
2) The impacts of TL impedance and IBR controllers on the relative angles are interpreted between similar sequence voltages measured at the fault and relay locations through analytical methods.
3) A comprehensive PSM is proposed based on comparing sequence angles between NS and ZS voltages and between NS and PS voltages to ensure the precise and secure phase selection for different IBR controllers, fault resistances, and fault locations.
In this section, short-circuit analyses are performed on a sample power system shown in

Fig. 1 Structure of sample power system.
In this subsection, the sequence network for an a-phase-to-ground (AG) fault is analyzed, as a representative for SLG faults, to determine the relation between the sequence fault voltages, i.e., , , and , and their relative angles. As shown in
(1) |

Fig. 2 Sequence circuit at fault location for an AG fault.
where , , and are the NS, ZS, and PS Thevenin impedances at the fault location, respectively; and is the ground fault resistance.
From (1), the relation between and and that between and are given by:
(2) |
Hence, and are given by:
(3) |
It is worth mentioning that in a typical transmission system, the PS, NS, and ZS equivalent impedance angles are almost equal, and they are around [

Fig. 3 range for an AG fault.
It can be observed from
As a representative of LLG faults, the sequence network for a b-phase-to-c-phase-to-ground (BCG) fault is analyzed, as shown in

Fig. 4 Sequence circuit at fault location for a BCG fault.
(4) |
where is the arc resistance between faulted phases. Hence, for solid faults, and are given by:
(5) |
However, to determine the values of and at different values of and ,

Fig. 5 Relative sequence angles for a BCG fault. (a) . (b) .
In this subsection, the sequence network for a b-phase-to-c-phase (BC) fault is analyzed. The relation between and is derived from
(6) |

Fig. 6 Sequence circuit at fault location for a BC fault.
Thereafter, the ratio between and is determined by:
(7) |
Consequently, it can be inferred that is susceptible to . If , . On the other hand, if is noticeable,

Fig. 7 range for a BC fault.
The TL introduces a voltage phase shift between sequence voltages measured at the relay and fault locations. This phase shift is negligible in conventional power grids; however, its impact is notable in the case of IBRs because their current angles differ from those of traditional sources. Hence, the impact of TLs should be analyzed to determine the phase angle between the NS and ZS voltages measured at the relay location, i.e., , and that between NS and PS voltages, i.e., .
The IBR is usually integrated into the power grid through an interfacing transformer, e.g., a delta/star-ground transformer. This transformer connection prevents any ZS current injection from the IBRs from flowing to the fault. Thus, the only source of ZS current that flows through the relay to the fault is from the ground path in the transformer. The equivalent single-line diagram (SLD) of the ZS circuit is illustrated in

Fig. 8 Equivalent SLD of ZS circuit.
By analyzing
(8) |
where is the equivalent ZS impedance of transformer; and is the equivalent ZS impedance between the relay and the fault location. Since , the relative angle between the ZS voltage measured at the relay and fault location, i.e., , is approximately equal to zero. This angle can be theoretically neglected, but its effect is considered as a margin when setting the proposed PSM zones.
In this subsection, the range of the phase shift between the NS voltages of relay and fault, i.e., , and that between the PS voltages of relay and fault, i.e., , are analyzed for different IBR controllers.
The controller is designed to inject only PS current, where a proportional-integral controller is used to track the reference current, and a feed-forward voltage is utilized to enhance the dynamic response of the controller. However, it diminishes the NS current similar to the balanced-current control strategy, i.e., . Hence, the effect of is abandoned in both balanced and conventional controllers.
On the other hand, the full range of the PS voltage phase shift between the fault and relay location is required to be analyzed. To determine the maximum angle of , the system is studied at the furthest point from the fault, which is the IBR location, because increasing the impedance between the relay and fault location increases the phase shift.

