Abstract
This paper presents a properly designed branch current based state estimator (BCBSE) used as the main core of an accurate fault location approach (FLA) devoted to distribution networks. Contrary to the approaches available in the literature, it uses only a limited set of conventional measurements obtained from smart meters to accurately locate faults at buses or branches without requiring measurements provided by phasor measurement units (PMUs). This is possible due to the methods used to model the angular reference and the faulted bus, in addition to the proper choice of the weights in the state estimator (SE). The proposed approach is based on a searching procedure composed of up to three stages
① the identification of the faulted zones; ② the identification of the bus closest to the fault; and ③ the location of the fault itself, searching on branches connected to the bus closest to the fault. Furthermore, this paper presents a comprehensive assessment of the proposed approach, even considering the presence of distributed generation, and a sensitivity study on the proper weights required by the SE for fault location purposes, which can not be found in the literature. Results show that the proposed BCBSE-based FLA is robust, accurate, and aligned with the requirements of the traditional and active distribution networks.
DISTRIBUTION networks typically have a radial topology consisting mainly of overhead lines, which makes them highly vulnerable to faults or short-circuits. Since a fault is the leading cause of power supply interruptions, the development of fault location approaches (FLAs) is of great interest to utilities to reduce interruption times, avoid deterioration of power quality indices, and improve the reliability of the network. Under fault conditions, the protection acts to isolate the area affected by the fault. Therefore, it is necessary to identify and locate the fault to restore the power supply and maintain the power quality indices within the limits [
The advances in communication and metering infrastructures, required by active distribution networks (ADNs) [

Fig. 1 Overview of FLAs and OIAs.
The impedance based approaches can be implemented in traditional distribution networks and ADNs. The main issues are the multiple fault location paradigm and the typical low accuracy, especially when facing unbalanced loads and distributed generation (DG) [
These approaches are based on the fact that each fault causes voltage sags and current rises with different features. However, due to the errors inherent to the measurements, the delays in communication, the limited number of available measurements, the presence of distributed generators, the three-phase representation of the network, and the typical unbalanced loads, the state estimation approach can be used as a key tool to provide the estimates required for fault location purposes. Indeed, a sparse measurements based FLA supported by a properly designed state estimator (SE) that uses only conventional non-synchronized measurements is the main focus of this paper.
Given an adequate set of measurements and network data, SEs can provide the most likely state of a power system, even under fault conditions, enabling network managements [
Considering the branch currents as state variables, an approach to locating the nearest neighbor bus to the fault is proposed in [
In summary, to the best of the author’s knowledge, the literature presents approaches based only on synchronized measurements provided by PMUs, and the ones that use conventional non-synchronized as well as synchronized measurements provided by PMUs (used to improve accuracy). In this context, this paper proposes an approach that uses only a limited set of conventional non-synchronized measurements and a properly designed SE to improve the quality of the fault location without requiring measurements provided by PMUs.
The proposed approach adopts a branch current based SE (BCBSE) with proper methods to model the angular reference and the faulted bus, in addition to the adequate choice of the weights for the measurements and pseudo-measurements. Furthermore, under fault conditions, all the contributions of the shunt admittances of the branches are considered in modeling of equivalent current measurements. These modeling aspects are fundamental to achieving high accuracy in fault location without requiring measurements from PMUs. The proposed approach allows for accurately locating faults at buses or branches. The weighted sum of squared residuals is used as the fault location index (FLI), which can be applied even in the presence of a reduced set of measurements, i.e., a redundant set of measurements is not required. The BCBSE is adopted because it results in a constant Jacobian matrix, which improves the overall computational performance. Furthermore, the proposed approach is based on a searching procedure composed of up to three stages: ① the identification of the faulted zone; ② the identification of the bus closest to the fault; and ③ the location of the fault itself, searching on branches adjacent to the bus closest to the fault. This procedure, together with the constant Jacobian matrix, results in a reduced computational burden, even considering that the computational time is not a hard constraint for FLAs. Moreover, this paper presents a comprehensive assessment of the proposed approach considers the presence of DGs, and also a sensitivity study on the weights required by the SE for fault location purposes, which to the best of the author’s knowledge, can not be found in the literature.
The remainder of this paper is structured as follows. Section II describes the proposed BCBSE, highlighting a simple and accurate way to specify the angular reference and model the equivalent measurements. The proposed FLA, along with the modeling of the fault and the FLI, is detailed in Section III. In Section IV, the performance of the proposed FLA is assessed considering several case studies under fault conditions. Finally, the conclusions are drawn in Section V.
In a distribution network under normal conditions, the bus voltage magnitudes are close to the nominal values, and the voltage angles are typically small. Under these conditions, the classical state estimation methods are expected to perform very well [
Given that PMUs are not expected to be widely available in distribution networks, the main idea in this paper is to use only conventional non-synchronized measurements obtained from smart meters and pseudo-measurements. For that, the so-called branch current based state estimator (BCBSE) is adopted, and a set of cautions in modeling is used to prevent convergence issues when running under fault conditions. Thus, special attention is given to the specification of the angular reference, the modeling of the voltage magnitude measurements, and the modeling of the fault condition.
The state variables of the BCBSE are the real and imaginary parts of the voltages at the reference bus plus the real and imaginary parts of the branch currents, i.e., , where the subscript denotes the branch connecting buses and ; the subscripts re and im denote the real and imaginary parts, respectively; and the subscript ref denotes the reference bus [
(1) |
This linear relationship between the state vector and the equivalent measurement vector leads to a constant Jacobian matrix , which is composed of system impedances, zeros, and ones, and vector e contains the errors inherent to the measurements [
(2) |

