Abstract
This paper performs a study on three-way subsynchronous torsional interactions (SSTI) between a hybrid dual-infeed high-voltage direct current (HVDC) system and a nuclear generator. The test case is based on the French IFA2000 line commutated converter (LCC) HVDC (2 GW) and the new Eleclink modular multilevel converter (MMC) HVDC (1 GW) interacting with the Gravelines generator (1 GW). The analysis is performed by the means of the eigenvalue stability assessment on an analytical model, while the accuracy of the conclusions is verified using the detailed non-linear electromegnetic transient program (EMTP) model. The study shows that the dual-infeed system may introduce higher risk of the SSTI compared with the point-to-point HVDC systems. It shows that MMC operating as static synchronous compensator (STATCOM) may further reduce the torsional damping at 6.3 Hz mode. This conclusion may be unexpected since it is known fact from literature that STATCOM has a beneficial impact on the transient performance of LCC. Further studies show that in a sequential HVDC loading, it may be beneficial to load the MMC HVDC first. Also, the risk of the SSTI may be minimized by changing HVDC controller gains, in particular, by increasing phase-locked-loop (PLL) gains on the LCC rectifier.
THE phenomenon of subsynchronous resonance (SSR) has been manifested in practice on multiple occasions since the 1970s [
The SSR is often associated with series compensated transmission systems; however, it can also be caused by the control of high-voltage direct current (HVDC) transmission, and this is commonly known as the subsynchronous torsional interactions (SSTI) [
However, there is limited practical experience or published work with the voltage source converter (VSC)-based systems, although this topic is gaining much interest since the emerging VSC topology is superseding the LCC in HVDC applications. Most SSTI studies consider the early two-level VSC and suggest a minor risk [
With the benefits of MMC, and considering many existing LCC HVDC, we expect to see a mix of MMC and LCC (hybrid dual-infeed HVDC system) interconnecting the same AC grids. This topic is of further interest since studies have indicated that MMC, in either HVDC transmission link or static synchronous compensator (STATCOM) application, may have a beneficial impact on the stability and performance of the LCC [
The aim of this study is to perform three-way SSTI investigation by considering all operating modes. The eigenvalue stability study will be based on a small-signal analytical model, which is the best approach for generic, in-depth stability and control design study [
The study is motivated by a practical dual-infeed hybrid HVDC system in the North of France, operated by Réseau de Transport d’Électricité (RTE), the French transmission system operator (TSO). This system has a history of SSTI stability issues [
The schematic of the test system representing North French topology is presented in

Fig. 1 Schematic of test system representing North French topology.
In 1988, the Électricité de France (EDF) study reported that the IFA2000 link may destabilize the dominant torsional mode (6.3 Hz) of Gravelines generator, for weak French AC grid [
The generator and the LCC HVDC models are represented using the standard electromagnetic transient (EMT) models which are based on the well-documented approaches [
The MMC HVDC is represented using the type 4 average value model according to the CIGRE working group B4.57 [
The parameters of the LCC HVDC are taken from the available IFA2000 data [
The electrical parameters of Gravelines generator are available in [
Turbine/generator | Inertia (MWs/MVA) | Spring constant (p.u./rad) | Mechanical damping |
---|---|---|---|
High-pressure (HP) turbine | 0.168 | 9.48 | 0.2 |
Low-pressure (LP) turbine A | 1.390 | 10.94 | 0.4 |
LP turbine B | 1.500 | 19.09 | 2.0 |
Generator | 0.981 | 0.4 |
The LCC HVDC has the standard control structure [
The MMC HVDC has the standard control structure [

