Abstract
The hybrid cascaded high-voltage direct current (HVDC) transmission system has various operation modes, and some operation modes are having sharply increasing requirements for protection rapidity, while the traditional pilot differential protection (PDP) has poor rapidity, and even refuses to operate when faults occur on the DC line. Therefore, a novel pilot protection scheme based on traveling wave characteristics is proposed. First, the adaptability of the traditional PDP applied in engineering is analyzed for different operation modes. Then, the expressions of the forward traveling wave (FTW) and backward traveling wave (BTW) on the rectifier side and the inverter side are derived for different fault locations. From the theoretical derivation, the difference between the BTW and FTW on the rectifier side is less than zero, and the same is true on the inverter side. However, in the event of an external fault of DC line, the difference between the BTW and FTW at near-fault terminal protection installation point is greater than zero. Therefore, by summing over the product of the difference between BTW and FTW of the rectifier side and that of the inverter side, the fault identification criterion is constructed. The simulation results show that the proposed pilot protection scheme can quickly and reliably identify the short-circuit faults of DC line in different operation modes.
HYBRID cascaded high-voltage direct current (HVDC) systems, which combine the advantages of line commutated converter based HVDC (LCC-HVDC) and modular multilevel converter based HVDC (MMC-HVDC) technologies, have become a hot spot for academic research and engineering applications [
To improve the rapidity of PDP, extensive studies have been carried out from the aspects of PDP optimization [
In terms of new principles of pilot protection, it mainly includes the protection schemes based on different feature quantities at both ends of the DC line, or the protection schemes using boundary characteristics of the DC line. For the former, a PDP principle based on the virtual impedance of the fault component is proposed in [
For the latter, the DC line fault of LCC-HVDC is identified by using surge impedance at tuning frequency and transient energy ratio based on the DC filter (DCF) boundaries at both ends of the DC line in [
However, for the hybrid cascaded HVDC systems with a structure similar to the Bai-Jiang Project, the three MMCs on the inverter side adopt a half-bridge submodule, with as many as 621 operation modes [
Based on this, the difference in the rapidity requirements of PDP in different operation modes of hybrid cascaded HVDC systems is considered, and a novel pilot protection scheme, which is suitable for multiple operation modes, is proposed. The principle of PDP adopted in the existing engineering is introduced in detail, which requires long delays to eliminate the effect of line distribution capacitance. The characteristics of line-mode voltage after fault at different positions are analyzed, and the FTW and BTW expressions are derived. Through analysis, it is found that only when the DC line fault occurs, both the difference values between BTW and FTW on the rectifier side and the inverter side are less than zero, but the external fault of DC line does not have such a feature. Therefore, this paper identifies the short-circuit faults of DC lines based on this characteristic. The proposed pilot protection scheme does not need to consider the transient process of faults in AC system, which improves the rapidity of the protection operation.
This paper focuses on the Bai-Jiang Project in China, a typical hybrid cascaded HVDC project. The rectifier of the hybrid cascaded HVDC systems is constructed with two 12-pulse LCCs, and the inverter is composed of a 12-pulse LCC in series with three parallel MMCs. Due to the symmetry of the bipolar structure for cascaded HVDC system, this paper only analyzes the unipolar structure, as shown in

Fig. 1 Unipolar structure of full-voltage operation.
Hybrid cascaded HVDC systems have two operation modes: full-voltage and half-voltage [
This paper takes the bipolar full-voltage operation (Mode a), the bipolar half-voltage operation of high-voltage valve (Mode b), and the bipolar half-voltage operation of low-voltage valve (Mode c) as examples for fault analysis. The unipolar structures of Mode b and Mode c are shown in

Fig. 2 Unipolar structures of half-voltage operation. (a) Mode b. (b) Mode c.
Combined with
The difference of the DC line current between the rectifier station and the inverter station is calculated, and if it is greater than the setting value within a certain period of time, it will be determined that a short-circuit fault occurs on the DC line. The criteria can be expressed as:
(1) |
where is the DC line current of the rectifier station; is the contralateral current; is the restraint current; is the setting value; and is the ratio factor.