Fig. 9 Equivalent SLD of PS circuit.
Using
(9) |
where is the PS voltage angle measured at the fault locations; and is the PS impedance angle.
By decomposing (9) into real and imaginary parts and applying trigonometric function properties, can be calculated as:
(10) |
To determine the maximum range of , is selected equal to the maximum current limit of IBR, i.e., [
1) For SLG fault, the minimum value of is p.u.. Thus, for bolted fault, the maximum value of in bolted SLG faults changes from to .
2) For LLG faults, the minimum value of p.u.. Thus, for a negligible value of , the maximum variation of for bolted LLG faults changes from to .
3) For LL faults, the minimum value of is .. Hence, for bolted LL faults, the range of is [, ].
The maximum value of is selected to be ., which is the threshold for a PS relay to operate. Thus, for high-resistive faults, i.e., high in SLG and high in LL(G) faults, the range of is [, ]. Consequently, when the IBR injects a balanced current, the TL effect on the difference between and , i.e., , and that between and , i.e., , are concluded in
Fault type | |||||
---|---|---|---|---|---|
AG | Bolted | 0 | [-2.3, 12.8] | [-12.8, 2.3] | 0 |
High | 0 | [-1.7, 9.5] | [-9.5, 1.7] | 0 | |
BCG | Bolted | 0 | [-4.5, 26.3] | [-26.3, 4.5] | 0 |
High | 0 | [-4.5, 26.3] | [-26.3, 4.5] | 0 | |
High | 0 | [-1.7, 9.5] | [-9.5, 1.7] | 0 | |
BC | Bolted | 0 | [-3, 17.2] | [-17.2, 3] | 0 |
High | 0 | [-1.7, 9.5] | [-9.5, 1.7] | 0 |
The controller of IBR is designed to inject both PS and NS currents according to recent GC specifications. Thus, and are determined by studying the NS and PS circuits, respectively.
In the NS circuit, the IBR is controlled to inject NS current at the IBR terminal, while the conventional power grid can be represented by a constant impedance. Thus, the reduced equivalent SLD of NS circuit can be depicted, as shown in