Fig. 2 Schematic of MMC control structure. (a) PLL. (b) Main control.
The generator has generic nuclear generator controllers: the AC4A exciter, the PSS2A power system stabilizer [
The generator controller gains are adopted by considering IEEE standards [
While the generator controller gains are fixed, this study will consider the impact of a wide range of possible HVDC controller gains. The adopted ranges of LCC and MCC HVDC controller gains are provided in
Controller | Controller gain | Basic value | Range | Feedback filter |
---|---|---|---|---|
DC current controller | KP (°/p.u.) | 45 | ±50% |
Time constant s |
KI (°/(s/p.u.)) | 4000 | ±50% | ||
DC voltage controller | KP (°/p.u.) | 35 | ±50% | s |
KI (°/(s/p.u.)) | 2250 | ±50% | ||
Gamma controller | KP (°/°) | 1 | ||
KI (°/(°s)) | 20 | |||
PLL | KP (rad/(s/p.u.)) | 10 | -60 | |
KI (rad/( | 50 |
Controller | Controller gain | Basic value | Range | Feedback filter |
---|---|---|---|---|
Active power controller (P) | KP (p.u./p.u.) | 0 | Cut-off frequency Hz | |
KI ( | 30 | 15-45 | ||
Reactive power controller (Q) | KP (p.u./p.u.) | 0 | Hz | |
KI ( | 30 | 15-45 | ||
AC voltage droop controller | K (p.u./p.u.) | -6 | -9--3 | Hz |
Vac,ref (p.u.) | 1 | |||
DC voltage controller (Vdc) | KP (p.u./p.u.) | 9.6 | Hz | |
KI ( | 294 | |||
DQ current controller (Idq) | KP (p.u./p.u.) | 1 |
Hz Hz | |
KI ( | 100 | 50-150 | ||
PLL | KP (rad/(s/p.u.)) | 80 | 40-120 | |
KI (rad/( | 1600 | |||
CCSC | KP (p.u./p.u.) | 0.8 | Hz | |
KI ( | 20 |
This study assumes that the operating strategy of dual-infeed HVDC system considers the most relevant, as shown in
Type of operation | Operating strategy | Power flow of two HVDC | Total HVDC loading |
---|---|---|---|
Sequential HVDC loading |
Operating strategy 1 |
The same direction | 0-2 GW: LCC HVDC + STATCOM |
2-3 GW: LCC at 2 GW + MMC HVDC | |||
Operating strategy 2 |
The same direction | 0-1 GW: MMC HVDC | |
1-3 GW: MMC at 1 GW + LCC HVDC |
It is possible to increase loading of two HVDC simultaneously and arbitrarily (and perhaps in the opposite direction); however, these operating strategies are not studied.
This study will analyze broad range of operating points depending on HVDC active/reactive power and generator active power/AC voltage. The French SCC will be reduced from strong to weak grid, with the lowest realistic SCC of 3 GVA according to the TSO [
The individual small-signal models of the two HVDC links and the generator are coded in MATLAB, and their accuracy has been individually verified against the EMTP models for wide range of operating conditions and for all variables, but they are not presented in detail for brevity.
The linearized state-space LCC HVDC analytical model employs the modeling approaches from [
The MMC linearized dynamic model is of the 1
The linearized generator model in state-space includes rotor/stator circuit, with the armature, field and damper windings, and multi-mass shaft model. The complete linearized model is of the 4
The complete test system is assembled in state-space by connecting the subsystems to enable flexibility in studies. The diagram in

Fig. 3 Block diagram of complete state-space model.
The impact of the French MMC operation as a STATCOM with AC voltage droop control, as defined in
The torsional damping of 6.3 Hz and 12 Hz modes for change of LCC HVDC loading and the French SCC showing also the impact of MMC STATCOM are shown in

Fig. 4 Torsional damping of 6.3 Hz and 12 Hz modes for change of LCC HVDC loading and French SCC showing also impact of MMC STATCOM. (a) 6.3 Hz mode, French of 10 GVA. (b) 6.3 Hz mode, French of 5 GVA. (c) 6.3 Hz mode, French of 4 GVA. (d) 6.3 Hz mode, French of 3 GVA. (e) 12 Hz mode, French of 10 GVA. (f) 12 Hz mode, French of 5 GVA. (g) 12 Hz mode, French of 4 GVA. (h) 12 Hz mode, French of 3 GVA.
In
Black plots represent the case when only LCC HVDC is connected, which show that LCC always reduces damping across the entire loading range for the 6.3 Hz mode, while the impact on the 12 Hz mode depends on the loading and SCC. Furthermore, the LCC HVDC deteriorates damping more as the French SCC is reducing. For a particularly weak AC grid (SCC below 3.5 GVA roughly), the HVDC may destabilize the 6.3 Hz mode, which is consistent with reports in [
The impact of the French MMC operating as STATCOM (zero active power) is shown by red plots. Compared with just LCC HVDC, STATCOM will generally further reduce the damping slightly, although the adverse impact is mostly of significance for lower LCC power. Similar results are obtained for other AC voltages levels in ±5% range, and also for lower generator power, although the torsional damping is higher according to the generator power characteristics [
Eigenvalue sensitivity of the torsional modes shows that the most influential MMC controller gains are the integral gain of reactive power controller and the droop gain of AC voltage controller. The impact of STATCOM controller gains on the 6.3 Hz mode is shown in

Fig. 5 Impact of STATCOM controller gains on 6.3 Hz mode. (a) , -6, -9. (b) , 30, 45.

