Abstract
The distributed capacitance of the line becomes larger as the scale of wind farms, the transmission voltage level, and the transmission distance increase. Hence, the error of the traditional time-domain distance protection scheme based on the R-L model, which ignores the distributed capacitance of the line, becomes unacceptable. Therefore, the error of the time-domain fault location method based on the R-L model, especially the maximum error range, is theoretically analyzed in this paper. On this basis, a novel fault location method based on the R-L and Bergeron models is proposed. Then, a fast time-domain distance protection scheme is designed. In the proposed scheme, the error in the fitting calculation is used to construct a weight matrix, and an algorithm for solving the time-domain differential equations is designed to improve the calculation speed and stability. Compared with the traditional frequency-domain distance protection scheme, the proposed scheme is independent of the power supply characteristics; thus, it is suitable for wind farm transmission lines. In addition, compared with the traditional method based on the R-L model, the proposed scheme effectively avoids the negative influence of the distributed capacitance of the line, which significantly improves the operating speed. Different types of faults are simulated by PSCAD/EMTDC to verify the effectiveness and superiority of the proposed scheme.
2022.
IN response to issues such as global climate change, environmental pollution, and energy strategies, countries around the world are actively promoting the low-carbon, clean, and sustainable transformation of energy systems [
At present, wind power generation is one of the most typical types of renewable energy power generation. However, the operation mode of a wind farm is obviously random and intermittent owing to the effects of climatic conditions and other factors [
Recently, much of the literature has focused on protection schemes that consider the effects of integrated wind farms [
However, it is noted that the above studies are mostly based on frequency-domain information. According to the response characteristic of a DFIG after a fault, the fault current of a power system integrated with a wind farm may exhibit frequency deviations and contain high-frequency harmonics [
Reference [
Therefore, a novel fast time-domain distance protection scheme based on iteration of the Bergeron model and error correction of the weight matrix is proposed in this paper. After a fault, the distance to the fault point is first estimated by an improved fault location algorithm based on the R-L model. Then, a confidence interval for the calculated value is evaluated according to a theoretical analysis of the steady-state and transient errors. According to this confidence interval, a point between the protection position and the fault point is selected. Moreover, the voltage and current at the selected point are calculated using the Bergeron model. Next, the voltage and current at the selected point are used to recalculate the fault distance with the improved fault location algorithm based on the R-L model. The above processes are iterated so that the selected point gradually approaches the fault point more closely without crossing the point of failure. Moreover, the effect of the distributed capacitance is also eliminated. After the iteration process, the final calculated result is obtained, and a protection judgment is made. The major contributions of this paper are summarized as follows.
1) The theoretical error of the fault location method based on the R-L model is derived in this paper. Hence, the limitations of the traditional time-domain distance protection scheme based on the R-L model and its applicable scenarios are clarified.
2) On the basis of the above error analysis, an iterative scheme combing the Bergeron and R-L models is proposed. The proposed scheme eliminates the location error caused by ignoring the distributed capacitance in the R-L model.
3) A stability enhancement algorithm based on the error weight matrix and the removal of singular points is proposed. Compared with existing time-domain distance protection schemes, the proposed algorithm has a faster convergence speed, greater stability, and better robustness to the transition resistance and noise. The feasibility and superiority of the proposed algorithm are verified by many simulation cases.
The remainder of this paper is organized as follows. Section II presents the time-domain distance protection scheme based on the R-L model and a theoretical derivation of its error range. In Section III, we introduce the principles of the proposed fast time-domain distance protection scheme. A case analysis and comparison are discussed in Section IV. Finally, Section V concludes the paper.
II. Time-domain Distance Protection Scheme Based on R-L Model and Theoretical Derivation of Its Error Range
With the rapid growth of wind power, the demand for long-distance and large-scale power transmission is increasing. Therefore, the error caused by ignoring the distributed capacitance of the transmission line in the R-L model may adversely affect protection. In view of this problem, the values of the errors in the distributed capacitance and its maximum range are analyzed in this section.
The differential equations for time-domain distance protection are based on the transmission line model with lumped parameters. The transmission line from the protection position to the fault point is represented by the series connection of resistors and inductors, i.e., equivalent to the R-L model. As shown in

Fig. 1 R-L series model of a transmission line.
