Abstract
The increasing penetration of renewable energy sources (RESs) brings great challenges to the frequency security of power systems. The traditional frequency-constrained unit commitment (FCUC) analyzes frequency by simplifying the average system frequency and ignoring numerous induction machines (IMs) in load, which may underestimate the risk and increase the operational cost. In this paper, we consider a multi-area frequency response (MAFR) model to capture the frequency dynamics in the unit scheduling problem, in which regional frequency security and the inertia of IM load are modeled with high-dimension differential algebraic equations. A multi-area FCUC (MFCUC) is formulated as mixed-integer nonlinear programming (MINLP) on the basis of the MAFR model. Then, we develop a multi-direction decomposition algorithm to solve the MFCUC efficiently. The original MINLP is decomposed into a master problem and subproblems. The subproblems check the nonlinear frequency dynamics and generate linear optimization cuts for the master problem to improve the frequency security in its optimal solution. Case studies on the modified IEEE 39-bus system and IEEE 118-bus system show a great reduction in operational costs. Moreover, simulation results verify the ability of the proposed MAFR model to reflect regional frequency security and the available inertia of IMs in unit scheduling.
WITH the aggravation of the global climate issue, low-carbon development has become the consensus of most countries. In 2020, China put forward the goals of carbon peak and carbon neutrality to address this global problem. In this context, the penetration of renewable energy sources (RESs) is gradually increasing while the utilization of fossil and coal resources is being reduced in power systems. While the increasing penetration of RESs reduces greenhouse gas emissions and fuel costs, it also brings new challenges to the security of power systems. Compared with traditional synchronous generators (SGs), RES generators provide weak inertia and lack the ability for PFR. Moreover, the uncertainties of RES worsen the power balance problems. Therefore, it is difficult for power systems with a high penetration of RES to tolerate a large frequency deviation [
At present, most studies on frequency-constrained unit commitment (FCUC) analyze frequency dynamics according to the center of inertia (COI) principle. After ignoring the spatial distribution characteristic of power system frequency, the COI principle usually assumes that the frequency in the whole system is unique and is regarded as the average frequency of the system [
Considering the highly nonlinear calculations of frequency security indices of power systems, the FCUC is mostly modeled with mixed-integer nonlinear programming (MINLP), which cannot be solved efficiently by commercial solvers. In [
Many linearization techniques are also adopted to handle the constraints of frequency security indices, with which the FCUC can be converted to mixed-integer linear programming (MILP). Separable programming is used in [
Recently, the decomposition optimization framework has also been introduced to the FCUC [
Although the above studies provide powerful tools for FCUC, there are some limitations. Firstly, frequency analysis with COI may induce an underestimate of frequency security risk as it ignores the difference in frequency responses in different areas, especially for large-scale systems. Secondly, the load of power systems has complicated frequency response properties. In existing FCUC models, the load is usually aggregated, and only its PFR is modeled as a proportional element. However, studies have shown that the induction machines (IMs) in load can also provide inertia support during disturbances [
In this context, this paper proposes an MFCUC model considering the inertia of IMs. The main contributions are summarized as follows:
1) The frequency dynamics of IMs is modeled in the FCUC by incorporating the inertia support of IMs into the system inertia response. The RoCoF and frequency nadir are improved by the available inertia of IMs, and thus the operational cost for frequency security enhancement is also reduced. It improves the tolerability of power systems for large frequency disturbances, especially those lacking inertia from SGs.
2) The multi-area frequency response (MAFR) model is considered to develop the MFCUC considering the inertia of IMs. Compared with the COI-based SFR model, the differences in frequency dynamics between areas are accurately modeled in the proposed model.
3) A multi-direction decomposition algorithm for solving the MFCUC efficiently is proposed. In addition to traditional optimization cuts, sensitivity cuts are proposed to further enhance the robustness of the decomposition algorithm for MFCUC.
The structure of this paper is organized as follows. Section II introduces the frequency response model. Section III proposes the MFCUC model, and Section IV discusses the solution to MFCUC model. Finally, case studies are performed in Section V and conclusions are drawn in Section VI.