Fig. 6 Torsional damping for two operating strategies considering change of French SCC and HVDC loading. (a) 6.3 Hz mode, French of 10 GVA. (b) 6.3 Hz mode, French of 5 GVA. (c) 6.3 Hz mode, French of 4 GVA. (d) 6.3 Hz mode, French of 3 GVA. (e) 12 Hz mode, French of 10 GVA. (f) 12 Hz mode, French of 5 GVA. (g) 12 Hz mode, French of 4 GVA. (h) 12 Hz mode, French of 3 GVA.
This is expected when comparing previous results for individual HVDC, LCC [
However, it is not expected that the damping is improved as the HVDC loading increases, especially in the 2-3 GW range. Further analysis concludes that this is primarily caused by the value of the LCC firing angle.

Fig. 7 Torsional damping for change of firing angle. (a) 6.3 Hz mode. (b) 12 Hz mode.

Fig. 8 RMS voltage of PCC and firing angle for change of total HVDC loading. (a) RMS voltage. (b) Firing angle.
Eigenvalue sensitivity analysis of the torsional modes is performed on the whole system, and the most influential HVDC controller gains are found to be: DC current controller and PLL gains at the rectifier LCC. This is explored in

Fig. 9 Torsional damping showing impact of rectifier LCC controller gains. (a) 6.3 Hz mode with different PLL gains. (b) 12 Hz mode with different PLL gains. (c) 6.3 Hz mode with different IDC controller gains. (d) 12 Hz mode with different IDC controller gains.

Fig. 10 Torsional damping considering two dual-infeed operating strategies. (a) 6.3 Hz mode with LCC HVDC or STATCOM. (b) 12 Hz mode with LCC HVDC or STATCOM. (c) 6.3 Hz with operating strategy 1 or 2. (d) 12 Hz mode with operating strategy 1 or 2.
This is the weakest grid for which the two HVDC links and the generator can deliver full power, according to the power flow analysis. However, similar results are obtained for reduced loading which allows weaker AC grid. The figure shows the damping for the change of the loading of the two HVDC links.
Additional eigenvalue sensitivity study shows that the dual-infeed system can reduce the torsional damping but of only the 6.3 Hz mode and only when the PLL gains are increased on the inverter LCC. It is shown in

Fig. 11 Damping of the 6.3 Hz mode for high PLL gains at inverter LCC.
All the results of the eigenvalue study are verified by detailed EMTP simulations. The disturbance (a 2.5% voltage sag) is simulated by connecting a light load (533 MW, 300 Ω resistance) for 0.2 s at the French PCC of the LCC HVDC.
Literature suggests that STATCOM improves transient performance of LCC HVDC [

Fig. 12 DC current response on LCC HVDC showing beneficial impact of STATCOM for transient stability. (a) DC current. (b) AC voltage.
The impact of the STATCOM is now investigated when the generator is operated at rated power and with weak French of 3.5 GVA.

Fig. 13 Generator-rotor speed responses for a voltage sag in 1.5-1.7 s. (a) Rated LCC power. (b) 0.5 p.u. LCC power. (c) 0.1 p.u. LCC power.
With STATCOM, the oscillations are similar for the rated LCC power, which means that STATCOM has negligible impact. However, as the LCC power decreases, the impact of STATCOM is to increase the growth rate of the oscillations, which confirms the analytical results obtained in
The eigenvalue study in

Fig. 14 Generator-rotor speed showing impact of increasing MMC power. (a) MCC HVDC with STATCOM. (b) MCC HVDC with 0.3 GW loading. (c) MCC HVDC with 0.7 GW loading.
Another important conclusion from analytical study in