In the project, to prevent the PDP malfunction resulted from the transient influence of AC short-circuit fault, the following protection logic is formulated: the current differences before and after 65 ms on the rectifier side and the inverter side, i.e., and , are calculated, respectively. If the current difference or is greater than the setting value (0.105 p.u.), a 600 ms lock-up delay will be carried out. And if or still exceeds the setting value during the lock-up period, the 600 ms lock-up delay will be repeated. This is called delay lock-up strategy (DLS). At the same time, after satisfying the PDP criterion, a 500 ms operation delay is required before the signal is issued. Therefore, the PDP requires a delay of 1.1 s.
According to the actual engineering parameters, this paper builds a simulation model based on PSCAD/EMTDC, and analyzes the PDP operation performance in different modes of hybrid cascaded HVDC systems.

Fig. 3 PDP operation characteristics of DC line fault for Mode c. (a) and state of DLS. (b) and state of DLS. (c) . (d) . (e) .

Fig. 4 Control characteristic curves of inverter station MMCs. (a) MMC1. (b) MMC2. (3) MMC3.
It can be observed from
The electrical quantities between the bipolar DC line are decoupled by pole-mode conversion. In addition, considering the frequency variable characteristics of the DC line, this paper analyzes the fault characteristics with the line-mode component. The fault characteristics of Modes a-c are analyzed, but only the fault analytical expression of Mode c is given due to space limitations.
From

Fig. 5 Peterson equivalent diagram of fault . (a) Rectifier side. (b) Inverter side.
From
(2) |
where is the voltage amplitude at the fault point; is the equivalent inductance of DCF; is the equivalent capacitance of DCF; is the terminal voltage of ; is the fault current of DC line; is the line-mode wave impedance of the DC line; and the subscript 1 represents the fault .
For f1, the relationship of FTW, BTW, and refracted traveling wave at point , i.e., , , and , respectively, is expressed as:
(3) |
can be expressed as:
(4) |
where is the the line-mode component of the propagation coefficient.
From
(5) |
where is the refracted voltage at point .
Therefore, can be expressed as:
(6) |
can be calculated according to
(7) |
can be obtained by the first-order model approximation as:
(8) |
Then, the reverse Laplace transform is performed to obtain as:
(9) |
From (4), (6), and (9), is expressed as:
(10) |
Similarly, for the inverter side, the BTW at point can be obtained as:
(11) |
where is the whole length of DC line.
The FTW at point is expressed as:
(12) |
The difference between and , i.e., , is expressed as:
(13) |
The difference between and , i.e., , is expressed as:
(14) |
The product of (13) and (14) is expressed as:
(15) |
From (15), is greater than zero. That is, and have the same sign.
The Peterson equivalent diagram is shown in
(16) |

Fig. 6 Peterson equivalent diagram of fault . (a) Rectifier side. (b) Inverter side.
where ; is the voltage amplitude for the short-circuit fault at fault point; and the subscript 2 represents the fault .
is calculated by the first-order model approximation as:
(17) |
The BTW at point is zero within the time of 2/ ( is the line-mode wave velocity) after the FTW is detected. The FTW at point propagates to point , and the BTW at point is expressed as:
(18) |
Referring to (5) and (6), the FTW at point can be obtained as:
(19) |
The DC line current can be calculated as:
(20) |
where is the arm equivalent reactance; and is the arm equivalent capacitance of the three parallel MMCs.
is calculated by the first-order model approximation as:
(21) |
where .
The reverse Laplace transform is performed for (21), and can be expressed as:
(22) |
The expression of is given as:
(23) |
The difference between and , i.e., , is given as:
(24) |
The difference between and , i.e., , is given as:
(25) |
The product of (24) and (25) is expressed as:
(26) |
From (26), is less than zero. That is, and have different signs.
