Abstract
When a renewable energy station (RES) connects to the rectifier station (RS) of a modular multilevel converter-based high-voltage direct current (MMC-HVDC) system, the voltage at the point of common coupling (PCC) is determined by RS control methods. For example, RS control may become saturated under fault, and causes the RS to change from an equivalent voltage source to an equivalent current source, making fault analysis more complicated. In addition, the grid code of the fault ride-through (FRT) requires the RES to output current according to its terminal voltage. This changes the fault point voltage and leads to RES voltage regulation and current redistribution, resulting in fault response interactions. To address these issues, this study describes how an MMC-integrated system has five operation modes and three common characteristics under the duration of the fault. The study also reveals several instances of RS performance degradation such as AC voltage loop saturation, and shows that RS power reversal can be significantly improved. An enhanced AC FRT control method is proposed to achieve controllable PCC voltage and continuous power transmission by actively reducing the PCC voltage amplitude. The robustness of the method is theoretically proven under parameter variation and operation mode switching. Finally, the feasibility of the proposed method is verified through MATLAB/Simulink results.
WITH the increase in the number of installations of large-scale renewable energy stations (RESs), their stable control and transmission are urgently demanded. A modular multilevel converter based high-voltage direct current (MMC-HVDC) can not only avoid commutation failure and reactive power compensation, but also build grid-connected voltage at the point of common coupling (PCC), thereby avoiding the need for large-capacity thermal power plant construction or AC grid expansion in remote areas. Thus, MMC-HVDC is a mainstream option for islanded renewable energy transmission.
Each RES interfaces the rectifier station (RS) of the MMC-HVDC through the PCC, which poses a high risk for an AC fault due to the large number of interconnected transmission lines. With a focus on fault analysis and fault ride-through (FRT), numerous studies have been conducted. However, they have mainly focused on grid-connected systems. References [
These previous studies focused on grid-connected systems, where the power grid could be Thevenin equivalent to an ideal voltage source in series with line impedance. Unlike the classic grid-connected system, the RS external response in an MMC-integrated system is determined by the RS AC voltage loop, which may become saturated under the fault, causing the RS to change from an equivalent voltage source to an equivalent current source [
Based on existing studies, the fault response under RES and RS control switching must be further examined, and the FRT method for an MMC-integrated system under multiple uncertainties must be improved. Accordingly, symmetric and asymmetric faults of an MMC-integrated system are fully analyzed in this study, and a high-performance FRT method is proposed, with its effectiveness demonstrated under parameter variations. The contributions of this study are described as follows.
1) The responses of symmetric and asymmetric faults under an MMC-integrated system are demonstrated. Under a symmetric fault, the MMC-integrated system has five operation modes and three common characteristics, and controllable PCC voltage and continuous power transmission are possible by optimizing PCC voltage. Under an asymmetric fault, NS voltage suppression rather than NS current suppression is adopted, and RS overcurrent and saturated modulation can be observed.
2) A high-performance AC FRT method is proposed. The proposed method can maintain continuous power transmission under fault, which is very helpful in blocking the unbalanced power that flows from the DC grid to the fault point. In addition, RS overcurrent and saturated modulation under an asymmetric fault can be effectively suppressed.
The remainder of this paper is organized as follows. Section II introduces the system description, where a basic block of the system model is presented to describe the research scope of the study. Section III analyzes the symmetric AC faults, including the RES and RS operation modes and solutions to the RS equilibrium points under fault resistance variation. Section IV analyzes asymmetric AC faults based on the findings from the Section III. Section V presents the active PCC voltage drop control, where the RS continuous power transmission area is identified and the maximum power transmission curve is derived. Moreover, the effective range calculation is conducted, and the robustness of the method is verified. Section VI presents simulation verification, where the veracity of the theoretical analysis and of the proposed method are proven through MATLAB/Simulink results. Finally, conclusions are given in Section VII.
The block of an RES connected to the MMC-HVDC system is shown in

