Abstract
Battery energy storage stations (BESSs) pose several challenges for both phasor-based differential protection and the newly-proposed time-domain differential protection. These challenges include low sensitivity and even rejection. Besides, the negative impact of various nonideal conditions, including current transformer (CT) saturation, errors, and outliers, on the security of differential protection remains an important problem. Motivated by the aforementioned issues, this study accounts for the trajectory distribution discrepancy on Cartesian plane under various conditions and proposes a time-domain differential protection method. In this paper, the trajectory formed by operating and restraining current samples is developed. Subsequently, after considering different operating states, the fault severity levels, and nonideal conditions, the variances in trajectory distribution between internal and external faults are extensively analyzed. On this basis, the Cartesian plane is divided into operating, uncertainty, and restraining zones. Further, the operating and restraining trajectory indices are meticulously designed and a protection criterion based on these indices is formed to accurately separate internal faults from other events, unaffected by CT saturation, errors, and outliers. The exceptional performance of the proposed protection method is extensively validated through PSCAD simulations and a hardware-in-the-loop testing platform. Regarding the dependability, sensitivity, and security, the proposed protection method outperforms three state-of-the-art differential protection methods.
FOR achieving carbon neutrality, the penetration rate of renewable energy is continuously and rapidly increasing and will eventually displace thermal power as the main source in power systems [
Despite its benefits, the BESS presents certain challenges to the reliability of conventional relay protection that depends on the fault behaviors of synchronous generators (SGs). To improve the performance of power frequency component based conventional current differential protection (CDP), two time-domain differential protection (TDDP) methods for lines connecting SGs are proposed in [
Photovoltaic power, wind power, voltage source converter based high-voltage direct current (VSC-HVDC) stations, and BESSs are power electronic-based power sources. Compared with SGs, they share some common fault behaviors. Thus, we consider protection methods of lines connecting renewable energy plants and VSC-HVDC stations as a reference. In [
Both the VSC-HVDC station and BESS can operate under the charging (rectifier) and discharging (inverter) states. Thus, they share more common fault behaviors compared with renewable energy plants. The performance difference of conventional CDP between the rectifier and inverter states is analyzed in [
The main contributions of this paper are summarized as follows.
1) The concept of the current trajectory formed by time-domain operating and restraining current samples is developed. The divergence in the distribution patterns of the current trajectories on a Cartesian plane under various conditions is investigated, establishing a fundamental basis for the proposal of a novel time-domain protection method.
2) After considering the distribution patterns of current trajectories under various conditions, the Cartesian plane is divided into five zones. The methodology for this division and the principles for selecting the key parameters are detailed.
3) The operating trajectory index (OTI) and restraining trajectory index (RTI) are designed. Furthermore, a TDDP method based on the OTI and RTI is proposed, which does not require discrete Fourier transform.
4) The excellent functionality of the proposed protection method is extensively validated using PSCAD simulations and a hardware-in-the-loop (HIL) testing platform. The proposed method functions well across a variety of fault types, resistances, locations, and operating states of a BESS, outperforming state-of-the-art time-domain protection methods.
The remainder of this paper is organized as follows. Section II describes the potential problems of phasor-based CDP. In Section III, the trajectory distribution discrepancy under various conditions is analyzed in detail, and the division principles of the operating, uncertainty, and restraining zones are described and derived. Furthermore, a protection criterion based on the OTI and RTI is designed. The exceptional performance of the proposed protection method is extensively validated, and a comparative study with some newly-proposed TDDP methods is conducted in PSCAD software and HIL testing platform in Sections IV and V, respectively. Section VI discusses future work and explores new trends. In Section VII, we draw conclusions.
A modified 230 kV 50 Hz IEEE 39-bus system with a BESS is considered, as shown in