Fig. 2 Basic algorithm for BCBSE.
The conventional measurements in the state estimation process are the active and reactive power injections and power flows and the voltage magnitudes. For the BCBSE, these conventional measurements are converted into equivalent currents and voltages [
Consider a three-phase branch with shunt admittances and loads connected at terminal buses and , as shown in
(3) |

Fig. 3 General model of a three-phase distribution branch.
where is the equivalent current injection of each phase j at terminal bus ; is the voltage phasor of each phase j at terminal bus k and iteration ; and are the active and reactive power injections of each phase j at terminal bus , respectively; and is a matrix containing the association of the shunt admittances of the branches and the shunt admittances connected to the buses . As a result, the vector contains the currents injected by the shunt elements at bus .
In a similar way, to obtain the equivalent current flow measurements, the active power and reactive power flowing through the branches are measured close to the terminal buses. These power flows are then converted into equivalent current flows as shown in (4).
(4) |
where is the equivalent current flow of each phase j on branch km; and and are the active and reactive power flows of each phase j on branch km, respectively.
As observed in (3) and (4), both the active and reactive power measurements are required to obtain the equivalent current measurements. If either of the two power measurements is missing, a pseudo-measurement with adequate variance can be used. Note that (3) and (4) include all available phases. To represent single- and two-phase branches as three-phase elements, the concept of dummy nodes and dummy lines can be adopted [
According to [
(5) |
where for each phase j; for each phase j; and is the rotation angle, which is constant and equal to the angles of the bus voltages at the first guess of the BCBSE. The angle is used to artificially create a complex voltage measurement from the measured voltage magnitudes. It can be observed that this angle is updated at every iteration of the solution process.
In BCBSE, as the state variables are the voltages of the reference bus and the branch currents, the equivalent voltage measurements need to be modeled as voltage drops from the reference bus ref to the measured bus . For that, and in (5) are rewritten as (6) and (7), respectively.
(6) |
(7) |
where and are the voltage magnitude and angle in a given phase j of the reference bus, respectively; is the set of branches connecting bus to reference bus; and are the real and imaginary parts of the currents of each phase j on branch , respectively; and is the series impedance matrix of the branch . Based on the above, the derivatives of the Jacobian matrix are obtained from (5), (6) and (7) and, therefore, the elements of the Jacobian matrix are constant. The values that go in are obtained from (5) and, hence, they are updated at every iteration .
In power system state estimation under normal conditions, more accurate measurements are recommended to be associated with higher weights, and less accurate measurements such as pseudo-measurements are associated with lower weights. The inverse of the variances of the measurements is typically used as weight [
In this paper, given that measurements are converted into equivalent measurements, considering the error propagation theory, the variances and covariances of the equivalent measurements are calculated from the variances of the measurements and used to compose the weighting matrix of the equivalent measurements [
According to [

