Abstract
The equivalent impedance parameters of loads have been widely used to identify and locate the harmonic sources. However, the existing calculation methods suffer from outliers caused by the zero-crossing of the denominator. These outliers can result in inaccuracy and unreliability of harmonic source location. To address this issue, this paper proposes an innovative method of equivalent impedance parameter calculation of three-phase symmetrical loads that avoid outliers. The correctness and effectiveness of the proposed method are verified by simulations on Simulink using actual monitoring data. The results show that the proposed method is not only simple and easy to implement but also highly accurate.
WITH a large number of distributed generations and nonlinear loads in power grids, harmonic distortion has become one of the most common and significant power-quality-related problems, which has attracted increasing research attention in recent years [
Nonlinear loads are considered as harmonic sources since they can actively emit harmonic currents to the power grid, which contribute to the harmonic voltage at the point of common coupling (PCC). However, linear loads cannot actively emit a harmonic current but can produce a harmonic current in the presence of background harmonic voltages. Therefore, harmonic magnitude measurement of load currents cannot be used directly for harmonic source location [
Researchers have long been dedicated to developing efficient harmonic source location methods to lay a foundation for harmonic responsibility division and harmonic mitigation. The existing harmonic source location methods can be roughly divided into two categories: methods based on an equivalent circuit model, and methods based on harmonic state estimation.
The former methods divide an equivalent circuit model into two sides, i.e., the system side and the user side at the PCC, and locate the harmonic source using various positioning techniques such as active or reactive harmonic power direction and harmonic impedance information [
The harmonic source location methods based on harmonic state estimation can determine the distribution of harmonic voltage and harmonic current of the whole system, allowing it to trace multiple harmonic sources throughout the system [
As the time-varying equivalent impedance parameters of the load are the primary cause of harmonic generation in nonlinear loads, a harmonic source location method based on parameter identification has been proposed in [
The purpose of this paper is to improve the calculation method of equivalent impedance parameters of three-phase symmetrical loads to reduce the influence of outliers on the harmonic source location.
The main contributions of this paper can be summarized as follows.
1) A new method for equivalent impedance parameter calculation of three-phase symmetrical loads is proposed to avoid the problem of outliers.
2) The proposed method is applied to the analysis of nonlinear loads, and its advantages over the existing methods in the field of harmonic source location are verified.
The rest of this paper is organized as follows. Section II introduces the basic principles of the parameter identification method for harmonic source location and formulates the outlier problem. Section III presents a novel equivalent impedance calculation method of three-phase symmetrical loads. Section IV presents case study that validates the proposed method by simulations using actual monitoring data. Finally, Section V concludes this paper and presents future work.
Two types of equivalent load models, i.e., a parallel impedance model and a series impedance model, have been commonly used in harmonic source location based on a parameter identification method. As shown in

Fig. 1 Equivalent series impedance model in time domain.
In the series impedance model, it holds that:
(1) |
Equations can be established by two adjacent sample data points using voltage and current signal sequences to determine the equivalent impedance parameters. Equations in the series impedance model can be established as follows:
(2) |
where are the adjacent sample point values in the corresponding signal sequences, and ().
For obtaining a harmonic source location, the emitted harmonic magnitude can be used to determine harmonic sources using active models such as the Norton model at harmonic frequencies [
Nonlinear loads are considered harmonic sources in power grids and can be identified by the non-linearity index (NLI) [
The solution to (2) is given by:
(3) |
When the denominators in (3) cross zero, outliers will occur in equivalent impedance waveforms. Reference [
(4a) |
(4b) |
where h is the order of harmonic current; is the

Fig. 2 Outliers in equivalent impedance waveforms.
In addition, in [
In the actual operation of a power grid, the main causes of harmonic pollution are high-capacity three-phase loads in industrial production and new centralized energy power plants.
Such loads are usually connected to the grid via three-phase wiring at the voltage level of 10 kV or above, and most of them are equipped with power quality monitoring devices. Therefore, (1) can be re-written as:
(5) |
where and are the sample point values of three-phase voltage and current, respectively; and and are the resistance and inductance of a three-phase load, respectively.
Assuming a three-phase symmetrical load, namely and , (5) can be re-written as follows:
(6) |
Using the fast Fourier transformation (FFT), the current is decomposed into the sum of harmonic currents, which can be expressed by:
(7) |
where is the instantaneous value of the
Combining (6) and (7) yields:
(8) |
Then transformation is adopted to three-phase voltage and current in (6), which can be written as follows:
(9) |
Further, R and L can be solved by (9), but this process involves derivatives, which makes it complex for practical applications, so it needs to be simplified. The equations of instantaneous three-phase current are given by [
(10) |
where ; , and are the peak amplitudes of the
Considering the three-phase symmetry, for the