Fig. 15 Generator-rotor speed for a voltage sag.
Three-way LCC-MMC-generator stability analysis has shown that a hybrid dual-infeed HVDC system may introduce a higher risk of the SSTI compared with the individual point-to-point HVDC systems. It is shown that adding an MMC STATCOM may reduce the torsional damping of an existing LCC HVDC and nuclear generator system. In a sequential operation of the dual-infeed system, the risk of the SSTI may be lower if the MMC HVDC is loaded first. The risk of the SSTI could be mitigated slightly by reducing the STATCOM reactive power or AC voltage droop gains at the expense of voltage control performance. The risk of destabilizing torsional modes may be mitigated by increasing PLL gains on the rectifier LCC. However, increasing PLL gain on the inverter LCC may have an opposite effect on the SSTI.
Appendix
Tables AI-AIII show the LCC HVDC, MMC HVDC, and generator parameters, respectively. Figure A1 shows the parameters of the AC filters on the LCC HVDC.
Type | Parameter | Value |
---|---|---|
Converter parameters | HVDC power (GW) | 2 |
DC voltage rating (kV) | ±270 | |
Smoothing reactance (mH) | 350 | |
Transformer (MVA) | 618 | |
Transformer reactance (p.u.) | 0.15 | |
Transformer ratio (kV) | 400/115 | |
DC cable distributed parameters | Resistance (Ω/km) | 0.015 |
Length (km) | 70 | |
Inductance (mH/km) | 0.792 | |
Capacitance (nF/km) | 14.4 |
Type | Parameter | Value |
---|---|---|
Converter parameters | Power rating (MW) | 1000 |
DC voltage (kV) | ±320 | |
Transformer primary voltage (kV) | 400 | |
Transformer secondary voltage (kV) | 360 | |
Transformer reactance (p.u.) | 0.18 | |
Arm inductance (p.u.) | 0.12 | |
Capacitor energy in submodule (kJ/MVA) | 40 | |
Number of submodules per arm | 400 | |
Underground DC cable parameters | Number of poles per cable | 2 |
Vertical distance from ground level (m) | 1.33 | |
Horizontal distance between poles (m) | 0.5 | |
Conductor outside radius (mm) | 32 | |
Sheath inside radius (mm) | 56.9 | |
Sheath outside radius (mm) | 58.2 | |
Outer insulation radius (mm) | 63.9 | |
Conductor resistivity per length unit (Ω/m) |
1.72×1 | |
Sheath resistivity per length unit (Ω/m) |
2.83×1 | |
Relative permeability | 1 | |
Insulator relative permittivity | 2.5 | |
Insulator loss factor | 0.0004 |
Type | Parameter | Value |
---|---|---|
Basic generator parameters | Power rating (MVA) | 1120 |
Stator frequency (Hz) | 50 | |
Stator terminal RMS line-to-line voltage (kV) | 24 | |
Number of poles | 4 | |
Armature winding connection (grounded) | Y | |
Parameters of equivalent electrical circuit | Armature resistance Ra (p.u.) | 0.004 |
Zero-sequence inductance L0 (p.u.) | 0.187 | |
Armature leakage inductance Ll (p.u.) | 0.27 | |
Armature d-axis inductance Ld (p.u.) | 2.57 | |
Armature q-axis inductance Lq (p.u.) | 2.57 | |
d-axis transient inductance (p.u.) | 0.411 | |
d-axis sub-transient inductance (p.u.) | 0.3 | |
d-axis short-circuit transient time constant (s) | 1.28 | |
d-axis short-circuit sub-transient time constant (s) | 0.043 | |
q-axis sub-transient inductance (p.u.) | 0.323 | |
q-axis short-circuit sub-transient time constant (p.u.) | 0.106 |