Fig. 4 Angular reference placed at internal bus of Thevenin equivalent representing network upstream of substation.
Given that under asymmetrical fault conditions the unbalances in currents and voltages can be severe, the second way is recommended in this paper. As it will be shown, it contributes to maintaining the good convergence features of the BCBSE under asymmetrical fault conditions and allows a proper fitting to the available measurements.
In this paper, a fault at bus is modeled by including pseudo-measurements representing the fault currents as injections at bus . To consider the effect of the symmetrical or asymmetrical faults, these pseudo-measurements are included in all phases of bus . The pseudo-measurements are obtained according to (8).
(8) |
where is the fault current injection of each phase j at bus k; and are the active and reactive power injections of each phase j at the substation, respectively; and is the voltage phasor of each phase j at the substation and iteration .
Since the angular reference is placed at an internal bus of the Thevenin equivalent described in Section II-D, the voltages at the substation and the fault currents are updated at every iteration . In cases where the distribution network has DGs, the fault current is modeled as the summation of the contributions of all available power sources. An equation similar to (8) is applied to every DG.
Finally, given that these fault currents are indeed approximations of the actual fault currents, they are associated with small weights. This allows the residual associated with the fault currents to better fit the available measurements, improving the fault location accuracy. A discussion of the adequate weights is presented in Section IV.
The proposed approach is based on a search procedure composed of two stages: ① the identification of the faulted zone; and ② the identification of the faulted bus. The first stage consists of splitting the network into zones determined by boundary buses, which are the fork buses and terminal buses. This is done to reduce the computational burden of the searching procedure once just the boundary buses are tested at the first stage. An overview of the algorithm proposed to identify the faulted zones at the first stage is shown in

Fig. 5 Algorithm for identification of faulted zone at first stage.
According to
After identifying the faulted zones, the BCBSE-based FLA is run for the buses of the most likely faulted zones, as proposed in

Fig. 6 Algorithm for fault location in faulted zone at second stage.
At the second stage, bus (a bus inside the faulted zone) is selected as suspect bus and the fault currents are specified at this bus according to (8). Similar to the algorithm of
Given that faults are more prone to occur on branches instead of buses, to improve the accuracy of the fault location, fictitious buses equally spaced can be placed on branches adjacent to the bus with the smallest , and the proposed approach can be run for these fictitious buses. However, it is worth mentioning that the spacing does not necessarily have to be fixed and can be of any size, that is, a finer or larger spacing. This will depend on the length of the branch. Given this, it is important to highlight that the smaller the distance between these fictitious buses, the greater the accuracy of the fault location. On the other hand, increasing the number of fictitious buses increases the computational burden. In practice, a distance from 50 to 100 m is recommended between fictitious buses. This is a typical distance among consecutive poles.
In cases where there are unobservable areas in the distribution networks, classical algorithms for observability analysis, as proposed in [
In this paper, the index , known as the weighted sum of squared residuals [
(9) |
(10) |
The proposed approach was implemented in MATLAB 2017b and the tests were run considering a modified version of the IEEE 34-bus distribution feeder [