For the fault , the Peterson equivalent circuit diagram is shown in
(27) |

Fig. 7 Peterson equivalent diagram of fault . (a) Rectifier side. (b) Inverter side.
where is the voltage amplitude for the short-circuit fault at fault point; and the subscript 3 represents the fault .
is obtained by the reverse Laplace transform as:
(28) |
However, the BTW is zero within the time 2/ after the FTW being detected at point . The FTW at point propagates to on the full line length of , and the BTW at point is expressed as:
(29) |
The FTW at point can be obtained as:
(30) |
The DC line current can be calculated as:
(31) |
is expressed by the first-order approximation model as:
(32) |
The reverse Laplace transform is performed for the above equation, and is expressed as:
(33) |
The expression of is given as:
(34) |
The difference between and , i.e., , is given as:
(35) |
The difference between and , i.e., , is given as:
(36) |
The product of (35) and (36) is expressed as:
(37) |
From (37), is less than zero. That is, and have different signs.
Similarly, Mode a and Mode b are also analyzed, and the above regularities still hold true. That is, the products of the traveling wave difference for the rectifier side and the inverter side are all greater than 0 for all of the three kinds of operation modes when short-circuit faults occur on the DC line, and it is less than 0 in the cases of external faults. In addition, since Mode b operates in the same way as the traditional LCC-HVDC structure, it shows that the proposed pilot protection scheme is also suitable for the traditional LCC-HVDC system.
The start-up criterion is carried out by the change of the line-mode current. The improved current gradient algorithm is used, and the expression is shown as:
(38) |
where is the line-mode current sampling value on the rectifier or inverter side of the DC line; and is the setting value, and it is 0.01 p.u..
From the analysis in Section III, it can be observed that when short-circuit faults occur on the DC line, both the difference between BTW and FTW on the rectifier side and that on the inverter side have the same sign. For the external fault, they have different signs. Therefore, based on the data of the FTW and BTW of the first detection of the traveling wave after the fault, the product of and is calculated, and if it is greater than 0, the DC line fault is identified. The pilot protection criterion of DC line fault is set as:
(39) |
where is the number of sampling points, and the value of is determined by the sampling data window. Theoretically, the shorter the length of the data window, the faster the fault detection, which satisfies the protection rapidity requirements, but the protection reliability may be reduced by the influence of system disturbance. The longer the data window, the longer the fault detection time, which meets the protection reliability requirements, but reduces the protection operation quickness. Based on this, the time window of the traveling wave difference is taken as 0.2 ms in this paper. Therefore, is equal to 20.
The DC line fault is identified when . Otherwise, it indicates that the external fault of the DC line occurs.
For a short-circuit fault on the DC line, in order to further determine whether the fault is located on the positive line, negative line, or bipolar line, the zero-mode component of fault voltage is used to construct the fault pole identification criterion, and the expression is given as:
(40) |
where is the protection threshold value, which is set to be greater than the maximum unbalance voltage of the bipolar fault, and it can be set to be 0.05 p.u.; represents that the short-circuit faults on the negative line; represents that the short-circuit faults on the positive line; and represents that the short-circuit faults on the bipolar line.
The flowchart of the proposed pilot protection scheme of the DC line for the hybrid cascaded HVDC system is shown in

Fig. 8 Flowchart of proposed pilot protection scheme.
Bipolar models in different operation modes of the hybrid cascaded HVDC systems are built on PSCAD/EMTDC as follows.
1) Model a. The rectifier station adopts two 12-pulse LCCs, the high-voltage side of the inverter station is a 12-pulse LCC, and the low-voltage side includes three parallel MMCs, of which the number of modules on MMC bridge arm is 200. The control strategy is that the rectifier side adopts fixed DC current control, the high-voltage side of the inverter side adopts fixed DC voltage control, the low-voltage side of inverter station adopts fixed DC voltage control and fixed reactive power control, and the remaining two MMCs adopt fixed active power control and fixed reactive power control.
2) Mode b. Rectifier side and inverter side both have a 12-pulse LCC in operation. The rectifier side adopts fixed DC current control, and the inverter side adopts fixed DC voltage control.