In the case of a phase A grounding fault, the voltage umA(t) and current imA(t) measured at the protection position are [
(1) |
where i0(t) is the zero-sequence current; and r1)/(3r1) and )/) are the zero-sequence compensation coefficients of the resistance and inductance, respectively, and r0 and l0 are the zero-sequence resistance and inductance per unit length of the transmission line, respectively.
Under certain conditions, it is approximately assumed that the phase of the zero-sequence current flowing through the transition resistance is close to the phase measured at the protection position for single-phase grounding faults [
(2) |
where n is the number of sampling sequences; is the sampling interval; and .
Using the voltage and current continuously sampled by the protection, a series of equations such as (2) can be obtained and organized into matrix form as:
(3) |
where U, I, and are the voltage, current, and coefficient matrices, respectively, which can be calculated as:
(4) |
(5) |
(6) |
where k is the number of sampling points in a data window for calculation; p(n) is the current sampling sequence for calculation, which can be expressed as (7); and pd(n) is the differential derivative sequence of the current sampling points for calculation, which can be expressed as (8).
(7) |
(8) |
On the basis of the sampling sequence of a certain redundant data window, the least-squares method is used to estimate and solve (3), i.e., fitting the coefficient matrix so that the calculated value of the voltage matrix in the data window and the actual value (U) have the minimum distance in Euclidean space E, which can be expressed as:
(9) |
By computing the partial derivative of the coefficient matrix in the above expression and setting the partial derivative to be zero, can be expressed as:
(10) |
As aforementioned, the time-domain differential equations are constructed based on the R-L model for fitting and solving, and thus obtaining the fault distance, which is referred to as the R-L algorithm.
By comparing the R-L model and the long line equation, the error in the fault distance calculation caused by ignoring the distributed capacitance in the R-L model is analyzed in this paper.
Taking a single-phase system as example, and are the voltage and current at the protection position, respectively. Then, the voltage of point x can be calculated using the voltage and current at the protection position and the long line equation as:
(11) |
where is the propagation coefficient; and is the wave impedance of the transmission line.
When a metallic grounding fault occurs on the line, the voltage of the fault point is zero, i.e., . Using (11), a relation between the measured impedance and the fault distance is obtained in (12). The measured impedance accounts for the distributed capacitance of the transmission line.
(12) |
where is the power frequency.
When the transmission line is equivalent to that in the R-L model, the unit impedance of the line is . Using the more accurate measured impedance in (12), the fault distance calculated with the R-L model can be expressed as:
(13) |
At this point, the true fault distance is x; thus, the error in the fault distance calculation caused by ignoring the distributed capacitance of the line can be expressed as:
(14) |
For a transmission line with a total length of lh and a protection setting coefficient of kz, the fault location error at x must be less than if the fault occurs at x on the line. The calculated fault distance can correctly fall in or out of the protection zone only in this manner. Therefore, the condition for correct operation of distance protection is that the fault location error is not greater than the difference between the fault distance and the set distance. The allowable error of the calculated fault distance can be expressed as:
(15) |
It can be observed from (9) that the error caused by the distributed capacitance in the R-L model is related to the frequency. The access of a wind farm may add an attenuation current component of the rotor speed frequency to the fault current, and its frequency is 0.7-1.3 times the power frequency [
Given the transmission line parameters , mH/km, and , the error caused by the distributed capacitance at 35, 50, and 65 Hz is calculated. Taking the distance protection setting value of as an example, the allowable error for distance protection is calculated when the line length is 200, 300, and 400 km, respectively. The calculated results are shown in

Fig. 2 Error of R-L model at different frequencies and its influence on distance protection. (a) Ranges of error in R-L model and allowable error of distance protection. (b) Rejection lengths of protection for different line lengths and frequencies.
The above analysis of the possible rejection length of protection is based on the steady state. In fact, owing to the access of the large-scale wind farm, the error in the calculated fault distance will be further increased as the high-frequency component in the fault transient increases. The reliability of distance protection will be reduced further.
When a fault with a transition resistance occurs at x on the line, the voltage at the fault point is no longer zero, and the assumption that in the aforementioned error analysis is no longer valid.
At , we expand the long line equation in (11) by a first-order Taylor expansion:
(16) |
where , which is the Lagrange remainder of the first-order Taylor expansion in (16), and is a certain point from the protection position to the fault point.