Fig. 7 Modified IEEE 34-bus distribution feeder.
To simulate the measured values , the fault, as well as the healthy network, was simulated on the software OpenDSS [
To simulate the availability of actual measurement values , deviations following normal distribution were added to the measured values according to (11), where is a normally distributed random variable with zero mean and unitary variance, i.e., [
(11) |
(12) |
The initial measurement plan (Plan A) is depicted in
All these measurements are provided by smart meters, for which the on power and voltage measurements is 2% and 1%, respectively. The considered for pseudo-measurements is 50% over the true power injections obtained from the OpenDSS. The current injection representing the fault is associated with a small weight [
A second measurement plan (Plan B) containing twice the number of meters is also considered. The new measurements of power and voltage magnitude are placed at Buses 3, 16, 18, 20, 25, 28, 30, 32, and 48. The convergence criterion of the BCBSE is reached if the maximum absolute value of mismatches on the state variables is less than a specified tolerance, i.e., , where the tolerance is .
In this subsection, the impact of the angular reference on the convergence of the BCBSE under fault conditions is assessed. Single- and three-phase faults are simulated since they represent the most frequent and severe faults, respectively. Three specifications of angular reference are considered.
1) Substation bus: the voltage magnitudes are measured by a smart meter and the angles are assumed to be displaced at the substation.
2) Internal bus: the complex voltages present the same magnitude and the angles are displaced at internal bus (bus behind the substation), as presented in Section II-D.
3) Substation bus (PMU): the voltage magnitudes and angles are provided by PMU at the substation bus.
For this purpose, the complex voltages estimated by the BCBSE () considering the three specifications of angular reference are assessed through the mean absolute error (MAE) according to (13), where is the measured complex voltage, and is the number of buses in the network. The smaller the MAE, the better the estimates fit the available measurements.
(13) |
Figures

Fig. 8 MAE considering single-phase faults at Bus 22 with two measurement plans and fault resistance varying from 1 to 100 . (a) Plan A. (b) Plan B.

Fig. 9 MAE considering three-phase faults at Bus 22 with two measurement plans and fault resistance varying from 1 to 100 . (a) Plan A. (b) Plan B.
Considering the same simulation depicted in the previous paragraph, Figs.

Fig. 10 Number of iterations considering single-phase faults at Bus 22 with two measurement plans and fault resistance varying from 1 to 100 . (a) Plan A. (b) Plan B.

Fig. 11 Number of iterations considering three-phase faults at Bus 22 with two measurement plans and fault resistance varying from 1 to 100 . (a) Plan A. (b) Plan B.
In summary, the proposed approach to represent the angular reference in the BCBSE under fault conditions can provide similar results to the adoption of a PMU at the substation with a significantly smaller cost. This approach shows the relevance with the accuracy of the BCBSE, specially in the presence of asymmetrical faults.
In this subsection, the performance of the proposed approach is assessed in terms of success percentage in correctly identifying the fault location, i.e., accuracy. Each fault scenario is run 1000 times considering randomly defined noisy measurements. Single- and three-phase faults were simulated across the IEEE 34-bus distribution feeder considering fault resistance varying from 1 to 100 . Tests were carried out considering fault resistance up to 1000 , and the general conclusions are similar. These results are not presented for a matter of space.
As can be observed in

Fig. 12 Accuracy of proposed approach considering single-phase faults with Plan A and Plan B. (a) Plan A. (b) Plan B.
Similar behavior is presented by the proposed approach when three-phase faults are assessed. According to

Fig. 13 Accuracy of proposed approach considering three-phase faults with Plan A and Plan B. (a) Plan A. (b) Plan B.
The previous analysis have considered faults at buses. However, it is well known that the faults are much more prone to occur on branches. To locate faults on branches, the proposed approach is run at the boundary buses in order to identify the faulted zones.
Then, it is run at buses belonging to these zones to identify the bus closest to the fault. Once the bus closest to the fault is located, the proposed approach is run on branches adjacent to this bus. These branches are examined by introducing a fictitious bus that sweeps them from the beginning to the end. Based on this procedure, single- and three-phase faults were assessed with fault resistance varying from 1 to 100 on Branch 21-22, as shown in