Fig. 1 IEEE 39-bus system with BESS. (a) Detailed model. (b) Simplified model.
Because of its absolute selectivity and speed, the phasor-based CDP is always the first choice for primary protection of transmission lines in conventional power systems. Its operating criterion is given by:
(1) |
where and are the operating and restraining currents, respectively; and K is the restraining coefficient with a value usually between 0.5 and 0.8.
The potential problems with phasor-based CDP can be divided into two categories. The first category is dependability issue caused by the presence of a BESS under an internal fault. The second category is a security issue caused by nonideal conditions during external faults, such as CT saturation, errors, and outliers.
To illustrate the potential problems, (1) is rewritten as:
(2) |
where is a complex number given by:
(3) |
where a and b are the real and imaginary parts of , respectively.
Based on (2) and (3), the following function is derived as:
(4) |
When , the operating criterion expressed as (2) is satisfied, thus indicating an internal fault.
When , the operating criterion is not satisfied, thus indicating an external fault. corresponds to the critical operating state.
In

Fig. 2 Operating and restraining zones under different restraining coefficients.
To illustrate the dependability problem of CDP, an internal fault with a fault resistance of is considered.

Fig. 3 Dynamic trajectory of λ in different operating states.
In the steady state, in the charging state, and in the discharging state. The magnitude of the real part substantially exceeds that of the imaginary part. Thus, the angle of approaches 0° and 180° in the discharging and charging states, respectively. This indicates that the currents at the ends are in phase in the discharging state and out of phase in the charging state. When a short-circuit fault occurs, the SG generally exhibits feed-in characteristics by feeding current to the fault point. Thus, when the BESS operates in the discharging state, both the SG and BESS exhibit feed-in characteristics that are similar to the fault behaviors of conventional power systems. However, when the BESS operates in the charging state, the fault currents of the SG and BESS are out of phase. Consequently, the BESS presents the opposite characteristic to the SG, i.e., a draw-out characteristic. In other words, the BESS draws current from the fault point. The different fault characteristics in the charging and discharging states lead to drastically different operating performances of CDP.
In this subsection, three typical nonideal conditions are considered as follows.
1) CT error: the CT on the grid side has a measurement error of during an external fault.
2) CT saturation: the CT on the grid side is saturated during an external fault.
3) Outliers: the outliers are introduced into the measured current on the BESS side during an external fault.

Fig. 4 Dynamic trajectories of λ during external faults under three nonideal conditions.
Considering the shortcomings of phasor-based CDP in the presence of a BESS, we propose a time-domain CDP. Time-domain current arrays on both sides are composed of current samples, which are expressed as:
(5) |
(6) |
where N is the length of the data window.
Similar to phasor-based CDP, the time-domain operating and restraining current arrays and are defined as:
(7) |
(8) |
(9) |
As shown in

Fig. 5 Schematic diagram of current trajectory formation.
To separate the internal faults from normal condition, the divergence in the trajectory distribution characteristics between these conditions should be analyzed.
Under normal conditions, the operating current approaches zero and is substantially lower than the restraining current. Thus, the current trajectory is close to y-axis, as shown in

Fig. 6 Current trajectories on Cartesian plane under normal condition and internal faults. (a) Normal condition (charging state). (b) Normal condition (discharging state). (c) Severe internal fault (charging state). (d) Severe internal fault (discharging state). (e) High-resistance internal fault (charging state). (f) High-resistance internal fault (discharging state).
Thus, we have:
(10) |
where .
According to the approximation relation in (10), the current trajectory should be around , as confirmed in
As the fault resistance increases, the current trajectory gradually deviates from . As shown in
For the precise identification of whether the fault occurs within or outside the protection zone, the trajectory distribution characteristics of the external fault and the difference with those of internal faults should be investigated. To improve the robustness and minimize the impact of CT saturation, errors, and outliers, the three abovementioned nonideal conditions are considered.
(11) |