In security assessment studies, the frequency dynamics of power systems is dominated by the response of generators and loads. It should be noted firstly that only conventional SG units and loads participate in frequency response in this paper, while RES generators are not considered as assumed in most studies.
The SGs exchange power with the grid through the change of amplitude and phase of electromotive force (EMF). According to the physical mechanism of SGs, the stator and rotor flux rotate at a synchronous speed, which makes the phase of EMF and the rotor position relatively static. After ignoring the damping factor of SGs, the phase motion of EMF can be directly expressed by the rotor motion
(1) |
In the per-unit form, the system frequency is equal to . Therefore, the frequency response model in the complex frequency domain is:
(2) |
The mechanical power deviation of SGs in the lower-order generator model [
(3) |
In most studies on frequency security, the inertia of load is ignored, and it is only modeled in the PFR as:
(4) |
It is noted that the frequency response model of load only includes the PFR, and its inertia response is neglected. For power systems with high penetration of RESs, the total inertia from SGs decreases with the increase of electric power generation from RES. Although the inertia of loads is smaller compared with that of SGs, it is of great significance for frequency security. In power systems, IMs account for a large proportion that is not less than 50% of the load. It has been found that IMs are able to provide inertial support like SGs when power deviation occurs [
Firstly, the rotor motion equation of IMs is expressed as (5), which is the same as that of SGs.
(5) |
In IMs, the phase of the EMF and the position of the rotor are asynchronous owing to the slip between the stators and the rotors. The rotor motion
(6) |
The available inertia of IMs in (6) is defined as:
(7) |
(8) |
It can be found from (8) that the available inertia of IMs is affected by both rotor inertia and slip frequency regulation. In contrast to the inertia of SGs, which is constant in frequency response analysis, the available inertia of IMs has a time-varying property. More details can be found in [
The COI-based SFR model is widely adopted in the frequency security assessment of power systems, which is shown in
(9) |

Fig. 1 COI-based SFR model with IMs.
In this paper, the massive IM units in power systems with different rated voltage levels are aggregated in the analysis of inertia response. Considering the available inertia of IMs in (7), the transfer function of inertial response Ginertia(s) in
(10) |
It has been demonstrated in [
Unlike the COI-based SFR model, the MAFR model divides a system into several areas, and then each area is represented by its average frequency.
(11) |

Fig. 2 Frequency response in area j of MAFR model with IMs.
As shown in
(12) |
where buses a and b are in areas j and k, respectively.
In the complex frequency domain, we have the Laplace transform of (12) as (13).
(13) |
(14) |
If there are multiple tie-lines between areas j and k, it is easy to have the parameter as (15).
(15) |
The frequency response in area j of MAFR model with IMs in
The MFCUC model considering the inertia of IMs is proposed with the MAFR. The objective function of the proposed MFCUC model is to minimize the operational cost under the operational constraints of power systems and area frequency security constraints.
The objective function of the MFCUC model is constructed as (16)-(20).
(16) |
(17) |
(18) |
(19) |
(20) |
The operational constraints of SGs include the generation limits, the up and down reserve limits, the ramp rate limits, and the minimum startup and shutdown time limits. The first three constraints can be found in [
Compared with the low-frequency issue, the over-frequency issue can be mitigated more practically by tripping the renewable plants or the SGs to eliminate the excessive power in the power system. The low-frequency issue is more challenging in power systems with high penetration of renewable energy due to the lack of inertia from renewable energy. Thus, in this paper, the frequency security constraints for area j are described with the limits of three low-frequency indices, which are expressed as:
(21) |
(22) |
(23) |
In this paper, the frequency dynamics is simulated with the Simulink toolbox in MATLAB. As shown in
As the available inertia of IMs in (7) is highly nonlinear in the time domain, it is difficult to derive the analytical formula of three frequency indices in (21)-(23). This makes it rather challenging to efficiently solve the MFCUC with the inertia of IMs. Thus, a decomposition algorithm is constructed in this section. Firstly, we review the classical decomposition algorithm in existing studies on solving the FCUC with the COI principle. Then, to address the multiple-area frequency issues, we propose a new optimization cut based on sensitivity analysis in the decomposition algorithm. Finally, a multi-direction optimization framework using parallel calculation is proposed to improve the robustness of MFCUC solutions.