Fig. 10 Equivalent SLD of NS circuit.
(11) |
Consequently, the value of can be inferred by:
(12) |
Recent GCs impose the injection of NS current to reduce unbalanced voltage during asymmetric faults. For instance, the German GC, i.e., VDE-AR-N 4120-GC [
(13) |
where is an inductive NS reactive current; and is a constant that can be selected from the range of []. Thus, the maximum NS current is equal to , while . By substituting , and assuming in (12), the maximum value of is . It is worth mentioning that . Thus, the actual maximum value of is less than . The actual maximum value of can be determined by substituting , , and in (11) as:
(14) |
By solving (14), the actual maximum value of is , which could be lower at bolted faults because the current is limited to avoid exceeding the maximum current limit. However, this reduction is small; thus, the maximum value of is considered equal to for both bolted and high-resistive faults, whereas the minimum value is at faults close to the relay location.
Similarly, the PS circuit can be analyzed as in Subsection III-B-1), where the PS current magnitude and power factor are determined from GC requirements. In the German GC, the IBR should inject positive-reactive power according to:
(15) |
where is a capacitive PS reactive current. In addition, the IBR should inject PS active current to achieve the maximum current limit. Thus, for bolted faults, is equal to when , but it could be reduced to during SLG faults for . At high-resistive faults, i.e., , is equal to and when is equal to 2 and 6, respectively. It is worth mentioning that is approximately equal to at high-resistive faults, and this value is reduced at low-resistive faults to avoid exceeding the maximum current limit, because the IBR is injecting PS and NS currents simultaneously.
Consequently, for bolted faults, approaches its maximum value when and ., while the minimum value occurs when . On the other hand, during high-resistive faults, reaches its maximum value when equals . Accordingly, when the IBR is controlled according to new GCs, the TL effects on and can be summarized, as shown in
Type | |||||
---|---|---|---|---|---|
AG | Bolted | [0, 3.8] | [1.7, -2.3] | [-1.7, 6.1] | [0, 3.8] |
High | [0, 3.8] | [0, 8.6] | [0, -5.1] | [0, 3.8] | |
BCG | Bolted | [0, 3.8] | [0, -4.5] | [0, 8.3] | [0, 3.8] |
High | [0, 3.8] | [0, -4.5] | [0, 8.3] | [0, 3.8] | |
High | [0, 3.8] | [0, 8.6] | [0, -5.1] | [0, 3.8] | |
BC | Bolted | [0, 3.8] | [0, -3] | [0, 6.8] | |
High | [0, 3.8] | [0, 8.6] | [0, -5.1] |
Active and reactive power ripples introduce challenges in the IBR control and generate oscillations in the direct current (DC) link voltage, which could reduce the lifetime of the DC link capacitor. Thus, some scholars suggest injecting NS current with specific magnitude and angle to eliminate either active or reactive power ripples. However, they do not consider the reliable operation of protection functions in their controllers. The instantaneous active and reactive power can be deduced from the instantaneous PS and NS currents and voltages as follows:
(16a) |
(16b) |
where and are the instantaneous active and reactive power, respectively; and are the oscillating components of active and reactive power at double the nominal frequency, respectively; is lagging the PS voltage measured at the relay by ; and is leading the NS voltage measured at the relay by .
One of the methods to eliminate active power oscillation is obtained by setting and as follows:
(17) |
Consequently, is inferred by:
(18) |
On the other hand, a method to eliminate reactive power ripples is inferred by calculating and using:
(19) |
Hence, should be given by:
(20) |
It can be observed that is the same for active and reactive power ripple elimination; thus, for these two control strategies has the same expression. By substituting (17) into (12), is formulated by:
(21) |
Since the DG fault current is limited, it is assumed that . Then, by comparing the result with (10), and are deduced by:
(22) |
Since IBRs inject PS and NS currents simultaneously, is limited to avoid exceeding the current limit of IBR. By considering current limitations for and , can be formulated by (23), as elaborated in Appendix B.
(23) |
Since ranges between and , varies from to when the system is controlled to eliminate active power ripples. Thus, for bolted faults, is as follows.
1) For SLG faults, p.u.. while p.u.. Thus, the range of is .
2) For LLG faults, .. Thus, the range of is .
3) For LL faults, . Thus, the range of is .
Nevertheless, during high-resistive faults, i.e., , will vary from to .
On the other hand, for eliminating reactive power ripples varies from to . Thus, is equal to , and the effect of the TL on can be neglected.
Fault type | |||||
---|---|---|---|---|---|
AG | Bolted | [-9.7, -1.7] | [9.7, 1.7] | [-19.4, 3.4] | [-9.7, 1.7] |
High | [-9.1, -1.6] | [9.1, 1.6] | [-18.2, 3.2] | [-9.1, 1.6] | |
BCG | Bolted | [-14.9, -2.6] | [14.9, 2.6] | [-29.8, 5.2] | [-14.9, 2.6] |
High | [-14.9, -2.6] | [14.9, 2.6] | [-29.8, 5.2] | [-14.9, 2.6] | |
High | [-9.1, -1.6] | [9.1, 1.6] | [-18.2, 3.2] | [-9.1, 1.6] | |
BC | Bolted | [-9.9, -1.8] | [9.9, 1.8] | [-19.8, 3.6] | |
High | [-9.1, -1.6] | [9.1, 1.6] | [-18.2, 3.2] |
Fault type | |||||
---|---|---|---|---|---|
AG | Bolted | [-1.7, 9.7] | [-1.7, 9.7] | [0, 0] | [-1.7, 9.7] |
High | [-1.6, 9.1] | [-1.6, 9.1] | [0, 0] | [-1.6, 9.1] | |
BCG | Bolted | [-2.6, 14.9] | [-2.6, 14.9] | [0, 0] | [-2.6, 14.9] |
High | [-2.6, 14.9] | [-2.6, 14.9] | [0, 0] | [-2.6, 14.9] | |
High | [-1.6, 9.1] | [-1.6, 9.1] | [0, 0] | [-1.6, 9.1] | |
BC | Bolted | [-1.8, 9.9] | [-1.8, 9.9] | [0, 0] | |
High | [-1.6, 9.1] | [-1.6, 9.1] | [0, 0] |
According to the analysis conducted in Sections II and III, the ranges for and are determined to allow accurate PSM for different fault resistances, IBR controllers, and fault locations. First, and are determined for bolted and high-resistive faults, as illustrated in Section II. Then, full ranges of and are determined for bolted and high-resistive faults, respectively, by selecting the maximum and minimum shifts deduced from Section III for different IBR controllers. Hence, the full range of and for bolted and high-resistive faults are determined individually, as shown in
Fault type | (full range) | (full range) | |||||||
---|---|---|---|---|---|---|---|---|---|
AG | Bolted | [-20, 6] | [-10, 10] | -180 | 0 | [-200, -174] | [-10, 10] | [-200, -96] | [-10, 10] |
High | [-19, 4] | [-10, 10] | -100 | 0 | [-119, -96] | [-10, 10] | |||
BCG | Bolted | [-30, 9] | [-15, 15] | 0 | 0 | [-30, 9] | [-15, 15] | [30, 72] | [-88, 10] |
High Rg | [-30, 9] | [-15, 15] | 0 | -73 | [-30, 9] | [-88, -65] | |||
High Rph | [-19, 4] | [-10, 10] | 68 | 0 | [49, 72] | [-10, 10] | |||
BC | Bolted | [-20, 7] | 0 | [-20, 7] |
[ | ||||
High | [-19, 4] | 68 | [49, 76] |
It can be deduced that for AG and BCG faults can vary from to and from to , respectively; thus, these zones can be combined. Then, by extending the zone width to , zones for AG and BCG faults range from to . Subsequently, BG and CAG faults can be determined by shifting the BG/CAG zone by , while CG and ABG are deduced by shifting the BG/CAG zones by . The proposed zones are depicted in