Fig. 7 Current trajectories on Cartesian plane under external faults and three nonideal conditions. (a) External fault. (b) Outliers. (c) -10% CT error on grid side. (d) -10% CT error on BESS side. (e) CT saturation on grid side. (f) CT saturation on BESS side.
Considering a CT error of on the grid side, the operating and restraining currents can be expressed as:
(12) |
Thus, we have:
(13) |
When , ires/iop is approximately 19, being a positive value. Therefore, the current trajectory exhibits a steep slope in the first and third quadrants, being consistent with the trajectory shown in
When a measurement error of is introduced into the CT on the BESS side, a similar derivation occurs. The following relation is obtained as:
(14) |
When , is approximately , being a negative value. Therefore, the current trajectory shows a high slope in the second and fourth quadrants, being consistent with the trajectory shown in
For differential protection, the CT saturation always bring great challenges to its security. In the linear transferring zone of CT, the currents on both sides satisfy the relation in (11). Thus, the operating current is close to zero. Part of the current trajectory is near y-axis. When the CT enters the saturation zone, the current trajectory deviates considerably from y-axis. As shown in
By carefully comparing and analyzing
1) Division Principle of Operating, Uncertainty, and Restraining Zones
We analyze the discrepancy in the current trajectory distribution on the Cartesian plane under various circumstances, i.e., normal conditions, internal faults, and external faults with and without nonideal conditions. Then, the Cartesian plane is divided into five zones, as shown in

Fig. 8 Schematic of partition on Cartesian plane.
Zones 1-4 can be determined by (15a)-(15d), respectively.
(15a) |
(15b) |
(15c) |
(15d) |
where and ranges from to 180°; is the current threshold; and , , and determine the sizes of zones 2-4, respectively.
Considering the trajectory analysis under diverse conditions in Section III-B, zones 1-3 are designated as restraining zone, zone 4 is designated as the uncertainty zone, and zone 5 is designated as the operating zone.
Under normal conditions, external faults without nonideal conditions, and the linear transferring zone of the CT, the trajectory points are expected to fall into zone 1. Hence, should be greater than the line capacitive current:
(16) |
where is the rated voltage; is the rated angular frequency; C is the capacitance per unit length; and l is the line length. For a 230 kV transmission line, its length typically does not exceed 300 km. Hence, in this paper, l is set to be 300 km.
As shown in
(17) |
The value of clearly depends on the CT error . To ensure the robustness against CT errors, we consider a worst-case scenario of being a large value of 10%. In this case, is approximately less than or equal to 84°. Considering 2° as a margin, is set to be 82°.
Under an external fault, when the CT on the grid side is saturated (see
(18) |
Thus, the points corresponding to the unsaturated zone of CT can easily fall into zone 1. When the CT on the grid side is saturated, is considered to instantaneously become zero, as stated in [
(19) |
From (19), most of the points corresponding to the saturated zone of the CT are very close to . Zone 3 is the zone with the symmetry axis of , and determines the size of zone 3. Because the points associated with the saturated zone of the CT theoretically lie on the , a relatively small value (e.g., 5°) is generally sufficient for most of the points corresponding to the saturated zone to fall into zone 3.
As shown in
(20) |
From (20), the points associated with the saturated zone of the CT theoretically lie on the . Thus, in theory, can be assigned the identical value as , i.e., . However, when a severe internal fault occurs, some trajectory points may also fall into zone 4, as shown in
2) Protection Criterion
A variable is defined to describe the location of the trajectory point as:
(21) |
where .
The variable is defined to indicate whether the trajectory point is inside zone as:
(22) |
It is clear that the variable can indicate the distribution discrepancy of the current trajectory on the Cartesian plane between an internal fault and other disturbances. Thus, if is used properly, an internal fault can be accurately distinguished from other events.
Considering the distribution discrepancy of the current trajectory under diverse conditions, the OTI of time-domain CDP is defined as:
(23) |
where is a weight satisfying .
The RTI can be chosen as a constant. An internal fault is identified when the OTI exceeds the RTI. A large RTI leads to high security but low sensitivity and dependability, while a small RTI results in high sensitivity and dependability but low security. To simultaneously achieve high security and sensitivity, the RTI is designed as the summation of a small constant and varying quantity :
(24) |
Regardless of normal condition, external faults without nonideal conditions, and external faults with outliers and CT saturation, there is always a considerable number of trajectory points falling into zone 1. On the other hand, few trajectory points are located inside zone 1 under various internal faults. Therefore, the number of trajectory points inside zone 1 can be used to design the varying quantity . The RTI can be rewritten as:
(25) |
The protection criterion for an internal fault is expressed as:
(26) |
In general, approaches 0.2 under internal faults, resulting in high sensitivity. Under external faults, since a considerable number of trajectory points are located in zone 1, the RTI is relatively large, resulting in high security.
Considering the extreme case, all the trajectory points in
The proposed protection method is implemented, as shown in