Since constraints (21)-(23) are nonlinear and not analytical, it is difficult for commercial optimization solvers to solve the FCUC model directly. As the decomposition algorithms are powerful tools to solve the MINLP, they have been developed for solving the FCUC with the COI principle [
In the decomposition algorithms for FCUC, the inertia Hsg and the unit regulating power are widely used to quantify the frequency response ability. Correspondingly, when constraints (21)-(23) are not satisfied at time , the optimization cuts can be generated as [
(24) |
(25) |
Here, and are defined as:
(26) |
(27) |
As the sensitivity cuts of inertia and unit regulating power only assess frequency security indirectly and are mainly designed for the FCUC with the COI principle, the optimization cuts (24) and (25) may lead to suboptimal solutions when the MAFR is considered. In this context, we propose a series of cuts based on the sensitivities of system frequency indices to further improve the robustness of the decomposition algorithm for MFCUC.
Firstly, let function g denote the MAFR model in Section II-D, which is given as:
(28) |
In this paper, the sensitivity of frequency indices to the commitment status of unit i at time , , is defined as the first-order analytic derivative of function g at the MFCUC solution . With the sensitivity definition, (28) can be approximated as (29).
(29) |
As function g is highly nonlinear and includes binary variables, it is rather difficult to accurately get its first-order analytic derivative. Thus, a simulation-based numerical analysis method is used to calculate the sensitivity in this paper. The steps are described as follows.
Firstly, when the frequency security constraints are violated at time , we approximate the sensitivities of frequency indices to the commitment status of SG units as (30)-(32).
(30) |
(31) |
(32) |
Then, we use the numerical simulation to acquire the index value following the change of commitment status of unit i. In the numerical simulation, the principle for setting the change of commitment status of unit i is described as follows.
1) If , we have . Namely, when the SG unit i is not committed in , its status is changed to be committed in .
2) If , we have . Namely, when the SG unit i is committed in , its status is changed to be not committed in .
After simulating the frequency response with the updated commitment status of the unit i, the sensitivities of frequency indices can be calculated as (30)-(32).
Compared with the amount of inertia and unit regulating capacity, the sensitivities provide more direct optimization information for frequency security improvement. Thus, the optimization cuts based on the sensitivities are proposed as follows.
Suppose is the solution to the master problem in the
(33) |
As the frequency indices in the iteration should be improved, we have the following constraints:
(34) |
(35) |
(36) |
Considering (29)-(32), we can obtain:
(37) |
(38) |
(39) |
Finally, the optimization cuts are derived as:
(40) |
(41) |
(42) |
(43) |
(44) |
(45) |

Fig. 3 Calculation flowchart of proposed sensitivity cuts for MFCUC.
With the construction of the sensitivity cuts for MFCUC, the proposed multi-direction method in

Fig. 4 Flowchart of proposed multi-direction method.
Generally, to apply the proposed MFCUC in the real world, the input parameters in
To verify the effectiveness of the proposed model, case studies are performed on the modified three-area IEEE 39-bus system and the IEEE 118-bus system in this section.

Fig. 5 Topologies of modified multi-area systems. (a) IEEE 39-bus system. (b) IEEE 118-bus system.
In this section, the master problem of MFCUC is solved by Gurobi, and the check of frequency constraints (21)-(23) in subproblems is performed with MATLAB/Simulink. In the Simulink settings, the step size is set to be 0.005 s, and the terminal time is 50 s. According to the simulation results, RoCoF is calculated as an average value in the first ten cycles, and is the frequency at s. For the frequency security constraints in FCUC, RoCoFmax, fnadir,min, and f∞,min are set to be 0.50 Hz/s, 49.50 Hz, and 49.70 Hz, respectively. It should be noted that all the frequency indices in case studies are represented by the worst values among multiple areas at the same time.