3) Mode c. Rectifier side has a 12-pulse LCC, and inverter side contains three parallel MMCs. The control strategy of the rectifier side is the same as that of Mode b, and the control strategy of the three MMCs is the same as that of Mode a. The DC line adopts the frequency variable parameter model and the line length is 2086 km. The sampling frequency is 100 kHz.
In the three operation modes, the following two cases are simulated.
Case 1: 100 grounding short-circuit fault occurs at x=1000 km.
Case 2: metal grounding short-circuit fault occurs on the positive DC line.
For the fault , the simulation results of the FTWs and BTWs on the rectifier and inverter sides, i.e., , and , , respectively, and and are shown in

Fig. 9 Simulation results of FTW and BTW at and for fault . (a) Mode a. (b) Mode b. (c) Mode c.

Fig. 10 Simulation results of FTW and BTW at and for fault . (a) Mode a. (b) Mode b. (c) Mode c.
It can be observed from
As can be observed from Figs.
The working conditions of fault locations, transition resistors, and fault types are considered in three modes to verify the adaptability of the proposed pilot protection scheme. The identification results are shown in
Operation mode | Fault case | () | Result | |
---|---|---|---|---|
Mode a | -P-500 | 300 | A/P | |
-P-1500 | 300 | A/P | ||
-P-2000 | 300 | A/P | ||
-N-1500 | 300 | A/N | ||
-P-500 | 500 | A/P | ||
-P-1500 | 500 | A/P | ||
-P-2000 | 500 | A/P | ||
-D-1000 | 0 | A/DP | ||
0 | B/P | |||
Mode b | -P-500 | 300 | A/P | |
-P-1500 | 300 | A/P | ||
-P-2000 | 300 | A/P | ||
-N-1500 | 300 | A/N | ||
-P-500 | 500 | A/P | ||
-P-1500 | 500 | A/P | ||
-P-2000 | 500 | A/P | ||
-D-1000 | 0 | A/DP | ||
0 | B/P | |||
Mode c | -P-500 | 300 | A/P | |
-P-1500 | 300 | A/P | ||
-P-2000 | 300 | A/P | ||
-N-1500 | 300 | A/N | ||
-P-500 | 500 | A/P | ||
-P-1500 | 500 | A/P | ||
-P-2000 | 500 | A/P | ||
-D-1000 | 0 | A/DP | ||
0 | B/P |
Note: taking f1-P-500 as an example, it indicates a positive line fault at x=500 km for fault f1.
From the
In actual engineering, the influence of noise is inevitable. It is necessary to study the performance of pilot protection under noise interference. In particular, the noise is mixed in the first step during the measurement of electrical quantities. Therefore, Gaussian white noise is added to the voltage and current signals with signal-to-noise ratios (SNRs) of 30 dB and 40 dB. The positive line fault at km for three operation modes with 1000 fault resistance is simulated to demonstrate the robustness performance. The results are shown in
SNR (dB) | Operation mode | x (km) | Result | |
---|---|---|---|---|
30 | Mode a | 500 | 0 | A/P |
Mode b | 500 | 0 | A/P | |
Mode c | 500 | 0 | A/P | |
40 | Mode a | 500 | 0 | A/P |
Mode b | 500 | 0 | A/P | |
Mode c | 500 | 0 | A/P |
Some pilot protection schemes have been proposed using double terminal components [
Pilot protection scheme | The maximum fault resistance (Ω) | Sampling time window (ms) |
---|---|---|
[ | Not declared | 65.0 |
[ | 300 | 0.5 |
[ | 1000 | 5.0 |
[ | 400 | 10.0 |
Proposed | 1000 | 0.2 |
The hybrid cascaded HVDC system has various operation modes, and there are significant differences in the characteristics of DC line faults in different operation modes. Affected by the diverse types of converters, the fault current in some operation modes increases rapidly, and the requirement for protection rapidity is very high. For exemple, the discharge current of MMC on the inverter side is up to 1.7 times as that during normal operation in some modes, which poses a great threat to the safe operation of the system. Therefore, it means that the traditional PDP with a time delay of 1.1 s is no longer applicable. Based on this, this paper proposes a fast pilot protection scheme applicable to multiple operation modes according to the product of the difference voltages between the BTW and FTW on the rectifier side and the difference voltages between the BTW and FTW on the inverter side. This scheme does not require long time delays to eliminate the effect of line distributed capacitance discharge, which meets the requirements of protection rapidity. The simulation results further verify the performance of the proposed pilot protection scheme.