Fig. 11 Proposed zones.
It can be observed from

Fig. 12 Proposed zones. (a) SLG zones. (b) LL(G) zones.
First, is compared with its proposed zones; thus, two types of faults, e.g., AG and BCG, can be determined. Thereafter, is used to differentiate between SLG and LLG faults. Hence, the fault type is pinpointed, e.g., if is within the AG zone; then, an AG fault is identified, but if it is located in the BCG zone; then, a BCG fault is determined. The two types of faults determined by zones have different zones when using . Thus, the fault type can be determined effectively.
The accuracy of the fault analysis and the effectiveness of the proposed PSM are verified using PSCAD/EMTDC simulations, which are carried out for several fault locations, resistances, types, and IBR controllers.

Fig. 13 SLD of test system.
Fault type | Fault at 50% of | Fault at bus B5 | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AG | 0 | 180.0 | 173.3 | -6.7 | 0.0 | 0.0 | 0.0 | 180.3 | 167.8 | -12.5 | 0.0 | 0.0 | 0.0 | |
50 | -127.6 | -130.9 | -3.3 | 0.3 | 0.4 | 0.1 | -118.7 | -126.3 | -7.6 | 0.2 | 0.5 | 0.3 | ||
BCG | 0 | 0 | 0.0 | -14.7 | -14.7 | 0.0 | 0.0 | 0.0 | 0.0 | -24.9 | -24.9 | 0.0 | -0.1 | -0.1 |
0 | 40 | 61.1 | 55.5 | -5.6 | -6.5 | -6.5 | 0.0 | 73.1 | 64.3 | -8.8 | 5.6 | 6.2 | 0.6 | |
50 | 0 | 0.0 | -9.0 | -9.0 | -66.3 | -66.0 | 0.0 | 0.0 | -17.9 | -17.9 | -68.9 | -69.0 | -0.1 | |
BC | 0 | 0.0 | -8.6 | -8.6 | 0.0 | -17.4 | -17.4 | |||||||
40 | 55.3 | 50.1 | -5.2 | 67.0 | 58.6 | -8.4 |
Fault type | Fault at 10% of | Fault at 50% of | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
BG | 0 | -60.0 | -59.8 | 0.2 | -120 | -120 | 0 | -60.0 | -59.0 | 1.0 | -120.0 | -120 | 0.0 | |
50 | -8.6 | -8.5 | 0.1 | -120 | -120 | 0 | -8.6 | -8.5 | 0.1 | -120.0 | -120 | -0.1 | ||
CAG | 0 | 0 | 120.0 | 120.8 | 0.8 | -120 | -120 | 0 | 120.0 | 122.3 | 2.3 | -120.0 | -120 | 0.0 |
0 | 40 | 169.0 | 169.6 | 0.2 | -148 | -148 | 0 | -178.9 | -178.0 | 0.9 | -127.0 | -127 | 0.0 | |
50 | 0 | 120.0 | 120.3 | 0.3 | 167 | 167 | 0 | 120.0 | 121.5 | 1.5 | 173.7 | 174 | 0.0 | |
CA | 0 | 120.0 | 120.3 | 0.3 | 120.0 | 121.4 | 1.4 | |||||||
40 | 168.0 | 168.1 | 0.2 | 175.3 | 176.1 | 0.8 |