Fig. 9 Flowchart of proposed protection method.
Step 1: obtain current samples on both sides.
Step 2: if a fault is detected, go to the next step. Otherwise, set to zero and return to Step 1. For fault detection, refer to [
Step 3: calculate variable .
Step 4: calculate the OTI and RTI using (23) and (25), respectively.
Step 5: if OTI surpasses RTI, the fault is considered to occur within the protection zone. Thus, the relay generates the tripping signal. Otherwise, the fault is considered to be outside the protection zone, i.e., an external fault.
To verify the effectiveness and assess the performance of the proposed protection method, the modified 39-bus system with a BESS shown in
Given that short-circuit faults commonly involve fault resistance, the capability to withstand a fault resistance serves as a crucial indicator to measure the performance of relay protection. To assess the capability of proposed protection method against fault resistance, AG faults with varying fault resistances are introduced at s at the midpoint of line 33-19. The fault resistance values include 1 , 50 , and 100 , covering a broad spectrum. Furthermore, both charging and discharging states of BESS are considered.
The simulation waveforms of the OTI and RTI with different fault resistances are shown in

Fig. 10 Simulation waveforms of OTI and RTI with different fault resistances. (a) 1 Ω. (b) 50 Ω. (c) 100 Ω.
To comprehensively evaluate the proposed protection method, several internal faults are applied considering different fault locations and types. The fault types include BG, AB, BCG, and ABC. Three fault locations, designated as F1, F2, and F3, are placed at 10%, 50%, and 90% of the distance from bus 33 to bus 19, respectively. The BESS operates in the charging state, and the fault resistance is set to be 30 .
The OTI and RTI under different fault types and locations are listed in
Fault location | Fault type | Phase A | Phase B | Phase C | |||
---|---|---|---|---|---|---|---|
OTI | RTI | OTI | RTI | OTI | RTI | ||
F1 | BG | 0 | 1 | 0.769 | 0.225 | 0 | 1 |
AB | 0.966 | 0.225 | 0.850 | 0.225 | 0 | 1 | |
BCG | 0 | 1 | 0.866 | 0.225 | 0.866 | 0.225 | |
ABC | 0.956 | 0.225 | 0.956 | 0.225 | 0.956 | 0.225 | |
F2 | BG | 0 | 1 | 0.594 | 0.213 | 0 | 1 |
AB | 0.938 | 0.225 | 0.894 | 0.225 | 0 | 1 | |
BCG | 0 | 1 | 0.881 | 0.225 | 0.863 | 0.225 | |
ABC | 0.975 | 0.225 | 0.975 | 0.225 | 0.975 | 0.225 | |
F3 | BG | 0 | 1 | 0.916 | 0.200 | 0 | 1 |
AB | 0.900 | 0.225 | 0.894 | 0.225 | 0 | 1 | |
BCG | 0 | 1 | 0.900 | 0.225 | 0.906 | 0.200 | |
ABC | 0.956 | 0.225 | 0.956 | 0.225 | 0.956 | 0.225 |
Various nonideal conditions such as CT errors, saturation, and outliers consistently threaten the security of differential protection. Therefore, we evaluate the ability of the proposed protection method to withstand various nonideal conditions. For this purpose, bus 33 is subjected to a bolted ABG fault considering CT errors, saturation, and outliers. The simulation results are shown in

Fig. 11 Simulation results under various nonideal conditions. (a) CT error. (b) Outliers. (c) CT saturation.
For the scenario corresponding to
To assess the tolerance of the proposed protection method to the BESS capacity, AG faults with a fault resistance of 100 are introduced at the midpoint of line 33-19 under different BESS capacities of 150 MW, 250 MW, and 350 MW. Moreover, the charging and discharging states of the BESS are considered. The waveforms of the OTI and RTI under different BESS capacities are shown in