It is noted that when (16) ignores the Lagrange remainder and is transformed into the time domain, it becomes a time-domain R-L equation. Therefore, is the error of the R-L model.
In the case of a fault with a transition resistance, the fault distance can be calculated as:
(17) |
where ; and . Therefore, .
xCALC(1) can be regarded as the fault distance calculated by the R-L model in the physical sense, and is the calculated fault distance of the Lagrange remainder. Therefore, the error in the fault distance calculated by the R-L model cannot exceed at most. Since an accurate value for in cannot be determined, an accurate calculated value for cannot be obtained. However, from the derivation process for the Lagrange remainder, it is known that is the voltage at a certain point from the protection position to the fault point; thus, it satisfies the condition that . Therefore, the range of can be expressed as:
(18) |
where is the conductance per unit length of the transmission line; and Zm is the apparent impedance at the protection position. Assuming that a transmission line is equivalent to the Γ model, Zm can be expressed as:
(19) |
By substituting (19) into (18) and rearranging, the maximum error is expressed as:
(20) |
where ; and .
When the frequency is set to be 50 Hz, the rejection length of protection caused by the error in the distributed capacitance is calculated for different transition resistances, as shown in

Fig. 3 Rejection lengths of protection for different transition resistances and line lengths.
In this subsection, an improvement to the algorithm for solving the differential equations of the R-L model based on the error weight matrix is presented (referred to as improved R-L algorithm). This algorithm can improve the convergence speed while ensuring stability. The calculated transient error based on the fitting error is analyzed.
When solving the differential equations of the R-L model, the difference instead of the differentiation for derivation causes algorithm errors. Differential derivation has the largest error across the sampling point at the peak of the current. Defining these points as singular points, it is easy to show that these points satisfy:
(21) |
As the protection installation continuously acquires sampling data, the current derivative sequence is continuously determined and detected by (21). If sampling point ns meets the above condition, the fitting calculation weight of ns and its nearby points will be reduced. To this end, a diagonal matrix of error weights is introduced, whose element is:
(22) |
where k is the number of sampling points in the unit data window; and cn is the value of the real number, which is determined by the number of sampling points in the unit data window.
After introducing the matrix of error weights, (9) can be rewritten as:
(23) |
By solving the equation above, the coefficient matrix to be calculated after the weights of the singular points are reduced is obtained as:
(24) |
In general, the calculated results may have relatively large fluctuations for the same sampling rate when the data window for calculating the differential equations is short; when the data window is relatively long, the calculated results are more stable. However, during the process of the transient-state to steady-state calculation, the long data window may contain both transient- and steady-state data, resulting in the calculated results that reach the final steady-state value more slowly than the shorter data window.
In order to solve the problems above, a short sliding data window is selected for calculation in this paper to ensure rapid convergence. After the calculation starts to enter the steady state, a matrix of error weights is introduced to calculate the weighted average of the fitting results to ensure the stability of the calculation. The error weight matrix is determined as follows.
The fitting error in the unit data window is defined as:
(25) |
The value of the fitting error reflects the degree of agreement between the results of the fitting calculation and the true parameters. When the transient process is severe, the differential equations cannot obtain stable solutions, and the fitting error is relatively large. When the calculation begins to enter the steady state, the fitting error approximates zero. Therefore, the reciprocal of the fitting error 1/Er can be used as the weight coefficient of the result of a single fitting calculation. A larger weight coefficient means that the result of the fitting calculation is closer to the actual value. In this paper, a specific value of Er is used as the threshold for determining whether the calculation starts to enter the steady state. When Er is larger than the threshold, the calculated results will not be artificially modified.
When Er is less than the threshold for the first time, the previous results of the fitting calculation are discarded. The subsequent calculated results are weighted and averaged according to the above-mentioned weight coefficients. Assume that Er is less than the threshold for the first time at the
(26) |
where is the element of ; ; and , and is the fitting error at the
On the basis of a simulation analysis of a power grid with 100% integration of a wind farm, a single-phase grounding fault simulation experiment is carried out at intervals of 50 km on a 400 km line, and different transition resistances are set for each fault. The experimental data are calculated by a least-squares fitting based on the R-L model. The simulation model and calculation parameters are presented in Section IV. The current threshold of the fitting error is set to be . The time for the fitting error Er to reach the threshold is defined as tthr. The relative error of the transient calculation is defined as the ratio of the current calculated value minus steady-state value to the steady-state value.