The parameters of IMs in this paper are also listed in [
(46) |
To verify the effectiveness of FCUC with different optimization cuts, the following six cases are considered for comparison. The optimization cuts in Cases 2-4 are generated for the total frequency response resources in the power system, while the optimization cuts in Cases 5 and 6 are generated for each area. For example, in Case 2, a cut of the total inertia in the power system is generated for the master problem when the frequency security is not guaranteed. And in Case 5, the inertia cuts are generated for three areas, respectively.
Case 1: conventional UC without frequency constraints.
Case 2: MFCUC with the inertia cut for the total system.
Case 3: MFCUC with the unit regulating power cut for the total system.
Case 4: MFCUC with the proposed sensitivity cut.
Case 5: MFCUC with the inertia cuts for each area.
Case 6: MFCUC with the unit regulating power cut for each area.
Cases 2-6 are solved in the MAFR model with IMs. The simulation results of Cases 1-6 are compared in
Case | Iteration | RoCoFmax (Hz· | fnadir,min (Hz) | f∞,min (Hz) | Cost (M$) |
---|---|---|---|---|---|
Case 1 | 0.7683 | 49.3948 | 49.5868 | 1.2024 | |
Case 2 | 8 | 0.4923 | 49.6068 | 49.7468 | 1.2159 |
Case 3 | 10 | 0.4923 | 49.6043 | 49.7416 | 1.2186 |
Case 4 | 4 | 0.4923 | 49.5932 | 49.7085 | 1.2146 |
Case 5 | No solution | ||||
Case 6 |

Fig. 6 Three indices during each period among three areas for Cases 1-4. (a) RoCoFmax. (b) fnadir,min. (c) f∞,min.
From

Fig. 7 UC schemes of Cases 1-4. (a) Case 1. (b) Case 2. (c) Case 3. (d) Case 4.
The results also show that the optimization cuts in Cases 5 and 6 for each area may make the FCUC infeasible after several iterations. For example, after the first iteration of FCUC in Case 5, we have the frequency index RoCoF2,11 as 0.5076 Hz/s and RoCoF3,11 as 0.5056 Hz/s. This indicates that the limit of RoCoFmax is violated in areas 2 and 3 at the 1
To illustrate the differences between the COI-based SFR model and the MAFR model in MFCUC, we consider the following Cases 7 and 8 for comparison with Case 4.
Case 7: FCUC with the proposed sensitivity cuts that consider the COI-based SFR model with IMs.
Case 8: frequency responses in the solution of Case 7 are simulated by the MAFR model.
Case | RoCoFmax (Hz· | fnadir,min (Hz) | f∞,min (Hz) | Cost (M$) |
---|---|---|---|---|
Case 4 | 0.4923 | 49.5932 | 49.7085 | 1.2146 |
Case 7 | 0.4209 | 49.5602 | 49.7031 | 1.2102 |
Case 8 | 0.5924 | 49.5698 | 49.7152 |

Fig. 8 Three indices during each period among three areas for Cases 4, 7, and 8. (a) RoCoFmax. (b) fnadir,min. (c) f∞,min.
To further illustrate the difference between the frequency response models in FCUC, we take the th hour in

Fig. 9 Comparison of dynamic frequency response between MAFR and COI-based SFR model.
It is shown in
To illustrate the impact of IMs on frequency response, we consider the following cases for comparison. For simplicity, we set all the SG units committed at the
Case 9: MAFR model with IMs.
Case 10: MAFR model without IMs.

Fig. 10 Three indices during each period among three areas for Cases 9 and 10. (a) RoCoFmax. (b) fnadir,min. (c) f∞,min.
We also take the nd hour as an example to compare the dynamic frequency response in Cases 9 and 10. The simulation is performed with a power deviation in area 3, and the results are shown in

Fig. 11 Comparison of dynamic frequency response between Cases 9 and 10.
Finally, Case 11 is considered to further illustrate the impact of IMs on MFCUC.