Fig. 3 Phasor diagram of the
For the convenience of analysis, the initial phase angle in (10) is assumed to be zero. Next, two cases presented in
For the sequence presented in
(11) |
(12) |
(13) |
(14) |
where , , and are the amplitudes of the
For the vector diagram presented in
(15) |
(16) |
Then, derivatives of and can be expressed as:
(17) |
(18) |
Based on the above analysis, (9) can be re-written as:
(19) |
(20) |
where X is the equivalent reactance at fundamental frequency. Sample point values of three-phase voltage and current are processed by the FFT, and the abc- transformation is performed on virtual waveforms of each harmonic current; then, equivalent impedance parameters are solved by (19). The solution to (19) is given by:
(21) |
(22) |
In comparison to (3), the denominators of (21) and (22) are always greater than zero for three-phase symmetrical loads; thus, (19) avoids abnormal values caused by zero-crossing of the denominator.
However, the above-mentioned algorithm employs the FFT, which requires selecting the data cycle. For fewer cycles, the accuracy of the virtual waveform is limited. Conversely, if there are too many cycles, the tracking speed of the algorithm of the parameters’ change will be decreased. Assuming that the abc- transformation is directly adopted to the three-phase voltage and current, the following expression can be obtained:
(23) |
Compared with (19), the coefficient h of each harmonic current in (19) is ignored, so there are relative deviations of the elements in the first and second rows in the second column, which can be expressed as:
(24) |
(25) |
To avoid the FFT process and increase the parameter-change tracking speed of the algorithm, the above-given relative deviations are ignored, and a new equation based on the idea of regression is constructed as:
(26) |
The solution to (26) is expressed by:
(27) |
(28) |
Therefore, an innovative method for the calculation of equivalent impedance parameters of three-phase symmetrical loads is obtained, which is given by (19) and (26). In the following section, this method is applied to various practical cases to demonstrate its effectiveness and superiority.
Based on the equivalent series impedance model shown in
1) The resistance is 10 , and the inductance is 0.01 H, which represent a linear load.
2) The resistance is a 200 Hz sine wave with amplitude between 10-20 , and the inductance is always 0.015 H.
3) The resistance is 10 , and the inductance is a 200 Hz sine wave with amplitude between 0.01-0.02 H.
4) The resistance is a 100 Hz triangular wave with an amplitude between 10-20 , and the inductance is a 200 Hz sine wave with amplitude between 0.01 H and 0.02 H.
The first case is configured to examine the precision under the assumption of constant equivalent impedance; the second and third cases are designed to examine the precision of solution when one of the resistance and inductance is constant while the other varies with time; the fourth case is used to evaluate the solving precision when the resistance and inductance are both time-varying.
Equations (

Fig. 4 Calculated resistance and inductance waveforms at the maximum frequency of 2550 Hz in FFT analysis. (a) Case 1. (b) Case 2. (c) Case 3. (d) Case 4.
Case | Parameter | Relative error (%) | |||||
---|---|---|---|---|---|---|---|
Method I | Method Ⅱ | Method Ⅲ | |||||
μ | σ | μ | σ | μ | σ | ||
1 | R | 0.7710 |
9×1 | 0.5013 | 0.3743 | 0.3855 |
1×1 |
L |
2×1 |
6×1 | 1.2257 | 0.9834 | 0.0100 |
6×1 | |
2 | R | 4.0816 | 3.8469 | 0.6377 | 0.4779 | 3.8469 | 1.2965 |
L | 19.2825 | 19.6920 | 1.2965 | 0.9571 | 3.8522 | 2.0427 | |
3 | R | 3.2563 | 2.8659 | 0.6877 | 0.5271 | 0.9411 | 0.6539 |
L | 4.3843 | 3.4761 | 1.2267 | 0.9718 | 4.3401 | 2.2373 | |
4 | R | 7.0512 | 4.0217 | 1.4753 | 1.3489 | 4.7448 | 2.3646 |
L | 39.1099 | 31.9961 | 4.2474 | 3.2070 | 6.2682 | 3.8958 |