References
G. Tang and Z. Xu, “A LCC and MMC hybrid HVDC topology with DC line fault clearance capability,” International Journal of Electrical Power & Energy Systems, vol. 62, pp. 419-428, Nov. 2014. [Baidu Scholar]
F. Dai, Z. Zhou, and X. Wang, “Single-end protection scheme based on transient power waveshape for hybrid HVDC transmission lines,” Journal of Modern Power Systems and Clean Energy, doi: 10.35833/MPCE.2022.000290 [Baidu Scholar]
S. Lin, D. Mu, L. Liu et al., “A novel fault diagnosis method for DC filter in HVDC systems based on parameter identification,” IEEE Transactions on Instrumentation and Measurement, vol. 69, no. 9, pp. 5969-5971, Sept. 2020. [Baidu Scholar]
J. Wu, H. Li, G. Wang et al., “An improved traveling-wave protection scheme for LCC-HVDC transmission lines,” IEEE Transactions on Power Delivery, vol. 32, no. 1, pp. 106-116, Feb. 2017. [Baidu Scholar]
C. Zhang, G. Song, A. P. S. Meliopoulos et al., “Setting-less nonunit protection method for DC line faults in VSC-MTdc systems,” IEEE Transactions on Industrial Electronics, vol. 69, no. 1, pp. 495-505, Jan. 2022. [Baidu Scholar]
X. Zheng, C. Chao, Y. Weng et al., “High-frequency fault analysis-based pilot protection scheme for a distribution network with high photovoltaic penetration,” IEEE Transactions on Smart Grid, vol. 14, no. 1, pp. 302-314, Jan. 2023. [Baidu Scholar]
S. Yu, X. Wang, and C. Pang, “A pilot protection scheme of DC lines for MMC-HVDC grid using random matrix,” Journal of Modern Power Systems and Clean Energy, vol. 11, no. 3, pp. 950-966, May 2023. [Baidu Scholar]
J. Liu, N. Tai, C. Fan et al., “Transient measured impedance-based protection scheme for DC line faults in ultra high-voltage direct-current system,” IET Generation, Transmission & Distribution, vol. 10, no. 14, pp. 3597-3609, Nov. 2016. [Baidu Scholar]
J. Guo, G. Wang, Y. Liang et al., “Global-sensitivity-based theoretical analysis and fast prediction of traveling waves with respect to fault resistance on HVDC transmission lines,” IEEE Transactions on Power Delivery, vol. 30, no. 4, pp. 2007-2016, Aug. 2015. [Baidu Scholar]
N. Zhang, Q. Chen, H. Wang et al., “Improvement and simulation validation of DC line longitudinal differential protection,” Southern Power System Technology, vol. 3, pp. 56-59, Aug. 2009. [Baidu Scholar]
G. Song, X. Chu, S. Gao et al., “A new whole-line quick-action protection principle for HVDC transmission lines using one-end current,” IEEE Transactions on Power Delivery, vol. 30, no. 2, pp. 599-607, Apr. 2015. [Baidu Scholar]
F. Kong, Z. Hao, and B. Zhang, “Improved differential current protection scheme for CSC-HVDC transmission lines,” IET Generation, Transmission & Distribution, vol. 11, no. 4, pp. 978-986, Mar. 2017. [Baidu Scholar]
X. Li, Y. Dai, X. Ding et al., “HVDC longitudinal differential protection operating characteristic analysis and improvement,” Power System Technology, vol. 40, pp. 283-289, Jan. 2016. [Baidu Scholar]
J. Zheng, M. Wen, and Y. Qin, “A novel differential protection scheme with fault line selection capability for HVDC transmission line,” Proceeding of the CSEE, vol. 38, no. 15, pp. 4350-4358, Aug. 2018. [Baidu Scholar]