Fig. 12 Performance evaluation under different BESS capacities. (a) 150 MW. (b) 250 MW. (c) 350 MW.
An AG fault is applied at bus 33, which is an external fault. The BESS capacity is set to be 250 MW, and BESS operates in the charging state. The tolerance of the proposed protection method to line capacitive current is examined by considering different line lengths of 50 km, 100 km, 200 km, and 300 km.
The line capacitive currents and waveforms of the OTI and RTI with different line lengths are shown in

Fig. 13 Line capacitive currents and waveforms of OTI and RTI with different line lengths. (a) Line capacitive current. (b) 50 km. (c) 100 km. (d) 200 km. (e) 300 km.
To further ensure the meliority of proposed protection method, an HIL testing platform is set up in a laboratory, as shown in

Fig. 14 HIL testing platform for relay protection.
The performance of the protection method is assessed by considering diverse fault scenarios, which are created by changing fault distances, resistances, types, and operating states. Fault distance indicates the distance between the fault point and BESS. The results of OTI and RTI in diverse fault scenarios are listed in
Operating state | Fault type | Fault distance (km) | Fault resistance (Ω) | Phase A | Phase B | Phase C | |||
---|---|---|---|---|---|---|---|---|---|
OTI | RTI | OTI | RTI | OTI | RTI | ||||
Charging state | AB (case 1) | 1 | 1 | 0.781 | 0.200 | 0.791 | 0.200 | 0 | 1 |
ABC | 10 | 25 | 0.975 | 0.225 | 0.981 | 0.200 | 0.956 | 0.225 | |
BCG | 20 | 50 | 0 | 1 | 0.938 | 0.225 | 0.938 | 0.225 | |
BG | 29 | 100 | 0 | 1 | 0.950 | 0.250 | 0 | 1 | |
Discharging state | AB | 1 | 1 | 0.894 | 0.200 | 0.741 | 0.200 | 0 | 1 |
ABC | 10 | 25 | 1 | 0.200 | 0.966 | 0.225 | 0.981 | 0.200 | |
BCG | 20 | 50 | 0 | 1 | 0.956 | 0.225 | 0.956 | 0.225 | |
BG (case 2) | 29 | 100 | 0 | 1 | 0.925 | 0.250 | 0 | 1 |
The results corresponding to cases 1 and 2 highlighted in bold in

Fig. 15 Results of case 1. (a) Phase A. (b) Phase B. (c) Phase C.

Fig. 16 Results of case 2. (a) Phase A. (b) Phase B. (c) Phase C.
In
The current trajectories and waveforms of the OTI and RTI for case 2 are depicted in
To highlight the superiority of the proposed protection method, it is compared with three state-of-the-art TDDP methods, i.e., CSC-based TDDP (CSC-TDDP) [
An AG fault with a fault resistance of 100 occurs at a distance of 10 km from the BESS.

Fig. 17 Comparison of four protection methods under internal fault. (a) CSC-TDDP. (b) FDI-TDDP. (c) CTC-TDDP. (d) Proposed protection method.
From
A comparative study on the robustness to CT saturation of the four protection methods is also necessary. To do this, an external AG fault with a fault resistance of 0 is applied, and the CT on the grid side is set to be the saturation mode. The BESS operates in the charging state.