Fig. 1 Block of an RES connected to MMC-HVDC system.
RESs are commonly used as models of lumped controllable current sources with choppers and grid-side inverters [
The AC transmission line can be characterized by lumped resistor-inductor (RL) model [
The AC fault, marked red in
The RS adopts a bipolar configuration, where both positive and negative converters are half-bridge MMCs with identical parameters. The MMC in the RS adopts a detailed equivalent model based on double diodes [
If the power loss at the fault point is less than the RES output power, the RS receives the residual power and continuously transmits it to the DC bus. In this case, the absolute value of RS current reference irdref is less than its limitation value Irmax, and thus, the d-axis PI controller of the RS AC voltage loop is not saturated, and ur can be controlled to be the rated value Urn.
The critical Rf value can be calculated by the constraint that the RS received power is greater than 0:
(1) |
where Ps and Pr are the active power output by the RES and that transmitted to the RS, respectively; and Ur and Urn are the measured and rated amplitudes of , respectively.
The main parameters of simulation are listed in
Symbol | Value | Symbol | Value | Symbol | Value |
---|---|---|---|---|---|
Pbase | 3000 MW | Psn | 2250 MW | Urn | 230 kV |
udcn | 500 kV | ks | 35/230 | ||
Lac | 13.08 mH | Irmax | 1.133 p.u. | kr | 230/290 |

Fig. 2 Simulation results when Ω.
In
When the RES output power is less than the power loss of the fault point, the RS active power flow is reversed. If , the PI controller of the RS AC voltage loop is not saturated, and ur is still controlled to be the rated value under the AC fault:
(2) |
where is the RS output power limitation.

Fig. 3 Simulation results when Ω.
If reaches Irmax, the PI controller of the RS AC voltage loop is saturated, and RS becomes a constant current source. In this case, the PCC voltage is out-of-control and its amplitude is determined by the RES output current, Irmax, and Rf.
If the amplitude of us remains higher than 0.9 p.u., the RES does not enter LVRT mode:
(3) |
where is the rated value of the amplitude of us; and isd is the d-axis current of is, which can be regarded as a rated value because the RES remains in normal operation mode.

Fig. 4 Simulation results when Ω.
Because of the saturation of the voltage loop, the output value of the PI integrator keeps increasing and causes overvoltage of usa [
When Rf is further decreased, the RES and RS output power can no longer maintain normal PCC voltage, and thus the RES begins to enter LVRT mode.
In this case, the fault point voltage is:
(4) |
where Isn is the rated value of is.
Based on the LVRT standard [
(5) |
According to (4) and (5), the relationship between Ur and Us must first be solved to obtain the critical value of Rf in this case.
The voltage equation given in
(6) |
where subscript denotes the frame.
(7) |
where subscript dq denotes the PLL frame; and is the angular frequency measured by the RES PLL.
Combined with the final value theorem, the fault steady- state equation of (7) becomes:
(8) |
As us is oriented to the d-axis by the RES PLL, (8) can be simplified as:
(9) |
where urd and urq are d- and q-axis components of ur, respectively.
(10) |
As isd is calculated by Isn in the AC fault, we can obtain:
(11) |
(12) |
When (5) is combined with (12), PCC voltage amplitude Ur under the fault steady state can be expressed as:
(13) |
When (5) and (13) are substituted into (4), the relationship between Rf and Us can be solved.

Fig. 5 Simulation results when Ω.
When Rf further decreases, the RES output current reaches its limitation, and therefore, both the RES and RS become constant current sources. Substituting these constraints into (10) and (4) yields:
(14) |
Simulation results when are shown in

Fig. 6 Simulation results when Ω.
The system operation mode under Rf variation is shown in

Fig. 7 System operation mode under Rf variation.

Fig. 8 RS equilibrium curve under a symmetric fault.
Figures
Asymmetric fault characteristics are studied based on the results presented in
Three-phase voltages, ua, ub, and uc are expressed as:
(15) |
where the superscripts + and - denote the positive sequence (PS) and NS components, respectively; and U and are the magnitude and phase of the voltage, respectively.
The Clarke transformation is applied to (15), and the result can be rewritten in an exponential form:
(16) |
Transforming (6) into the global PS and NS rotating frame yields:
(17) |
where means the conjugate. Equations (
Reference [

Fig. 9 Sequence network under a P-G fault when RS adopts NS voltage suppression.
According to the superposition theorem, we can obtain:
(18) |
where Zac denotes the line impedance.
The absolute value of the NS voltage equation in (18) is:
(19) |
where is the amplitude of ; and Rac is the resistance component of Zac.
The NS current specified by the grid code is:
(20) |
where is the NS reactive current coefficient.
Combining (19) and (20) yields:
(21) |
Obviously, the solution to (21) is . From (20), equals 0. Therefore, no NS component exists in the RES during a P-G fault. However, an NS current is generated, which may cause RS overcurrent and saturated modulation during AC FRT.
The MMC valve-side voltage equation and modulation ratio Mr in
(22) |
where Lreq is the equivalent MMC inductor; um is the MMC valve-side voltage; Um is the amplitude of um; and irp is the current of the RS positive pole, which equals .
Solving (18) and (22) yields Mr and the amplitude of , as shown in

Fig. 10 Irp and Mr under a P-G fault.