Case 11: MFCUC with the proposed sensitivity cut, in which is set to be 0.3 and the other parameters are the same as those in Case 4.
Cases | λ | RoCoFmax (Hz· | fnadir,min (Hz) | f∞,min (Hz) | Cost (M$) |
---|---|---|---|---|---|
Case 4 | 0.6 | 0.4923 | 49.5932 | 49.7085 | 1.2146 |
Case 11 | 0.3 | 0.4981 | 49.6048 | 49.7497 | 1.2213 |

Fig. 12 Inertia provided by SGs for each area during each period. (a) Area 1. (b) Area 2. (c) Area 3.
In this subsection, we further validate the proposed MFCUC model on the IEEE 118-bus system. Similar to Section V-A, the following Cases 12-16 are considered.
Case 12: conventional UC without frequency constraints for the IEEE 118-bus system.
Case 13: MFCUC with the inertia cut for the total system, in which the inertia of IMs is considered in the MAFR model.
Case 14: MFCUC with the unit regulating power cut for the total system, in which the inertia of IMs is considered in the MAFR model.
Case 15: MFCUC with the proposed sensitivity cut, in which the inertia of IMs is considered in the MAFR model.
Case 16: MFCUC with the proposed sensitivity cut, in which the inertia of IMs is not considered in the MAFR model.
Cases | Iteration | RoCoFmax (Hz· | fnadir,min (Hz) | f∞,min (Hz) | Cost (M$) |
---|---|---|---|---|---|
Case 12 | 0.8310 | 49.3082 | 49.6195 | 6.9891 | |
Case 13 | 50 | 0.4981 | 49.5763 | 49.8054 | 7.4782 |
Case 14 | 44 | 0.4982 | 49.5744 | 49.8022 | 7.4864 |
Case 15 | 40 | 0.4997 | 49.5016 | 49.7392 | 7.0795 |
Case 16 | 5 | 0.4181 | 49.5310 | 49.7512 | 7.2294 |

Fig. 13 Three indices during each period among three areas for Cases 12-16. (a) RoCoFmax. (b) fnadir,min. (c) f∞,min.
It can be observed from
The results also show that the cost increments in Cases 15 and 16 are slighter than those in Cases 13 and 14. The slightest cost increment is 1.3% in Case 15 while the greatest one is 7.1% in Case 14. The reason is that the proposed sensitivity cut can help the operators improve the uniformity of the inertia distribution in the multi-area power system while the operators are required to increase the total inertia due to inertia cut or the unit regulating power cut. As a result, the increment of the number of committed units is less when the sensitivity cut is considered. Additionally, the UC in Case 15 is more economical than that in Case 16 as the inertia of IMs is considered.
In this paper, an MFCUC considering the MAFR model with the inertia of IMs is developed to address the frequency security issues of power systems with a high penetration of RESs. To solve the proposed MFCUC, this paper proposes a multi-direction optimization framework with sensitivity cuts. The conclusions are drawn as follows.
1) The proposed MFCUC is more precise than traditional FCUC with the COI-based SFR model. It can capture the spatial distribution characteristic of frequency response and thus avoid underestimating frequency violation risk.
2) The consideration of IMs in the MFCUC can enhance the frequency response with the improvement of the RoCoF index and frequency nadir index, which may reduce the operational cost of power systems compared with the MFCUC without the consideration of IMs.
3) The proposed sensitivity cuts can further improve the robustness of the decomposition algorithm for solving the nonlinear MFCUC, especially when it is not practical to generate the traditional cuts of inertia and unit regulating capacity for each area instead of the whole power system in MFCUC.