Fig. 14 Accuracy of proposed approach considering single- and three-phase faults on Branch 21-22. (a) Single-phase fault. (b) Three-phase fault.
The measurement plan is Plan A. The performance assessment is performed in terms of the maximum error class considering 1000 sets of randomly defined noisy measurements that are produced for each fault scenario. For simplicity, the fictitious buses were spaced every 100 m far from each other. However, any distance between the fictitious buses can be adopted. When the fault resistance is less than , the accuracy of the proposed approach is between 0 and 100 m considering the single-phase fault, which means that the fault is between two consecutive fictitious buses. As the fault resistance increases, the accuracy of the proposed approach decreases. This can be observed, for instance, in the cases of single-phase faults with the resistance greater than . For the adopted spacing between the fictitious buses, the worst error was smaller than 300 m. Recall that these results can be improved by installing more meters. A similar behavior occurs with the three-phase faults, as shown in
A case study in a distribution network containing underground cables is presented in the following.
This case study is based on the 37-bus test feeder. This feeder is an actual feeder in California, USA, with a 4.8 kV operating voltage. It is featured by delta configuration, all branch segments are underground, the substation voltage regulation is based on two single-phase open-delta regulators, spot loads, and very unbalanced [
In this case, a fictitious bus containing the fault sweeps the branch from the beginning to the end. Based on this, single- and three-phase faults were assessed with the fault resistance varying from 1 to on Underground Branch 702-703, as shown in

Fig. 15 Accuracy of proposed approach considering single- and three-phase faults on Underground Branch 702-703. (a) Single-phase fault. (b) Three-phase fault.
When the fault resistance is less than , the accuracy of the proposed approach is between 0 and 20 m considering the single-phase fault. As the fault resistance increases, the accuracy of the proposed approach decreases. This can be observed, for instance, in the cases of single-phase faults with the resistance greater than . In the worst cases, the errors are smaller than 60 m. Keep in mind that these results can be improved by installing more meters. A similar behavior occurs with the three-phase faults, as can be observed in
In this subsection, the proposed approach is assessed in the presence of DGs. For that, three distributed generators were added at Buses 14, 40, and 46 (two synchronous generators at Buses 14 and 40 and one PV at Bus 46 [
As can be observed in

Fig. 16 Accuracy of proposed approach considering single- and three-phase faults with presence of DG. (a) Single-phase fault. (b) Three-phase fault.
In the previous subsections, the weights of the measurements and pseudo-measurements were set according to (11) and (12). The weights of the zero injections and the fault current were set to be and , respectively. These values were chosen from the experience of the authors with state estimation and FLAs. In this subsection, a sensitivity study on these weights is presented.
In the first case, a single-phase fault was applied across the test system considering different weights to the pseudo-measurements and the fault current. The Plan A was considered. For each fault scenario, a total of 1000 sets of noisy measurements were produced and assessed.