Fig. 11 Simulation results under a P-G fault ( Ω).
From the analysis in Section III, if Urn is adopted as the reference of RS AC voltage control, the fault response is uniquely determined, as shown in Figs.
If the RS AC voltage loop is unsaturated, the general expression of transmitted power is:
(23) |
Combined with RES LVRT mode analysis, (5) and (13) are substituted into (23), and the result of is plotted in

Fig. 12 RS active power under LVRT mode.
In
Both the colored surface and green areas of the 3D curve in

Fig. 13 RS active power optimization.

Fig. 14 Proposed fault ride-through function.
In addition to the maximum power transmission, active PCC voltage drop can not only help reduce voltage error, desaturate the PI controller, and suppress the PCC overvoltage after fault clearance, but also decrease the current loop feedforward to avoid over-modulation, as shown in
To avoid algorithm switching during a fault, the fitting result shown in
(24) |
According to (24), when an AC fault occurs, Pr decreases immediately, and thus the proposed method actively reduces Ur to move the RS equilibrium point to the maximum power transmission curve shown in
(25) |
where 0.9 p.u. is the lower limitation of normal PCC voltage; and 0.4 p.u. is the maximum valne of Pr in (24).
Combining (24) and (25) enables us to generate the proposed method, given as

Fig. 15 Block of proposed method.
When p.u., the RS equilibrium point violates the constraint in (24), , and the proposed method is equal to the rated AC voltage control. Similarly, when Ur and Pr violate (25), and the proposed method also becomes the rated AC voltage control to avoid steady-state PCC undervoltage. When , the output of (24) is activated to output the reference of the d-axis RS voltage loop.
The design guidelines of the proposed method are presented in

Fig. 16 Design guidelines of proposed method.
The effective range of the proposed method is shown in the green area of

Fig. 17 Effect of proposed method on continuous power supply.
The dotted-dashed and dotted lines indicate the RS equilibrium points under rated AC voltage control, where the dotted-dashed line indicates the continuous power transmission area. The green area represents the continuous power transmission area of the proposed method, which is a projection of the surface shown in
As
With the results in Figs.

Fig. 18 Proof of robustness under Lac variation.
In addition, if the topology in

Fig. 19 Proof of robustness under a newly connected RES.
As the wind speed usually changes in practice, the proposed method should be tested under a steady-state low-power operation. The results are shown in

Fig. 20 Proof of robustness under a steady-state low-power operation.
Therefore, the proposed method is robust under inaccurate parameter measurements, unplanned RES expansion, and wide variations in wind speed.
To prove the veracity of the analysis presented in Figs.

Fig. 21 Simulation comparisons when Ω. (a) Fault response. (b) MMC internal states under proposed method.

Fig. 22 Simulation comparisons when Ω. (a) Fault response. (b) MMC internal states under proposed method.

Fig. 23 Simulation comparisons when Ω. (a) Fault response. (b) MMC internal states under proposed method.

Fig. 24 Simulation comparisons when Ω. (a) Fault response. (b) MMC internal states under proposed method.

Fig. 25 Verification under a P-G fault ( Ω). (a) Fault response. (b) MMC internal states under proposed method.

Fig. 26 Verification under a 2P-G fault ( Ω). (a) Fault response. (b) MMC internal states under proposed method.

Fig. 27 Verification under a newly connected RES ( Ω).
A. Comparisons with Case Shown in Fig. 2
The dotted lines in
B. Comparisons with Case Shown in Fig. 3
The dotted lines in
C. Comparisons with Case Shown in Fig. 4
The dotted lines in
D. Comparisons with Case Shown in Fig. 5
The dotted lines in
The proposed method was verified under a P-G fault, and the results are shown in
The proposed method was verified under a 2P-G fault, and the results are shown in
Although the ZS voltage and current are 0, the responses of a phase-to-phase (P-P) fault are similar to those of a 2P-G fault [
Under a newly connected RES, the topology in
In this section, the latest version of the voltage-optimized FRT method [
As the NS and ZS values are 0 under a symmetric fault, the method presented in Appendix A shows the similar response as the rated voltage control and its current loop. Thus, the response of this method is equal to that shown in Figs.