Nomenclature
Symbol | —— | Definition |
---|---|---|
A. | —— | Indices and Sets |
* | —— | Per-unit values |
—— | Set of bus indices for area j | |
Δ | —— | Index of variations, deviations, and increments |
τ0, τ | —— | Indices of initial values and current values |
A | —— | Set of tie-lines |
i | —— | Index of generators |
j, k | —— | Indices of areas |
n | —— | Index of iterations |
t | —— | Index of time intervals |
—— | Value of variables x in the solution to current master problem | |
B. | —— | Parameters |
—— | Unit regulating power of synchronous generators (SGs) | |
λ | —— | Ratio of induction machine (IM) load to the total load in area j (default value as 0.6) |
—— | Fuel cost factors of SG unit i | |
—— | Up and down reserve factors of SG unit i | |
—— | Penalty factors of wind and photovoltaic (PV) curtailment | |
—— | Fraction of total power generated by the turbine of SGs | |
—— | Security threshold of settling frequency index | |
—— | Rated frequency of power systems | |
—— | Security threshold of frequency nadir index | |
—— | Rotor inertia of IMs | |
—— | Rotor inertia of SGs | |
Ke | —— | Load rate of IMs |
—— | Load regulating factor | |
—— | Number of SG units | |
—— | Number of wind plants and PV stations | |
—— | Rated capacity of SG unit i | |
—— | Rated capacity of IMs | |
—— | Security threshold of rate of change of frequency (RoCoF) index | |
—— | Startup cost of SG unit i | |
T | —— | Number of periods in multi-area frequency-constrained unit commitment (MFCUC) |
—— | Parameters in inertia of IM model | |
—— | Ratio of variation of transmission power to phase angle difference between areas j and k | |
—— | Reheat time constant of SGs | |
—— | Impedance of line l1 | |
C. | —— | Variables |
—— | Increment of bus phase angle | |
—— | Variation of power flow on line l1 | |
—— | Power deviation in area j | |
—— | Deviation of electromagnetic power in primary frequency response (PFR) | |
—— | Deviation of load on actual frequency | |
—— | Deviation of load on rated frequency | |
—— | Fluctuation of renewable energy source (RES) generation | |
—— | Total power that is transmitted from area j to neighboring areas | |
—— | Rotation speed of IMs | |
—— | Synchronous speed of SGs | |
—— | Total sensitivity of index at time τ | |
—— | Operation cost in objective function | |
—— | Reserve cost in objective function | |
—— | Startup cost of SGs in objective function | |
—— | Total sensitivity of index at time τ | |
—— | RES curtailment cost in objective function | |
—— | Total sensitivity of RoCoF index at time τ | |
—— | Frequency index at time τ | |
—— | System frequency | |
—— | Settling frequency | |
—— | Frequency nadir | |
—— | Total inertia and unit regulating power at time τ | |
—— | Available inertia of IMs | |
—— | Mechanical power of SGs | |
—— | Electromagnetic power of SGs | |
—— | Mechanical power of IMs | |
—— | Electromagnetic power of IMs | |
—— | Generation of SG unit i at time τ | |
—— | Up and down reserves of SG unit i at time τ | |
—— | Load of bus k on rated frequency at time τ | |
—— | Forecast generation of wind and PV | |
—— | Real generation of wind and PV | |
RoCoF | —— | Value of RoCoF index |
—— | Sensitivity of index to status of SG unit i at time τ | |
—— | Sensitivity of frequency indices to status of SG unit i at time τ | |
—— | Sensitivity of index to status of SG unit i at time τ | |
—— | Sensitivity of RoCoF index to status of SG unit i at time τ | |
—— | Binary variable of commitment status of SG unit i at time τ (equals 1 if unit is on and 0 otherwise) | |
—— | Vector of commitment status of SG units at time τ |
References