Fig. 5 Mean deviation of relative error of calculated impedance parameters. (a) Resistance for Case 1. (b) Resistance for Case 2. (c) Resistance for Case 3. (d) Resistance for Case 4. (e) Inductance for Case 1. (f) Inductance for Case 2. (g) Inductance for Case 3. (h) Inductance for Case 4.
Except for Case 1, the accuracy of Methods II and III is much better than that of Method I. Furthermore, the accuracy of Method III is slightly lower than that of Method II since it ignores the deviation of (24) and (25). In addition, compared with the proposed method, the equivalent impedance waveforms of nonlinear load obtained by Method I deviate significantly from the real waveforms.
Since the equivalent impedance is constant in Case 1, which does not meet the generation of zero-crossing of the denominator [

Fig. 6 Deviation between superposition of virtual harmonic current waveform and original waveform.
As shown in

Fig. 7 Hilbert spectrum of equivalent impedance waveforms obtained by Method Ⅱ for Case 1 when the maximum frequency in FFT analysis is 2550 Hz. (a) Hilbert spectrum of equivalent resistance waveform. (b) Hilbert spectrum of equivalent inductance waveform.
If the maximum frequency for the FFT analysis is 5050 Hz, and the maximum harmonic order considered is 100, the Hilbert spectrum of equivalent impedance waveforms solved by Method II for Case 1 is shown in

Fig. 8 Hilbert spectrum of equivalent impedance waveforms obtained by Method Ⅱ for Case 1 when the maximum frequency for FFT analysis is 5050 Hz. (a) Hilbert spectrum of equivalent resistance waveform. (b) Hilbert spectrum of equivalent inductance waveform.
As illustrated in Figs.

Fig. 9 Resistance and inductance waveforms solved by Method II before and after filtering. (a) Before filtering. (b) After filtering.
The strengths, weaknesses, and application scenarios of the three methods are obtained based on the results of the case in this subsection, and are shown in
Method | Strength | Weakness | Application scenarios |
---|---|---|---|
Method I | Easy to implement | Prone to outliers | Single and three-phase loads under non-zero-crossing conditions |
Method Ⅱ | Avoiding outliers; high accuracy for nonlinear loads | Requiring more than adjacent sample point values | Three-phase symmetrical loads |
Method Ⅲ | Avoiding outliers; high tracking speed of parameters’ change | Less accurate for nonlinear loads | Three-phase symmetrical loads |
Modern nonlinear loads can be roughly classified into three types based on the harmonic current generation mechanism type, i.e., ferromagnetic saturation, electric arc, and power electronics, and their representatives are denoted by transformers, electric arc furnaces (EAFs), and rectifiers, respectively.
The Simulink simulation scheme of three-phase comprehensive loads is shown in

Fig. 10 Simulink simulation of three-phase comprehensive loads.
In
Load | Parameter | Value |
---|---|---|
Linear load | Resistance (Ω) | 120 |
Inductance (H) | 0.1 | |
EAF | Equivalent resistance (μΩ) | 419.9 |
Equivalent inductance (μH) | 9.55 | |
Capacity (MVA) | 40 | |
Rectifier | Number of pulses | 12 |
Resistance (Ω) | 250 | |
Inductance (H) | 0.5 |
The equivalent impedance waveforms of comprehensive loads obtained by the three methods are shown in

Fig. 11 Equivalent impedance waveforms of comprehensive loads obtained by different methods. (a) Linear load. (b) EAF. (c) Rectifier.
The results of the NLI and total harmonic current distortion THDi are shown in
Load | NLI | THDi (%) | ||
---|---|---|---|---|
Method I | Method Ⅱ | Method Ⅲ | ||
Linear load | 0.2105 | 0.0055 | 0.0056 | 0.97 |
EAF | 1.5407 | 0.3478 | 0.3165 | 9.30 |
Rectifier | 0.9220 | 0.3575 | 0.3892 | 11.02 |
Based on
In this test, a 55 t EAF in a steelmaking plant is used as an example. The power supply diagram is shown in