Fig. 17 Accuracy of proposed approach considering weight influence of pseudo-measurement and zero injection versus fault current. (a) Weight influence of pseudo-measurement versus fault current. (b) Weight influence of zero injection versus fault current.
In
In
Based on the results shown in this subsection, the range for the specification of the weights is wide. This simplifies the choice of suitable weights for the proposed approach. Besides, this indicates that from a reduced set of simulations, these weights can be properly set.
Due to the errors inherent to the measurements, the delays in communication, the limited number of available measurements (leading to the adoption of pseudo-measurements), the presence of distributed generators, the required three-phase representation of the distribution feeders, and the typical unbalanced loads, the state estimation approaches are promising as the main core for FLAs. In this paper, the proposed FLA is based on an improved BCBSE, in which the Jacobian matrix remains constant throughout the solution process, reducing the computational burden of the FLA. However, the computational time is not a hard constraint for FLAs. Moreover, the proposed approach allows the accurate locating of faults at buses or branches without requiring measurements from PMUs. The use of the PMUs is the most common requirement of the more recent approaches for fault location based on SEs.
In summary, the proposed FLA can use measurements from PMUs, however, this is not a requirement. Indeed, the proposed approach can be applied given a reduced set of conventional non-synchronized measurements. However, similar to approaches based on measurements, increasing the number of available measurements increases the robustness and accuracy of the proposed approach.
As shown in the results, the improved BCBSE can be successfully applied to faulted three-phase distribution networks mainly due to: ① the way the angular reference is modeled; ② the way the faulted bus is represented; ③ the proper weights assigned for the measurements and pseudo-measurements; and ④ the representation of all shunt admittances at buses and branches in modeling of equivalent current measurements. These modeling aspects can be adopted regardless of the networks. Therefore, these are not conditions required to the proposed approach to gain a good performance, but they are modeling aspects that are usually disregarded when the SE is being applied in healthy networks. These modeling aspects are recommended in this paper to be adopted in faulted networks achieving high accuracy in fault location without requiring measurements from PMUs.
In order to assess the performance of the proposed approach, several properly designed fault scenarios, using Monte Carlo simulations, were run on the IEEE 34-bus distribution feeder and the 37-bus distribution feeder (with overhead and underground branches, respectively). Results indicate that the proposed approach is an accurate and efficient alternative to the available approaches without the need of adopting phasor measurements.
Similar to all FLAs based on measurements and network analysis tools (short-circuit, load flow, and state estimation), in the proposed approach, the accuracy of the fault location depends on the number and location of the available measurements. In addition, these FLAs based on network analysis tools usually can present difficulties to converge in networks that have very high grounding impedances as well as in ungrounded systems.
References
F. Shen, Q. Wu, and Y. Xue, “Review of service restoration for distribution networks,” Journal of Modern Power Systems and Clean Energy, vol. 8, no. 1, pp. 1-14, Jan. 2019. [Baidu Scholar]
C. D’Adamo, S. Jupe, and C. Abbey, “Global survey on planning and operation of active distribution networks – update of CIGRE C6.11 working group activities,” in Proceedings of CIRED 2009 – 20th International Conference and Exhibition on Electricity Distribution – Part 1, Prague, Czech Republic, Jun. 2009, pp. 1-4. [Baidu Scholar]
R. H. Salim, M. Resener, A. D. Filomena et al., “Extended fault-location formulation for power distribution systems,” IEEE Transactions on Power Delivery, vol. 24, no. 2, pp. 508-516, Apr. 2009. [Baidu Scholar]