T. Zhu and W. Peng, “Research on high impedance earth fault of tian-guang HVDC transmission project,” Power System Protection and Control, vol. 37, pp. 137-140, Dec. 2009. [Baidu Scholar]
J. Ma, X. Pei, W. Ma et al., “A new transmission line pilot differential protection principle using virtual impedance of fault component,” Canadian Journal of Electrical and Computer Engineering, vol. 38, no. 1, pp. 37-44, Mar. 2015. [Baidu Scholar]
W. Xiang, H. Zhang, S. Yang et al., “A differential pilot protection scheme for MMC-based DC grid resilient to communication failure,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 9, no. 5, pp. 5631-5645, Oct. 2021. [Baidu Scholar]
M. Farshad, “A pilot protection scheme for transmission lines of half-bridge MMC-HVDC grids using cosine distance criterion,” IEEE Transactions on Power Delivery, vol. 36, no. 2, pp. 1089-1096, Apr. 2021. [Baidu Scholar]
K. Chen, J. He, M. Li et al., “A similarity comparison based pilot protection scheme for VSC-HVDC grids considering fault current limiting strategy,” Journal of Modern Power Systems and Clean Energy, vol. 11, no. 4, pp. 1305-1315, Jul. 2023. [Baidu Scholar]
X. Yu and L. Xiao, “A DC fault protection scheme for MMC-HVDC grids using new directional criterion,” IEEE Transactions on Power Delivery, vol. 36, no. 1, pp. 441-451, Feb. 2021. [Baidu Scholar]
J. Ma, C. Liu, and Y. Wu, “A pilot directional protection scheme for LCC-HVDC lines based on grounding resistance,” IEEE Transactions on Power Delivery, vol. 37, no. 5, pp. 4460-4473, Oct. 2022. [Baidu Scholar]
Z. Dai, N. Liu, C. Zhang et al., “A pilot protection for HVDC transmission lines based on transient energy ratio of DC filter link,” IEEE Transactions on Power Delivery, vol. 35, no. 4, pp. 1695-1706, Aug. 2020. [Baidu Scholar]
N. Liu, Y. Li, S. Li et al., “A pilot protection for LCC-HVDC transmission lines based on measured surge impedance at tuning frequency,” IEEE Transactions on Power Delivery, vol. 37, no. 3, pp. 2090-2103, Jun. 2022. [Baidu Scholar]
C. Wang, G. Song, X. Kang et al., “Novel transmission-line pilot protection based on frequency-domain model recognition,” IEEE Transactions on Power Delivery, vol. 30, no. 3, pp. 1243-1250, Jun. 2015. [Baidu Scholar]
Q. Huang, G. Zou, S. Zhang et al., “A pilot protection scheme of DC lines for multi-terminal HVDC grid,” IEEE Transactions on Power Delivery, vol. 34, no. 5, pp. 1957-1966, Oct. 2019. [Baidu Scholar]
S. Li, W. Chen, X. Yin et al., “A novel integrated protection for VSC-HVDC transmission line based on current limiting reactor power,” IEEE Transactions on Power Delivery, vol. 35, no. 1, pp. 226-233, Feb. 2020. [Baidu Scholar]
B. Li, Y. Li, J. He et al., “An improved transient traveling-wave based direction criterion for multi-terminal HVDC grid,” IEEE Transactions on Power Delivery, vol. 35, no. 5, pp. 2517-2529, Oct. 2020. [Baidu Scholar]
Z. Liu, W. Ma, S. Wang et al., “The schematic design of hybrid cascaded ultra HVDC and its modification in dynamic model experiment,” Power System Technology, vol. 45, pp. 1214-1222, Mar. 2021. [Baidu Scholar]