Z. Zhou, L. Shi, and Y. Chen, “An optimal over-frequency generator tripping strategy for regional power grid with high penetration level of renewable energy,” Journal of Modern Power Systems and Clean Energy, vol. 9, no. 5, pp. 1007-1017, Sept. 2021. [Baidu Scholar]
R. Yan, T. K. Saha, F. Bai et al., “The anatomy of the 2016 south Australia blackout: a catastrophic event in a high renewable network,” IEEE Transactions on Power Systems, vol. 33, no. 5, pp. 5374-5388, Sept. 2018. [Baidu Scholar]
NGESO. (2019, Sept.). Technical report on the events of 9 August 2019. [Online]. Available: https://www.ofgem.gov.uk/system/files/docs/2019/09/esotechnicalreport-final.pdf [Baidu Scholar]
F. Milano and Á. O. Manjavacas, “Frequency-dependent model for transient stability analysis,” IEEE Transactions on Power Systems, vol. 34, no. 1, pp. 806-809, Jan. 2019. [Baidu Scholar]
M. L. Chan, R. D. Dunlop, and F. Schweppe, “Dynamic equivalents for average system frequency behavior following major distribances,” IEEE Transactions on Power Apparatus and Systems, vol. PAS-91, no. 4, pp. 1637-1642, Jul. 1972. [Baidu Scholar]
P. M. Anderson and M. Mirheydar, “A low-order system frequency response model,” IEEE Transactions on Power Systems, vol. 5, no. 3, pp. 720-729. Aug. 1990. [Baidu Scholar]
L. Badesa, F. Teng, and G. Strbac, “Conditions for regional frequency stability in power system scheduling – Part I: theory,” IEEE Transactions on Power Systems, vol. 36, no. 6, pp. 5558-5566, Nov. 2021. [Baidu Scholar]
L. Che, X. Shen, and M. Shahidelpour, “Primary frequency response based rescheduling for enhancing microgrid resilience,” Journal of Modern Power Systems and Clean Energy, vol. 7, no. 4, pp. 696-704, Jul. 2019. [Baidu Scholar]
H. Gu, R. Yan, T. K. Saha et al., “System strength and inertia constrained optimal generator dispatch under high renewable penetration,” IEEE Transactions on Sustainable Energy, vol. 11, no. 4, pp. 2392-2406, Oct. 2020. [Baidu Scholar]
C. Mosca, E. Bompard, G. Chicco et al., “Technical and economic impact of the inertia constraints on power plant unit commitment,” IEEE Open Access Journal of Power and Energy, vol. 7, pp. 441-452, Oct. 2020. [Baidu Scholar]
J. Lu, Y. Mao, L. Liu et al., “Unit commitment of power system with wind power and photovoltaic considering frequency safety constraint,” in Proceedings of 2021 IEEE Sustainable Power and Energy Conference (iSPEC), Nanjing, China, Dec. 2021, pp. 1486-1493. [Baidu Scholar]
Y. Zhang, H. Cui, J. Liu et al., “Encoding frequency constraints in preventive unit commitment using deep learning with region-of-interest active sampling,” IEEE Transactions on Power Systems, vol. 37, no. 3, pp. 1942-1955, May 2022. [Baidu Scholar]
D. T. Lagos and N. D. Hatziargyriou, “Data-driven frequency dynamic unit commitment for island systems with high RES penetration,” IEEE Transactions on Power Systems, vol. 36, no. 5, pp. 4699-4711, Sept. 2021. [Baidu Scholar]
N. Nguyen, V. Johnson, and J. Mitra, “Environmental-economic dispatch of power system in the presence of wind generation,” in Proceedings of 2015 North American Power Symposium (NAPS), Charlotte, USA, Oct. 2015, pp. 1-6. [Baidu Scholar]
C. J. Ferrandon-Cervantes, B. Kazemtabrizi, and M. C. M. Troffaes, “Inclusion of frequency stability constraints in unit commitment using separable programming,” Electric Power Systems Research, vol. 203, p. 107669, Feb. 2022. [Baidu Scholar]
C. Zhang, L. Liu, H. Cheng et al., “Frequency-constrained co-planning of generation and energy storage with high-penetration renewable energy,” Journal of Modern Power Systems and Clean Energy, vol. 9, no. 4, pp. 760-775, Jun. 2021. [Baidu Scholar]