S. Das, N. Karnik, and S. Santoso, “Distribution fault-locating algorithms using current only,” IEEE Transactions on Power Delivery, vol. 27, no. 3, pp. 1144-1153, Apr. 2012. [Baidu Scholar]
H. Mirshekali, R. Dashti, A. Keshavarz et al., “A novel fault location methodology for smart distribution networks,” IEEE Transactions on Smart Grid, vol. 12, no. 2, pp. 1277-1288, Mar. 2021. [Baidu Scholar]
F. Aboshady, D. Thomas, and M. Sumner, “A new single end wideband impedance based fault location scheme for distribution systems,” Electric Power Systems Research, vol. 173, pp. 263-270, Aug. 2019. [Baidu Scholar]
K. Jia, T. Bi, Z. Ren et al., “High frequency impedance based fault location in distribution system with DGs,” IEEE Transactions on Smart Grid, vol. 9, no. 2, pp. 807-816, Mar. 2018. [Baidu Scholar]
A. Borghetti, M. Bosetti, C. Nucci et al., “Integrated use of time-frequency wavelet decompositions for fault location in distribution networks: theory and experimental validation,” IEEE Transactions on Power Delivery, vol. 25, no. 4, pp. 3139-3146, Apr. 2010. [Baidu Scholar]
S. Robson, A. Haddad, and H. Griffiths, “Fault location on branched networks using a multiended approach,” IEEE Transactions on Power Delivery, vol. 29, no. 4, pp. 1955-1963, Jun. 2014. [Baidu Scholar]
L. Xie, L. Luo, Y. Li et al., “A traveling wave-based fault location method employing VMD-TEO for distribution network,” IEEE Transactions on Power Delivery, vol. 35, no. 4, pp. 1987-1998, Aug. 2020. [Baidu Scholar]
E. C. Maritz, J. M. Maritz, and M. Salehi, “A travelling wave-based fault location strategy using the concepts of metric dimension and vertex covers in a graph,” IEEE Access, vol. 9, pp. 155815-155825, Nov. 2021. [Baidu Scholar]
A. Tashakkori, P. J. Wolfs, S. Islam et al., “Fault location on radial distribution networks via distributed synchronized traveling wave detectors,” IEEE Transactions on Power Delivery, vol. 35, no. 3, pp. 1553-1562, Jun. 2020. [Baidu Scholar]
D. Thukaram, H. Khincha, and H. Vijaynarasimha, “Artificial neural network and support vector machine approach for locating faults in radial distribution systems,” IEEE Transactions on Power Delivery, vol. 20, no. 2, pp. 710-721, Apr. 2005. [Baidu Scholar]
M. Pourahmadi-Nakhli and A. A. Safavi, “Path characteristic frequency-based fault locating in radial distribution systems using wavelets and neural networks,” IEEE Transactions on Power Delivery, vol. 26, no. 2, pp. 772-781, Apr. 2011. [Baidu Scholar]
W.-H. Kim, J.-Y. Kim, W.-K. Chae et al., “LSTM-based fault direction estimation and protection coordination for networked distribution system,” IEEE Access, vol. 10, pp. 40348-40357, Apr. 2022. [Baidu Scholar]
Y. Jiang, “Data-driven fault location of electric power distribution systems with distributed generation,” IEEE Transactions on Smart Grid, vol. 11, no. 1, pp. 129-137, Jan. 2020. [Baidu Scholar]
Y. Jiang, “Data-driven probabilistic fault location of electric power distribution systems incorporating data uncertainties,” IEEE Transactions on Smart Grid, vol. 12, no. 5, pp. 4522-4534, Apr. 2021. [Baidu Scholar]
R. A. F. Pereira, L. G. W. da Silva, M. Kezunovic et al., “Improved fault location on distribution feeders based on matching during-fault voltage sags,” IEEE Transactions on Power Delivery, vol. 24, no. 2, pp. 852-862, Mar. 2009. [Baidu Scholar]
F. C. Trindade, W. Freitas, and J. C. Vieira, “Fault location in distribution systems based on smart feeder meters,” IEEE Transactions on Power Delivery, vol. 29, no. 1, pp. 251-260, Feb. 2014. [Baidu Scholar]
K. Jia, B. Yang, T. Bi et al., “An improved sparse-measurement-based fault location technology for distribution networks,” IEEE Transactions on Industrial Informatics, vol. 17, no. 3, pp. 1712-1720, May 2020. [Baidu Scholar]
M. Majidi and M. Etezadi-Amoli, “A new fault location technique in smart distribution networks using synchronized/nonsynchronized measurements,” IEEE Transactions on Power Delivery, vol. 33, no. 3, pp. 1358-1368, Dec. 2017. [Baidu Scholar]
K. Jia, B. Yang, X. Dong et al., “Sparse voltage measurement-based fault location using intelligent electronic devices,” IEEE Transactions on Smart Grid, vol. 11, no. 1, pp. 48-60, Jan. 2020. [Baidu Scholar]
A. Monticelli, State Estimation in Electric Power Systems: a Generalized Approach. Berlin: Springer Science & Business Media, 2012. [Baidu Scholar]