Fig. A1 Parameters of AC filters on LCC HVDC. (a) French side: the
References
P. Kundur, Power System Stability and Control. New York: McGraw-Hill, 1994. [Baidu Scholar]
P. M. Anderson, B. L. Agrawal, and J. E. V. Ness, Subsynchronous Resonance in Power Systems. New York: IEEE Press, 1990. [Baidu Scholar]
C. Karawita, “HVDC interaction studies using small signal stability assessment,” Ph.D. dissertation, University of Manitoba, Winnipeg, Canada, 2009. [Baidu Scholar]
M. Bahrman, E. Larsen, R. Piwko et al., “Experience with HVDC ‒ turbine-generator torsional interaction at Square Butte,” IEEE Transactions on Power Apparatus and Systems, vol. PAS-99, no. 3, pp. 966-975, May 1980. [Baidu Scholar]
Y. Yu, Q. Wei, X. Zhao et al., “Evaluation of subsynchronous oscillation of Xiluodu right station ‒ Guangdong double line [Baidu Scholar]
kV DC transmission project,” in Proceedings of 2012 IEEE International Conference on Power System Technology (POWERCON), Auckland, New Zealand, Oct.-Nov. 2012, p. 13248588. [Baidu Scholar]
W. Du, Z. Zhen, and H. Wang, “The subsynchronous oscillations caused by an LCC HVDC line in a power system under the condition of near strong modal resonance,” IEEE Transactions on Power Delivery, vol. 34, no. 1, pp. 231-240, Feb. 2019. [Baidu Scholar]
P. Bornard, D. Souque, and A. Vieilpeau, “Torsional interactions between the Gravelines units and the 2000 MW cross-channel DC links: protection of the turbine-generator units,” in Proceedings of CIGRE International Conference on Large High Voltage Electric Systems, Paris, France, Aug.-Sept. 1988, pp. 5-19. [Baidu Scholar]
S. Kovacevic, D. Jovcic, O. Despouys et al., “Eigenvalue study of torsional interactions between Gravelines generator and IFA2000 HVDC,” in Proceedings of the 2019 20th International Symposium on Power Electronics, Novi Sad, Serbia, Oct. 2019, p. 19231985. [Baidu Scholar]
N. Prabhu and K. R. Padiyar, “Investigation of subsynchronous resonance with VSC-based HVDC transmission systems,” IEEE Transactions on Power Delivery, vol. 24, no. 1, pp. 433-440, Jan. 2019. [Baidu Scholar]
L. Harnefors, “Analysis of subsynchronous torsional interaction with power electronic converters,” IEEE Transactions on Power Systems, vol. 22, no. 1, pp. 305-313, Feb. 2007. [Baidu Scholar]
D. Jovcic and K. Ahmed, High Voltage Direct Current Transmission: Converters Systems and DC Grids, 2nd ed. New York: Wiley, 2019. [Baidu Scholar]
S. Kovacevic, D. Jovcic, S. S. Aphale et al., “Analysis of potential low frequency resonance between a 1 GW MMC HVDC and a nearby nuclear generator,” Electric Power Systems Research, vol. 187, p. 106491, Oct. 2020. [Baidu Scholar]
C. Guo, W. Liu, C. Zhao et al., “Small-signal dynamics and control parameters optimization of hybrid multi-infeed HVDC system,” International Journal of Electrical Power & Energy Systems, vol. 98, pp. 409-418, Jun. 2018. [Baidu Scholar]
S. Kovacevic, D. Jovcic, O. Despouys et al., “Comparative stability analysis of LCC, MMC and dual-infeed HVDC operating with weak AC network,” in Proceedings of the 2020 IEEE PES General Meeting (PESGM), Montreal, Canada, Aug. 2020, p. 20276873. [Baidu Scholar]
D. Jovcic, N. Pahalawaththa, M. Zavahir et al., “Small signal analysis of HVDC-HVAC interactions,” IEEE Transactions on Power Delivery, vol. 14, no. 2, pp. 525-530, Apr. 1999. [Baidu Scholar]
H. Dommel, EMTP Theory Book. Vancouver: Microtran Power System Analysis Corporation, Apr. 1996. [Baidu Scholar]
IEEE Guide for Synchronous Generator Modeling Practices in Stability Analyses, IEEE Standard P1110, 2002. [Baidu Scholar]
Guide for the Development of Models for HVDC Converters in a HVDC Grid, CIGRE Working Group B4.57, 2014. [Baidu Scholar]
O. Ramos, L. Naredo, J. Mahseredjian et al., “A wideband line/cable model for real-time simulations of power system transients,” IEEE Transactions on Power Delivery, vol. 27, no. 4, pp. 2211-2218, Oct. 2012. [Baidu Scholar]
Experience Feedback on the Cross-channel 2000 MW Link After 20 Years of Operation, CIGRE Working Group B4-203, 2006. [Baidu Scholar]
P. H. Adam and Z. Yao, “Validation of digital simulation for studies of torsional interaction between a turbo-generator and an HVDC link,” in Proceedings of International Conference on AC and DC Power Transmission, London, UK, Sept. 1991, p. 4031712. [Baidu Scholar]
Dynamic Models for Turbine ‒ Governors in Power System Studies, Tech. Rep. PES-TR1, IEEE Power & Energy Society, USA, 2013. [Baidu Scholar]
IEEE Recommended Practice for Excitation System Models for Power System Stability Studies, IEEE Standard 421.5-2016, 2016. [Baidu Scholar]
S. Kovacevic, D. Jovcic, P. Rault et al., “Small signal state space model of the frequency-dependent DC cable based on direct vector fitting,” in Proceedings of the 15th IET International Conference on AC and DC Power Transmission, Coventry, UK, Feb. 2019, pp. 1-6. [Baidu Scholar]
A. Jamshidifar and D. Jovcic, “Small signal dynamic DQ model of modular multilevel converter for system studies,” IEEE Transactions on Power Delivery, vol 31, no. 1, pp. 191-199, Feb. 2016. [Baidu Scholar]