Fig. 14 Performance of proposed PSM during conventional controller. (a) A BCG fault at bus B5. (b) A BG fault at of .
Figure represents a BCG fault at bus B5 when the IBR injects a unity power factor current. The results show that both and settle correctly within the proposed zones in less than half a cycle. In addition, and are placed in their zones with adequate margins from their zone limits, i.e., about . On the other hand,
In this subsection, the precision of the proposed PSM when the IBR is controlled to follow the new German GC is validated. Moreover, the correctness of the mathematical analysis, which studies the TL effect on and , is confirmed.
Fault type | Fault at 50% of | Fault at bus B5 | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
CG | 0 | 61.0 | 63.5 | 2.5 | 122.0 | 123.7 | 1.7 | 60.5 | 64.8 | 4.3 | 121.0 | 124.0 | 3.0 | |
50 | 117.4 | 116.6 | -0.8 | 122.0 | 123.7 | 1.7 | 123.2 | 120.7 | -2.5 | 121.0 | 125.0 | 3.6 | ||
ABG | 0 | 0 | -120.0 | -116.0 | 3.7 | 120.0 | 121.7 | 1.7 | -120.0 | -113.8 | 6.2 | 120.0 | 123.0 | 2.8 |
0 | 20 | -67.5 | -64.6 | 2.9 | 122.0 | 123.5 | 1.7 | -56.4 | -51.9 | 4.5 | 130.0 | 133.0 | 3.0 | |
50 | 0 | -120.0 | -117.0 | 2.9 | 53.7 | 55.4 | 1.7 | -120.0 | -115.1 | 4.9 | 51.1 | 53.9 | 2.8 | |
AB | 0 | -120.0 | -117.0 | 2.8 | -120.0 | -115.2 | 4.8 | |||||||
20 | -76.7 | -74.2 | 2.5 | -64.7 | -60.6 | 4.1 |
Fault type | Fault at 10% of | Fault at 50% of | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
BG | 0 | -59.5 | -59.4 | 0.1 | -118 | -118 | 0.2 | -59.4 | -61.1 | -1.7 | -119 | -118.0 | 0.8 | |
50 | -3.5 | -4.0 | -0.5 | -118 | -118 | 0.1 | -5.2 | -8.2 | -3.0 | -119 | -118.0 | 0.8 | ||
CAG | 0 | 0 | 120.0 | 120.8 | 0.8 | -120 | -120 | 0.2 | 120.0 | 122.3 | 2.3 | -120 | -119.0 | 0.8 |
0 | 20 | 161.5 | 161.1 | -0.4 | -142 | -141 | 0.2 | 168.2 | 166.0 | -2.2 | -122 | -121.0 | 0.7 | |
50 | 0 | 120.0 | 120.4 | 0.4 | 167 | 168 | 0.2 | 120.0 | 121.5 | 1.5 | 174 | 174.5 | 0.8 | |
CA | 0 | 120.0 | 120.3 | 0.3 | 120.0 | 121.4 | 1.4 | |||||||
20 | 152.2 | 152.0 | -0.2 | 158.5 | 157.3 | -1.2 |