Fig. 12 Power supply diagram of 55 t EAF.
The measured three-phase voltage and current waveforms of the EAF whose transformer’s rated capacity is 38 MVA are shown in

Fig. 13 Measured three-phase voltage and current waveforms obtained by EAF. (a) Current waveforms. (b) Voltage waveforms.
Based on the measured data, the equivalent impedance waveforms are obtained, as shown in

Fig. 14 Equivalent impedance waveforms of EAF’s measured data.
NLI | THDi (%) | ||
---|---|---|---|
Method I | Method Ⅱ | Method Ⅲ | |
0.4177 | 0.1649 | 0.1656 | 4.80 |
Based on the results in
The above analysis demonstrates the applicability of the proposed method in practical engineering.
In this paper, an efficient method of equivalent impedance parameter calculation of three-phase symmetrical loads for harmonic source location is proposed. Combined with the FFT and abc- transformation, a set of equations based on the relationship between current and voltage of the equivalent circuit are constructed to solve equivalent impedance waveforms, which generally avoids outliers caused by the zero-crossing of the denominator. The results obtained under three cases are discussed, and the corresponding conclusions can be summarized as follows.
1) Compared with the traditional equivalent impedance parameter calculation method, the proposed method is not only simpler, easier to implement, and more accurate, but also able to avoid outliers.
2) The results show that the waveforms solved by one of the calculation equations proposed in this paper contain a small-amplitude high-frequency oscillation, whose frequency is closely related to the specified maximum frequency in the FFT analysis. Therefore, these components can be filtered using an appropriate low-pass filter.
3) According to equivalent impedance waveforms solved using the proposed method, the difference in the NLI between the linear and the nonlinear loads is significant, which is helpful in harmonic source localization.
References
F. M. Camilo, M. E. Almeida, R. Castro et al., “Multi-conductor line models for harmonic load-flow calculations in LV networks with high penetration of PV generation,” Journal of Modern Power Systems and Clean Energy, vol. 10, no. 5, pp. 1288-1301, Sept. 2022. [Baidu Scholar]
Y. Pu, Q. Shu, and F. Xu, “Harmonic amplification analysis of cable lines with distributed parameters based on Kalman filter and convolution inversion,” Journal of Modern Power Systems and Clean Energy, vol. 11, no. 6, pp. 1804-1813, Nov. 2023. [Baidu Scholar]
IEEE Recommended Practice and Requirements for Harmonic Control in Electric Power Systems, IEEE Standard 519-2014, 2014. [Baidu Scholar]
M. Dalali and A. Jalilian, “Indices for measurement of harmonic distortion in power systems according to IEC 61000-4-7 standard,” IET Generation Transmission & Distribution, vol. 9, no. 14, pp. 1903-1912, Nov. 2015. [Baidu Scholar]
F. Xu, C. Wang, K. Guo et al., “Harmonic sources’ location and emission estimation in underdetermined measurement system,” IEEE Transactions on Instrumentation and Measurement, vol. 70, pp. 1-11, May 2021. [Baidu Scholar]
K. Tang and C. Shen, “Harmonic emission level assessment method based on parameter identification analysis,” IET Generation Transmission & Distribution, vol. 13, no. 7, pp. 976-983, Apr. 2019. [Baidu Scholar]
L. Cristaldi and A. Ferrero, “Harmonic power flow analysis for the measurement of the electric power quality,” IEEE Transactions on Instrumentation and Measurement, vol. 44, no. 3, pp. 683-685, Jun. 1995. [Baidu Scholar]
W. Xu and Y. Liu, “A method for determining customer and utility harmonic contributions at the point of common coupling,” IEEE Transactions on Power Delivery, vol. 15, no. 2, pp. 804-811, Apr. 2000. [Baidu Scholar]