Fig. 28 Results of method in [
When FRT grid code is used in the RES, (20) requires that the RES output an NS current according to its NS terminal voltage, which changes the fault point voltage and in turn generates RES voltage regulation and current redistribution, resulting in a fault response interaction. From (19)-(21), the NS RES current is maintained at 0 in all cases when the RS adopts NS voltage suppression. Thus, the interaction is blocked. However, both the RES and RS become NS current sources when the method in [

Fig. 29 Results of method in [
Thus, although the method in [
This study analyzed the AC fault responses of MMC-integrated wind farms. It showed that the integrated system has five operation modes and three common fault characteristics under various fault resistances at the fault point. Wherein out-of-control PCC voltage and RS power reversal occur under multiple operation modes. This study also determined the RS continuous power transmission area during a fault and revealed that excessive PCC voltage amplitude is the primary cause of these instances of performance degradation. In addition, the active PCC voltage drop can greatly expand the continuous power transmission area under an AC fault. A novel FRT method was then proposed to realize the maximum power transmission and controllable PCC voltage under wide fault resistance variation. The method was shown to be robust under inaccurate line parameter measurements, unplanned RES expansion, and wide variations in wind speed.
Appendix
The blocks of RES control methods in PS and NS are shown in Figs. A1 and A2, respectively.

Fig. A1 Block of RES control method in PS.

Fig. A2 Block of RES control method in NS.

Fig. A3 Block of PS voltage control and its current loop.

Fig. A4 Block of NS voltage suppression control and its current loop.