Fig. 18 Comparison of four TDDP methods under external faults with CT saturation. (a) CSC-TDDP. (b) FDI-TDDP. (c) CTC-TDDP. (d) Proposed protection method.
According to the above-mentioned analysis, CTC-TDDP and the proposed protection method demonstrate higher dependability than the CSC-TDDP and FDI-TDDP in different operating states. However, the proposed protection method outperforms CTC-TDDP in terms of sensitivity. In addition, compared with CSC-TDDP and FDI-TDDP, CTC-TDDP and the proposed protection method also exhibit superior security in the presence of CT saturation. Overall, compared with other three TDDP methods, the proposed protection method exhibits increased dependability, sensitivity, and security.
Modern power systems are gradually evolving toward new power systems dominated by power electronic-based sources, including renewable energy sources, VSC-HVDC stations, and BESSs, etc. This profoundly alters the fault characteristics of the power system, deteriorates the operating performance of relay protection, and poses a threat to the safety of the power system. Most studies focus on studying the fault characteristics of certain power electronic-based sources and exploring protection principles that match these characteristics. However, the differing fault characteristics between different types of power electronic-based sources make the existing protection principles less universally applicable.
Thus, conducting in-depth research on the common characteristics of various types of power electronic-based sources and devising novel protection principles that can adapt to various types of power electronic-based sources may be more well-received. Additionally, exploring new protection methods that do not rely on the fault characteristics of power sources is also an emerging research trend.
Deep learning may be useful to address problems in relay protection. Integrating state-of-the-art deep learning algorithms with relay protection may produce remarkable results beyond the initial expectations. However, the interpretability of deep learning based data-driven protection methods is poor. In future work, deep learning can be merged with expert knowledge to develop a new protection method driven by a combination of knowledge and data to ensure high accuracy while improving interpretability.
In response to the challenges posed by the integration of BESSs in both conventional CDP and newly-proposed TDDP methods, we account for the trajectory distribution discrepancy to propose a new time-domain CDP method based on the OTI and RTI. An extensive performance evaluation of the proposed protection method and comparative study with state-of-the-art TDDP methods are conducted using PSCAD simulations and an HIL testing platform. The findings of this study are summarized as follows.
1) Compared with the discharging state, the effectiveness of CDP is more likely to be compromised in the charging state of BESS. Conventional CDP is highly resilient to CT errors, but its security may be reduced, leading to false trip signals in the presence of CT saturation and outliers.
2) The trajectory formed by operating and restraining current samples exhibits notable variations in its distribution characteristics between internal faults and other events. This behavior is exploited to develop the proposed TDDP method that precisely identifies internal faults from other events.
3) The proposed protection method demonstrates excellent robustness to CT saturation, errors, and outliers, and it performs well across various fault types, resistances, locations, and operating states. Compared with three state-of-the-art TDDP methods, i.e., CSC-TDD, FDI-TDDP, and CTC-TDDP, the proposed protection method exhibits superior dependability, sensitivity, and security.
References
F. Zheng, X. Zhou, B. Rahat et al., “Carbon neutrality target for leading exporting countries: on the role of economic complexity index and renewable energy electricity,” Journal of Environmental Management, vol. 299, p. 113558, Dec. 2021. [Baidu Scholar]
U. Datta, A. Kalam, and J. Shi, “The relevance of large-scale battery energy storage (BES) application in providing primary frequency control with increased wind energy penetration,” Journal of Energy Storage, vol. 23, pp. 9-18, Jun. 2019. [Baidu Scholar]