H. Ahmadi and H. Ghasemi, “Security-constrained unit commitment with linearized system frequency limit constraints,” IEEE Transactions on Power Systems, vol. 29, no. 4, pp. 1536-1545, Jul. 2014. [Baidu Scholar]
S. S. Oskouee, S. Kamali, and T. Amraee, “Primary frequency support in unit commitment using a multi-area frequency model with flywheel energy storage,” IEEE Transactions on Power Systems, vol. 36, no. 6, pp. 5105-5119, Apr. 2021. [Baidu Scholar]
F. Perez-Illanes, E. Alvarez-Miranda, C. Rahmann et al., “Robust unit commitment including frequency stability constraints,” Energies, vol. 9, no. 11, pp. Nov. 2016. [Baidu Scholar]
N. Yang, Z. Dong, L. Wu et al., “A comprehensive review of security-constrained unit commitment,” Journal of Modern Power Systems and Clean Energy, vol. 10, no. 3, pp. 562-576, May 2022. [Baidu Scholar]
Y. Yang, J. Peng, C. Ye et al., “A criterion and stochastic unit commitment towards frequency resilience of power systems,” IEEE Transactions on Power Systems, vol. 37, no. 1, pp. 640-652, Jul. 2021. [Baidu Scholar]
S. Jiang, X. Zhao, G. Pan et al., “A novel robust frequency-constrained unit commitment model with emergency control of HVDC,” Energy Reports, vol. 8, pp. 57-67, Oct. 2022. [Baidu Scholar]
J. Ye, T. Lin, R. Bi et al., “Unit commitment in isolated grid considering dynamic frequency constraint,” in Proceedings of 2016 IEEE PES General Meeting (PESGM), Boston, USA, Jul. 2016, pp. 1-5. [Baidu Scholar]
D. Wang and X. Yuan, “Available inertia estimation of induction machine in electromechanical timescale and its effects on frequency dynamics of power systems with renewable energy,” Proceedings of CSEE, vol. 38, no. 24, pp. 7258-7266, Dec. 2018. [Baidu Scholar]
D. Wang, X. Yuan, W. Shen et al., “Available inertia estimation of induction machine and its effect on frequency response of power systems with wind penetration,” in Proceedings of 2019 IEEE Innovative Smart Grid Technologies–Asia (ISGT Asia), Chengdu, China, May 2019, pp. 1783-1787. [Baidu Scholar]
Y. Wen, J. Zhan, C. Y. Chung et al., “Frequency stability enhancement of integrated AC/VSC-MTDC systems with massive infeed of offshore wind generation,” IEEE Transactions on Power Systems, vol. 33, no. 5, pp. 5135-5146, Sept. 2018. [Baidu Scholar]
O. I. Elgerd. and C. E. Fosha, “Optimum megawatt-frequency control of multiarea electric energy systems,” IEEE Transactions on Power Apparatus and Systems, vol. PAS-89, no. 4, pp. 556-563, Apr. 1970. [Baidu Scholar]
Q. Yang, J. Wang, H. Yin et al., “A fast calculation method for long-term security-constrained unit commitment of large-scale power systems with renewable energy,” Journal of Modern Power Systems and Clean Energy, vol. 10, no. 5, pp. 1127-1137, Sept. 2022. [Baidu Scholar]
M. Ban, J. Yu, M. Shahidehpour et al., “Integration of power-to-hydrogen in day-ahead security-constrained unit commitment with high wind penetration,” Journal of Modern Power Systems and Clean Energy, vol. 5, no. 3, pp. 337-349, May 2017. [Baidu Scholar]
R. Lu, T. Ding, B. Qin et al., “Multi-stage stochastic programming to joint economic dispatch for energy and reserve with uncertain renewable energy,” IEEE Transactions on Sustainable Energy, vol. 11, no. 3, pp. 1140-1151, Jul. 2020. [Baidu Scholar]
T. Amraee, M. G. Darebaghi, A. Soroudi et al., “Probabilistic under frequency load shedding considering RoCoF relays of distributed generators,” IEEE Transactions on Power Systems, vol. 33, no. 4, pp. 3587-3598, Jul. 2018. [Baidu Scholar]
LX2000Xu. (2023, Jan.). Input parameters. [online]. Available: https://github.com/LX2000Xu/Data [Baidu Scholar]