Fig. 15 Performance of proposed PSM when IBR follows new German GC for a fault at of . (a) A CG fault. (b) A CAG fault.
In this subsection, the mathematical analysis and the accuracy of proposed PSM are verified when the IBR is controlled to eliminate either active or reactive power ripples.
Fault type | Elimination of active power ripples | Elimination of reactive power ripples | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AG | 0 | 177.9 | 160.9 | -17.0 | -3.7 | -11.9 | -8.2 | 182.4 | 182.4 | 0.0 | 4.2 | 12.6 | 8.4 | |
50 | -123.0 | -132.5 | -9.8 | -3.8 | -10.5 | -6.7 | -116.0 | -116.0 | -0.2 | 3.6 | 10.7 | 7.1 | ||
BCG | 0 | 0 | 0.0 | -24.6 | -24.6 | 0.0 | -11.7 | -11.7 | 0.0 | 0.0 | 0.0 | 0.0 | 13.7 | 13.7 |
0 | 40 | 68.3 | 53.0 | -15.3 | 4.0 | -3.5 | -7.5 | 74.0 | 73.9 | -0.1 | 8.8 | 17.0 | 8.2 | |
50 | 0 | 0.0 | -18.5 | -18.5 | -68.9 | -77.8 | -8.9 | 0.0 | 0.0 | 0.0 | -68.9 | -58.9 | 10.0 | |
BC | 0 | 0.0 | -18.2 | -18.2 | 0.0 | 0.0 | 0.0 | |||||||
40 | 61.7 | 47.0 | -14.7 | 67.5 | 67.4 | -0.1 |
In addition, the results verify the accuracy of the calculated values of in elimination of both active and reactive power ripples. For instance, is almost equal to for elimination of reactive power ripple, and equals a negative value that varies according to the fault type and resistance when the IBR is controlled to eliminate active power ripples. For example, for a BCG fault when the IBR is injecting active current and eliminating active power ripples, is equal to , , and for bolted, , and , respectively. Furthermore, the measured values of and are placed correctly in their fault type zones. For example, and are equal to and , respectively, for a BCG fault with .
Fault type | Elimination of active power ripples | Elimination of reactive power ripples | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
CG | 0 | 60.4 | 63.7 | 3.3 | 120.6 | 121.9 | 1.3 | 59.6 | 59.6 | 0.0 | 119.3 | 117.8 | -1.5 | |
50 | 102.4 | 104.9 | 2.5 | 120.5 | 121.5 | 1.0 | 100.3 | 100.3 | 0.0 | 119.3 | 117.8 | -1.5 | ||
ABG | 0 | 0 | -120.0 | -115.6 | 4.4 | 120.0 | 121.5 | 1.5 | -120.0 | -119.9 | 0.1 | 120.0 | 117.7 | -2.3 |
0 | 40 | -48.1 | -45.3 | 2.8 | 127.3 | 128.4 | 1.1 | -51.0 | -51.0 | 0.0 | 123.8 | 122.3 | -1.5 | |
50 | 0 | -120.0 | -116.4 | 3.6 | 51.1 | 52.3 | 1.2 | -120.0 | -119.9 | 0.1 | 65.3 | 63.5 | -1.8 | |
AB | 0 | -120.0 | -116.7 | 3.3 | -120.0 | -120.0 | 0.0 | |||||||
40 | -55.0 | -52.8 | 2.2 | -57.3 | -57.3 | 0.0 |

Fig. 16 Performance of proposed PSM for a fault at bus B5 during active and reactive power ripples. (a) A BCG fault. (b) An ABG fault.
This verifies the accuracy of both the mathematical analysis and fault type zones. As shown in
In this subsection, the proposed PSM is compared against other methods from the literature to substantiate its superiority in detecting faulty phase(s) in transmission systems.