A. Abur and A. G. Exposito, Power System State Estimation: Theory and Implementation. Bath: CRC press, 2004. [Baidu Scholar]
M. Pignati, L. Zanni, P. Romano et al., “Fault detection and faulted line identification in active distribution networks using synchrophasors-based real-time state estimation,” IEEE Transactions on Power Delivery, vol. 32, no. 1, pp. 381-392, Feb. 2017. [Baidu Scholar]
M. U. Usman and M. O. Faruque, “Validation of a PMU-based fault location identification method for smart distribution network with photovoltaics using real-time data,” IET Generation, Transmission & Distribution, vol. 12, no. 21, pp. 5824-5833, Oct. 2018. [Baidu Scholar]
M. Gholami, A. Abbaspour, M. Moeini-Aghtaie et al., “Detecting the location of short-circuit faults in active distribution network using PMU-based state estimation,” IEEE Transactions on Smart Grid, vol. 11, no. 2, pp. 1396-1406, Mar. 2020. [Baidu Scholar]
Y. Zhang, J. Wang, and M. E. Khodayar, “Graph-based faulted line identification using micro-PMU data in distribution systems,” IEEE Transactions on Smart Grid, vol. 11, no. 5, pp. 3982-3992, Sept. 2020. [Baidu Scholar]
F. Conte, F. D’Agostino, B. Gabriele et al., “Fault detection and localization in active distribution networks using optimally placed phasor measurements units,” IEEE Transactions on Power Systems, vol. 38, no. 1, pp. 714-727, Jan. 2023. [Baidu Scholar]
S. Jamali and A. Bahmanyar, “A new fault location method for distribution networks using sparse measurements,” International Journal of Electrical Power & Energy Systems, vol. 81, pp. 459-468, Oct. 2016. [Baidu Scholar]
J. Cordova and M. O. Faruque, “Fault location identification in smart distribution networks with distributed generation,” in Proceedings of 2015 North American Power Symposium (NAPS), Charlotte, USA, Oct. 2015, pp. 1-7. [Baidu Scholar]
S. Jamali, A. Bahmanyar, and E. Bompard, “Fault location method for distribution networks using smart meters,” Measurement, vol. 102, pp. 150-157, May 2017. [Baidu Scholar]
M. E. Baran and A. W. Kelley, “A branch-current-based state estimation method for distribution systems,” IEEE Transactions on Power Systems, vol. 10, no. 1, pp. 483-491, Feb. 1995. [Baidu Scholar]
M. C. de Almeida and L. F. Ochoa, “An improved three-phase AMB distribution system state estimator,” IEEE Transactions on Power Systems, vol. 32, no. 2, pp. 1463-1473, Mar. 2017. [Baidu Scholar]
L. F. Ugarte, J. Tuo, and M. C. de Almeida, “Assessing approaches to modeling voltage magnitude measurements in state estimators devoted to active distribution networks,” Electric Power Systems Research, vol. 200, p. 107440, Nov. 2021. [Baidu Scholar]
M. Abdel-Akher and K. M. Nor, “Fault analysis of multiphase distribution systems using symmetrical components,” IEEE Transactions on Power Delivery, vol. 25, no. 4, pp. 2931-2939, Oct. 2010. [Baidu Scholar]
D. A. Haughton and G. T. Heydt, “A linear state estimation formulation for smart distribution systems,” IEEE Transactions on Power Systems, vol. 28, no. 2, pp. 1187-1195, May 2013. [Baidu Scholar]
R. S. da Silva, T. R. Fernandes, and M. C. de Almeida, “Specifying angular reference for three-phase distribution system state estimators,” IET Generation, Transmission & Distribution, vol. 12, no. 7, pp. 1655-1663, Feb. 2018. [Baidu Scholar]
W. H. Kersting, “Radial distribution test feeders,” IEEE Transactions on Power Systems, vol. 6, no. 3, pp. 975-985, Aug. 1991. [Baidu Scholar]
R. C. Dugan and T. E. McDermott, “An open source platform for collaborating on smart grid research,” in Proceedings of 2011 IEEE PES General Meeting, , Detroit, USA, Jul. 2011, pp. 1-7. [Baidu Scholar]
P. A. Cavalcante and M. C. de Almeida, “Fault location approach for distribution systems based on modern monitoring infrastructure,” IET Generation, Transmission & Distribution, vol. 12, no. 1, pp. 94-103, Oct. 2017. [Baidu Scholar]
A. Abur, “A bad data identification method for linear programming state estimation,” IEEE Transactions on Power Systems, vol. 5, no. 3, pp. 894-901, Aug. 1990. [Baidu Scholar]
US Department of Energy, “Contribution to power system state estimation and transient stability analysis,” Tech. Rep. DOE/ET/29362-1, Feb. 1984. [Baidu Scholar]