L. M. S. de Siqueira and W. Peng, “Control strategy to smooth wind power output using battery energy storage system: a review,” Journal of Energy Storage, vol. 35, p. 102252, Mar. 2021. [Baidu Scholar]
Z. Guo, W. Wei, L. Chen et al., “Impact of energy storage on renewable energy utilization: a geometric description,” IEEE Transactions on Sustainable Energy, vol. 12, no. 2, pp. 874-885, Apr. 2021. [Baidu Scholar]
A. N. R. L. Sirisha and A. K. Pradhan, “Subcycle transmission line protection using time-domain similarity measure,” International Journal of Electrical Power & Energy Systems, vol. 137, p. 107766, May 2022. [Baidu Scholar]
L. Chen, X. Lin, Z. Li et al., “Similarity comparison based high-speed pilot protection for transmission line,” IEEE Transactions on Power Delivery, vol. 33, no. 2, pp. 938-948, Apr. 2018. [Baidu Scholar]
S. Chen, N. Tai, C. Fan et al., “Sequence-component-based current differential protection for transmission lines connected with IIGs,” IET Generation, Transmission & Distribution, vol. 12, no. 12, pp. 3086-3096, Jul. 2018. [Baidu Scholar]
H. Gao, J. Li, and B. Xu, “Principle and implementation of current differential protection in distribution networks with high penetration of DGs,” IEEE Transactions on Power Delivery, vol. 32, no. 1, pp. 565-574, Feb. 2017. [Baidu Scholar]
G. Chen, Y. Liu, and Q. Yang, “Impedance differential protection for active distribution network,” IEEE Transactions on Power Delivery, vol. 35, no. 1, pp. 25-36, Feb. 2020. [Baidu Scholar]
K. Jia, Y. Li, Y. Fang et al., “Transient current similarity based protection for wind farm transmission lines,” Applied Energy, vol. 225, pp. 42-51, Sept. 2018. [Baidu Scholar]
L. Zheng, K. Jia, T. Bi et al., “Cosine similarity based line protection for large-scale wind farms,” IEEE Transactions on Industrial Electronics, vol. 68, no. 7, pp. 5990-5999, Jul. 2021. [Baidu Scholar]
L. Zheng, K. Jia, W. Wu et al., “Cosine similarity based line protection for large scale wind farms part II – the industrial application,” IEEE Transactions on Industrial Electronics, vol. 69, no. 3, pp. 2599-2609, Mar. 2022. [Baidu Scholar]
A. Saber, M. F. Shaaban, and H. H. Zeineldin, “A new differential protection algorithm for transmission lines connected to large-scale wind farms,” International Journal of Electrical Power & Energy Systems, vol. 141, p. 108220, Oct. 2022. [Baidu Scholar]
Z. Yang, W. Liao, H. Wang et al., “Improved euclidean distance based pilot protection for lines with renewable energy sources,” IEEE Transactions on Industrial Informatics, vol. 18, no. 12, pp. 8551-8562, Dec. 2022. [Baidu Scholar]
A. Saber, H. H. Zeineldin, T. H. M. El-Fouly et al., “A signed correlation index-based differential protection scheme for inverter-based islanded microgrids,” International Journal of Electrical Power & Energy Systems, vol. 145, p. 108721, Feb. 2023. [Baidu Scholar]
Y. Liang, Y. Ren, and W. He, “An enhanced current differential protection for AC transmission lines connecting MMC-HVDC stations,” IEEE Systems Journal, vol. 17, no. 1, pp. 892-903, Mar. 2023. [Baidu Scholar]
Y. Liang, Y. Ren, and Z. Zhang, “Pilot protection based on two-dimensional space projection of dual differential currents for lines connecting MMC-HVDC stations,” IEEE Transactions on Industrial Electronics, vol. 70, no. 5, pp. 4356-4368, May 2023. [Baidu Scholar]
A. M. Joshua and K. P. Vittal, “Protection schemes for a battery energy storage system based microgrid,” Electric Power Systems Research, vol. 204, p. 107701, Mar. 2022. [Baidu Scholar]
Y. Liang, X. Yang, Y. Wang et al., “Internal fault probability-based time domain differential protection applied to transmission lines connecting battery energy storage stations,” Journal of Energy Storage, vol. 55, p. 105707, Nov. 2022. [Baidu Scholar]
Y. Liang, C. Pan, and J. Zhang, “Current trajectory coefficient based time domain line protection for battery storage energy stations,” Journal of Energy Storage, vol. 51, p. 104468, Jul. 2022. [Baidu Scholar]
M. Hossain, I. Leevongwat, and P. Rastgoufard, “Revisions on alpha plane for enhanced sensitivity of line differential protection,” IEEE Transactions on Power Delivery, vol. 33, no. 6, pp. 3260-3262, Dec. 2018. [Baidu Scholar]
J. R. Camarillo-Peñaranda, M. Aredes, and G. Ramos, “Hardware-in-the-loop testing of a distance protection relay,” IEEE Transactions on Industry Applications, vol. 57, no. 3, pp. 2326-2331, May 2021. [Baidu Scholar]