Fig. 17 PSM measurements during an AG fault at of . (a) Method in [

Fig. 18 PSM measurements during a BCG fault at of . (a) Method in [
PSM is a prerequisite element for main protection functions and for new controllers that emulate SG fault currents, though existing PSMs may operate improperly when fault currents are fed by IBRs. In this paper, the root causes for the failure of the PSM based on the relative angles between sequence voltages measured at relay locations, i.e., and , are elaborated. First, short-circuit analysis at the fault location is investigated to determine the relative angles between sequence voltages measured at fault locations, i.e., and . Then, and are deduced by analyzing the TL effects on the angle difference between sequence voltages measured at the relay and fault locations. Further, new zones of PSM are designed to guarantee precise fault type identification for different fault resistances. Simulation studies substantiate the effectiveness of the proposed PSM with different IBR controllers and fault conditions. Future work could investigate the applicability of using machine learning methods in determining the faulty phase accurately for various IBR control strategies while taking into consideration the TL impact on PSM accuracy.
Appendix
By analyzing the sequence network for a BCG fault shown in Fig. 4, the sequence voltages are inferred as:
(A1) |
The relations between sequence currents and their corresponding voltages are given by:
(A2) |
Thus, using (A1) and (A2), , , and can be given by:
(A3) |
Accordingly, and are determined by:
(A4) |
The maximum magnitude of each phase current, i.e., , can be represented in terms of PS and NS currents as:
(B1) |
where represents phase shift , , and for phases a, b, and c, respectively. To avoid any phase current from exceeding its maximum limit, the limit current is equivalent to the maximum phase, which is calculated by:
(B2) |
According to (B2), the maximum value of is determined when the value of is the minimum, which is equal to 0.5 when , , or . Thus, the maximum value of is derived from:
(B3) |
By substituting (17) into (B3), is obtained by:
(B4) |
By substituting (B4) into (22) and keeping p.u., can be calculated by:
(B5) |
References
F. Blaabjerg, Y. Yang, D. Yang et al., “Distributed power-generation systems and protection,” Proceedings of the IEEE, vol. 105, no. 7, pp. 1311-1331, Jul. 2017. [Baidu Scholar]
Y. Mohammadi and R. C. Leborgne, “Improved DR and CBM methods for finding relative location of voltage sag source at the PCC of distributed energy resources,” Electrical Power and Energy Systems, vol. 117, p. 105664, May 2020. [Baidu Scholar]
N. George, O. Naidu, and A. Pradhan, “Distance protection for lines connecting converter interfaced renewable power plants: adaptive to grid-end structural changes,” IEEE Transactions on Power Delivery, vol. 38, no. 3, pp. 2011-2021, Jun. 2023. [Baidu Scholar]
Y. Mohammadi and R. C. Leborgne, “A new approach for voltage sag source relative location in active distribution systems with the presence of inverter-based distributed generations,” Electric Power Systems Research, vol. 182, p. 106222, May 2020. [Baidu Scholar]
M. Salehi and F. Namdari, “Fault classification and faulted phase selection for transmission line using morphological edge detection filter,” IET Generation, Transmission & Distribution, vol. 12, no. 7, pp. 1595-1605, Apr. 2018. [Baidu Scholar]
J. Fang, K. Chen, C. Liu et al., “An explainable and robust method for fault classification and location on transmission lines,” IEEE Transactions on Industrial Informatics, vol. 19, no. 10, pp. 10182-10191, Oct. 2023. [Baidu Scholar]
W. Yuan, Y. Li, L. Xu et al., “A fast faulty phase selection method considering fault tolerance for single phase to ground fault in distribution networks,” IEEE Transactions on Instrumentation and Measurement, vol. 72, pp. 1-12, Sept. 2023. [Baidu Scholar]
P. Barman, N. Subhrahmanyam, S. Roy et al., “A statistical feature-based transmission fault identification and classification,” in Proceedings of 2022 IEEE 2nd International Conference on Sustainable Energy and Future Electric Transportation (SeFeT), Hyderabad, India, Aug. 2022, pp. 1-6. [Baidu Scholar]