R. Azouaou, S. Rabahallah, and S. Leulmi, “Study of the direction of the harmonic injections in the electrical power systems,” in Proceedings of 39th International Universities Power Engineering Conference, Bristol, England, Sept. 2004, pp. 944-947. [Baidu Scholar]
C. Li, W. Xu, and T. Tayjasanant, “A ‘critical impedance’-based method for identifying harmonic sources,” IEEE Transactions on Power Delivery, vol. 19, no. 2, pp. 671-678, Apr. 2004. [Baidu Scholar]
W. Xu, X. Liu, and Y. Liu, “An investigation on the validity of power-direction method for harmonic source determination,” IEEE Transactions on Power Delivery, vol. 18, no. 1, pp. 214-219, Jan. 2003. [Baidu Scholar]
B. Wang, G. Ma, J. Xiong et al., “Several sufficient conditions for harmonic source identification in power systems,” IEEE Transactions on Power Delivery, vol. 33, no. 6, pp. 3105-3113, Dec. 2018. [Baidu Scholar]
X. Xiao, R. Zhou, X. Ma et al., “A novel method for estimating utility harmonic impedance based probabilistic evaluation,” IET Generation, Transmission & Distribution, vol. 16, no. 7, pp. 1438-1448, Jan. 2022. [Baidu Scholar]
G. T. Heydt, “Identification of harmonic sources by a state estimation technique,” IEEE Transactions on Power Delivery, vol. 4, no. 1, pp. 569-576, Jan. 1989. [Baidu Scholar]
N. Kanao, M. Yamashita, H. Yanagida et al., “Power system harmonic analysis using state-estimation method for Japanese field data,” IEEE Transactions on Power Delivery, vol. 20, no. 2, pp. 970-977, Apr. 2005. [Baidu Scholar]
E. Sezgin, M. Göl, and Ö. Salor, “State-estimation-based determination of harmonic current contributions of iron and steel plants supplied from PCC,” IEEE Transactions on Industry Applications, vol. 52, no. 3, pp. 2654-2663, May-Jun. 2016. [Baidu Scholar]
Y. Wang, R. Xu, X. Ma et al., “Harmonic state estimation based on graph signal processing,” IET Generation, Transmission & Distribution, vol. 16, no. 6, pp. 1083-1095, Jan. 2022. [Baidu Scholar]
M. M. M. E. Arini, “A time domain load modelling technique and harmonics analysis,” in Proceedings of 8th International Conference on Harmonics and Quality of Power, Athens, Greece, Oct. 1998, pp. 930-938. [Baidu Scholar]
A. A. Moustafa, A. M. Moussa, and M. A. El-Gammal, “Separation of customer and supply harmonics in electrical power distribution systems,” in Proceedings of 9th International Conference on Harmonics and Quality of Power, Orlando, USA, Oct. 2000, pp. 1035-1040. [Baidu Scholar]
Y. Liu, H. Gong, X. Xiao et al., “Harmonic source location at the point of common coupling based on the nonlinearity index of load,” in Proceedings of 2009 Asia-Pacific Power and Energy Engineering Conference, Wuhan, China, Mar. 2009, pp. 1-5. [Baidu Scholar]
K. Tang, C. Shen, S. Liang et al., “Outlier issues in harmonic source location based on parameter identification method,” in Proceedings of 2016 IEEE PES General Meeting, Boston, USA, Jul. 2016, pp. 1-5. [Baidu Scholar]
Y. Zhang, C. Lin, Z. Shao et al., “A non-intrusive identification method of harmonic source loads for industrial users,” IEEE Transactions on Power Delivery, vol. 37, no. 5, pp. 4358-4369, Oct. 2022. [Baidu Scholar]
E. Thunberg and L. Soder, “A Norton approach to distribution network modeling for harmonic studies,” IEEE Transactions on Power Delivery, vol. 14, no. 1, pp. 272-277, Jan. 1999. [Baidu Scholar]
X. Xiao, Analysis and Control of Power Quality. Beijing: China Electric Power Press, 2010, pp. 161-162. [Baidu Scholar]
F. Lin, Y. Lin, D. Huang et al., “Ultra-high-power arc furnace model for low frequency non-stationary inter-harmonics,” in Proceedings of 2020 5th Asia Conference on Power and Electrical Engineering, Chengdu, China, Jun. 2020, pp. 2049-2053. [Baidu Scholar]