Fig. A5 Block of circulating current suppression control.
The mathematical expression of Pr surface is:
(A1) |
Based on , the continuous power transmission area in the (Rf, Ur) plane can be obtained.
Solving and substituting the result into Pr, we can obtain the maximum curve in the Rf direction. A detailed expression is given by (A2).
(A2) |
References
H. Yuan, H. Xin, L. Huang et al., “Stability analysis and enhancement of type-4 wind turbines connected to very weak grids under severe voltage sags,” IEEE Transactions on Energy Conversion, vol. 34, no. 2, pp. 838-848, Jun. 2019. [Baidu Scholar]
M. Talha, S. R. S. Raihan, and N. A. Rahim, “A grid-tied PV inverter with sag-severity-independent low-voltage ride through, reactive power support, and islanding protection,” Journal of Modern Power Systems and Clean Energy, vol. 9, no. 6, pp. 1300-1311, Nov. 2021. [Baidu Scholar]
Y. Qu, L. Gao, G. Ma et al., “Conjoint analysis of crowbar switching scheme and its resistance based on statistical sampling for LVRT of DFIG,” Journal of Modern Power Systems and Clean Energy, vol. 7, no. 3, pp. 558-567, May 2019. [Baidu Scholar]
J. Yang, S. Mao, X. Li et al., “Influence mechanism and suppression control of the MMC on short-circuit current under AC faults,” IEEE Access, vol. 8, pp. 138307-138317, Jul. 2020. [Baidu Scholar]
J. Moon, J. Park, D. Kang et al., “A control method of HVDC-modular multilevel converter based on arm current under the unbalanced voltage condition,” IEEE Transactions on Power Delivery, vol. 30, no. 2, pp. 529-536, Apr. 2015. [Baidu Scholar]
S. Wang, G. P. Adam, A. M. Massoud et al., “Analysis and assessment of modular multilevel converter internal control schemes,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 8, no. 1, pp. 697-719, Mar. 2020. [Baidu Scholar]
Y. Li, X. Wang, J. Guo et al., “PLL synchronization stability analysis of mmc-connected wind farms under high-impedance AC faults,” IEEE Transactions on Power Systems, vol. 36, no. 3, pp. 2251-2261, May 2021. [Baidu Scholar]
H. Ye, W. Cao, W. Chen et al., “An AC fault ride through method for MMC-HVDC system in offshore applications including DC current-limiting inductors,” IEEE Transactions on Power Delivery, vol. 37, no. 4, pp. 2818-2830, Aug. 2022. [Baidu Scholar]
Y. Li, J. Guo, X. Zhang et al., “Over-voltage suppression methods for the MMC-VSC-HVDC wind farm integration system,” IEEE Transactions on Circuits and Systems II: Express Briefs, vol. 67, no. 2, pp. 355-359, Feb. 2020. [Baidu Scholar]
X. Wang, L. Yang, B. Lin et al., “Mechanism and restraining strategy of the sending-end grid overvoltage in offshore wind farm-flexible HVDC transmission system under grid faults,” High Voltage Engineering, vol. 47, no. 8, pp. 2688-2699, Aug. 2021. [Baidu Scholar]
L. Shi, G. P. Adam, R. Li et al., “Control of offshore MMC during asymmetric offshore AC faults for wind power transmission,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 8, no. 2, pp. 1074-1083, Jun. 2020. [Baidu Scholar]
Y. Jing, R. Li, L. Xu et al., “Enhanced AC voltage and frequency control of offshore MMC station for wind farm connection,” IET Renewable Power Generation, vol. 12, no. 15, pp. 1771-1777, Sept. 2018. [Baidu Scholar]
J. Freytes, S. Akkari, P. Rault et al., “Dynamic analysis of MMC-based MTDC grids: use of MMC energy to improve voltage behavior,” IEEE Transactions on Power Delivery, vol. 34, no. 1, pp. 137-148, Feb. 2019. [Baidu Scholar]
L. Shi, G. P. Adam, R. Li et al., “Enhanced control of offshore wind farms connected to MTDC network using partially selective DC fault protection,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 9, no. 3, pp. 2926-2935, Jun. 2021. [Baidu Scholar]
Technical Rule for Connecting Wind Farm to Power System, GB/T 19963-2011, China, 2011. [Baidu Scholar]
Technical Requirements for Connecting Photovoltaic Power System to Power System, GB/T 19964-2012, 2012. [Baidu Scholar]
X. Sun, Q. Zhang, B. Ren et al., “A novel digital phase-locked loop for distributed grid-connected power generation systems under unbalanced and distorted utility conditions,” in Proceedings of the 2nd International Symposium on Power Electronics for Distributed Generation Systems, Hefei, China, Aug. 2010, pp. 813-817. [Baidu Scholar]
W. Zhou, “The algorithm research about three-level APF virtual flux models predict SVPWM and FPGA implementation,” M.S. thesis, Department of Electronic Engineering, Lanzhou University of Technology, Lanzhou, China, 2018. [Baidu Scholar]
J. Freytes, J. Li, G. de Préville et al., “Grid-forming control with current limitation for MMC under unbalanced fault ride-through,” IEEE Transactions on Power Delivery, vol. 36, no. 3, pp. 1914-1916, Jun. 2021. [Baidu Scholar]
H. Zeng, F. Lin, and X. Kang. “Distributed parameter based distance protection for transmission lines and identification of short-circuit faults under low-, medium- and high-resistance at fault point,” Power System Technology, vol. 38, no. 1, pp. 262-268, Jan. 2014. [Baidu Scholar]
M. Langwasser, G. de Carne, M. Liserre et al., “Fault current estimation in multi-terminal HVDC grids considering MMC control,” IEEE Transactions on Power Systems, vol. 34, no. 3, pp. 2179-2189, May 2019. [Baidu Scholar]
X. Long, Y. Li, W. Xu et al., “A new technique to detect faults in de-energized distribution feeders ‒ Part II: symmetrical fault detection,” IEEE Transactions on Power Delivery, vol. 26, no. 3, pp. 1902-1910, Jul. 2011. [Baidu Scholar]
S. Chatterjee and B. K. S. Roy. “Fast identification of symmetrical or asymmetrical faults during power swings with dual use line relays,” CSEE Journal of Power and Energy Systems, vol. 6, no. 1, pp. 184-192, Mar. 2020. [Baidu Scholar]
M. G. Taul, X. Wang, P. Davari et al., “An overview of assessment methods for synchronization stability of grid-connected converters under severe symmetrical grid faults,” IEEE Transactions on Power Electronics, vol. 34, no. 10, pp. 9655-9670, Oct. 2019. [Baidu Scholar]
G. Bergna-Diaz, J. A. Suul, E. Berne et al., “Optimal shaping of the mmc circulating currents for preventing AC-side power oscillations from propagating into HVDC grids,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 7, no. 2, pp. 1015-1030, Jun. 2019. [Baidu Scholar]
W. Li and J. Bélanger, “An equivalent circuit method for modelling and simulation of modular multilevel converters in real-time HIL test bench,” IEEE Transactions on Power Delivery, vol. 31, no. 5, pp. 2401-2409, Oct. 2016. [Baidu Scholar]
J. Wang, J. Liang, C. Wang et al., “Circulating current suppression for MMC-HVDC under unbalanced grid conditions,” IEEE Transactions on Industry Applications, vol. 53, no. 4, pp. 3250-3259, Mar. 2017. [Baidu Scholar]
R. Li, J. E. Fletcher, and B. W. Williams. “Influence of third harmonic injection on modular multilevel converter-based high-voltage direct current transmission systems,” IET Generation, Transmission & Distribution, vol. 10, no. 11, pp. 2764-2770, Jun. 2016. [Baidu Scholar]