Technical Manual: MiCOMho P446 – Fast Multifunction Distance Protection Pelay, Alstom, Stafford, U.K., 2011. [Baidu Scholar]
Power Converter with Ground Fault Detection Function and Fault Detection Method, U.S. Patent no. 11502507, Nov. 2022. [Baidu Scholar]
J. Zhang, B. Zhang, and C. Wang, “Improved schemes for traditional current-based phase selectors in wind power systems,” IET Generation, Transmission & Distribution, vol. 12, no. 21, pp. 5781-5788, Oct. 2018. [Baidu Scholar]
G. Song, C. Wang, T. Wang et al., “A phase selection method for wind power integration system using phase voltage waveform correlation,” IEEE Transactions on Power Delivery, vol. 32, no. 2, pp. 740-748, Apr. 2017. [Baidu Scholar]
M. A. Azzouz, A. Hooshyar, and E. El-Saadany, “Resilience enhancement of microgrids with inverter-interfaced DGs by enabling faulty phase selection,” IEEE Transactions on Smart Grid, vol. 9, no. 6, pp. 6578-6589, Nov. 2018. [Baidu Scholar]
M. A. Azzouz and A. Hooshyar, “Dual current control of inverter-interfaced renewable energy sources for precise phase selection,” IEEE Transactions on Smart Grid, vol. 10, no. 5, pp. 5092-5102, Sept. 2019. [Baidu Scholar]
W. Medhat and M. A. Azzouz, “Triple current control of four-wire inverter-interfaced DGs for correct fault type identification,” IEEE Transactions on Smart Grid, vol. 13, no. 5, pp. 3607-3618, Sept. 2022. [Baidu Scholar]
A. A. Aboelnaga, M. A. Azzouz, H. Sindi et al., “Fault ride through of inverter-interfaced renewable energy sources for enhanced resiliency and grid code compliance,” IEEE Transactions on Sustainable Energy, vol. 13, no. 4, pp. 2275-2290, Oct. 2022. [Baidu Scholar]
E. Carrasco, M. Moreno, M. Martínez et al., “Improved faulted phase selection algorithm for distance protection under high penetration of renewable energies,” Energies, vol. 13, no. 3, p. 558, Jan. 2020. [Baidu Scholar]
A. Hooshyar, E. F. El-Saadany, and M. Sanaye-Pasand, “Fault type classification in microgrids including photovoltaic DGs,” IEEE Transactions on Smart Grid, vol. 7, no. 5, pp. 2218-2229, Sept. 2016. [Baidu Scholar]
K. Xu, Z. Zhang, Q. Lai et al., “Fault phase selection method applied to tie line of renewable energy power stations,” IET Generation, Transmission & Distribution, vol. 14, no. 13, pp. 2549-2557, Jul. 2020. [Baidu Scholar]
P. Praveen and V. Kumar, “Faulty phase selection method for microgrid with inverter-interfaced DGs,” in Proceedings of 2023 IEEE IAS Global Conference on Renewable Energy and Hydrogen Technologies (GlobConHT), Male City, Maldives, Mar. 2023, pp. 1-5. [Baidu Scholar]
S. Paladhi and A. K. Pradhan, “Adaptive fault type classification for transmission network connecting converter-interfaced renewable plants,” IEEE Systems Journal, vol. 15, no. 3, pp. 4025-4036, Sept. 2021. [Baidu Scholar]
A. A. Aboelnaga and M. A. Azzouz, “Adaptive current-angle-based phase selection for microgrids with inverter-interfaced renewable energy sources,” IEEE Transactions on Smart Grid, vol. 13, no. 1, pp. 417-428, Jan. 2022. [Baidu Scholar]
Y. Xie, Y. Liu, Y. Nie et al., “Improved fault phase selection scheme for lines terminated by inverter based resources,” in Proceedings of IEEE PES General Meeting, Orlando, USA, Jul. 2023, pp. 1-6. [Baidu Scholar]
G. Ziegler, Numerical Distance Protection: Principles and Applications, 4th ed., Erlangen: Publicis, 2011. [Baidu Scholar]
T. Gonen, Modern Power System Analysis,
J. Glover, M. Sarma, and T. Overbye, Power System Analysis and Design,
P. M. Anderson, Power System Protection. New York: IEEE Press, 1998. [Baidu Scholar]
Y. Fang, K. Jia, Z. Yang et al., “Impact of inverter-interfaced renewable energy generators on distance protection and an improved scheme,” IEEE Transactions on Industrial Electronics, vol. 66, no. 9, pp. 7078-7088, Sept. 2019. [Baidu Scholar]
Technical Requirements for the Connection and Operation of Customer Installations to the Medium Voltage Network (TAR Medium Voltage), VDE_AR_N_4110, 2018. [Baidu Scholar]