In all examples, the value and distribution of tthr are shown in

Fig. 4 Relationship between fitting error and transient error. (a) Time taken to reach fitting error threshold. (b) Relative transient error ranges at tthr and every 1 ms after tthr.
In the time domain, the voltage and current at x on the transmission line can be calculated with the voltage and current at the protection position using the Bergeron model [
(27) |
(28) |
(29) |
(30) |
where , v is the wave celerity; is the retardation factor, so there is ; and is the wave impedance of a nondissipative line.
When the R-L model is used for calculation, the error in the fault location caused by the distributed capacitance is . The voltage and current can be calculated from the protection position to () on the line by the Bergeron model in (27) and in combination with the phase-mode transformation. The R-L model is used to recalculate the fault distance using the voltage and current at on the transmission line. The error in the fault distance caused by distributed capacitance in the final calculated result is . Therefore, the error caused by the distributed capacitance can be reduced through the calculation of the Bergeron model.
At the same time, the starting point of the R-L model is shifted towards the fault point because of the calculation of the Bergeron model. The influence of the distributed capacitance is reduced. Therefore, the convergence speed and stability of the calculation will be improved.
It can be observed from Section II that the fault location calculated by the R-L model is greater than the actual value when the error in the branching coefficient CF is neglected. Further, it is more difficult to determine the true fault point owing to the effects of the transient process. If the voltage and current are calculated to the rear of the fault point by the Bergeron model, the obtained voltage and current are false. In particular, the phase of the calculated voltage is opposite to that of the actual value when a transition resistance exists. Therefore, the fault location based on this calculation will no longer be accurate. It is particularly important to select the appropriate calculation point for the Bergeron model. In this paper, a distance protection scheme based on Bergeron iteration combined with an error analysis is proposed. The flowchart of this scheme is shown in

Fig. 5 Flowchart of distance protection scheme based on Bergeron iteration combined with error analysis.
In each fault distance fitting calculation, the short sliding data window is selected, and the improved R-L algorithm is used for the fitting calculation. The value of the fault distance from the fitting calculation at tthr is selected as x0, and distance protection is first determined using (31). Considering the transient calculation error and the minimum error caused by the distributed capacitance, the fault distance can fall within the setting value, and the transition resistance is less than the setting value. Thus, the distance protection operates. When (31) is not satisfied at time tthr, new calculated results for the fault distance are continuously obtained with the continuous entry of sampling data. From tthr to 5 ms after tthr, the distance protection determined by (31) is continued until it is satisfied.
(31) |
where xset is the value set for the distance protection; is the calculated result for the equivalent transition resistance in the
When 5 ms after tthr has passed, if (31) is still not satisfied, it can be determined that the fault point is closer to the set point or that the transition resistance is larger.
Thus, the process of Bergeron iteration is started. The line length that can be calculated in the direction of the fault point by the Bergeron model is expressed in (32). The maximum error caused by the transient calculation and distributed capacitance is comprehensively considered to ensure that the calculation point is in front of the fault point. For single terminal information, it is impossible to know an accurate value for the transition resistance. In this paper, RF is taken as the maximum possible value of the current voltage level when considering the maximum error of the distributed capacitance.
(32) |
where is the maximum distance that can be calculated with the Bergeron model during the
The condition for stopping the iterative calculation of the Bergeron model is expressed in (33). This means that the error that is actually reduced by the two iterative calculations before and after is already less than the minimum theoretical error that can be reduced by the two iterative calculations. At this time, it is no longer an actual benefit to continue the iterative calculation. It is considered that the theoretical and transient calculation errors have been eliminated to the greatest extent.
(33) |
where kb is the coefficient considering the error margin of the calculation, which is selected according to the calculation schedule, and is taken to be 1.2 in this study.
When the last two calculated results for the fault distance satisfy (33), the starting point of the calculation for the R-L model is already close to the fault point to the greatest extent. Thus, the transient calculation process has been greatly weakened. At this time, the margin of the transient calculation error is no longer considered. Therefore, the distance protection operation is judged by:
(34) |
In summary, when the transition resistance is less than the threshold value, the scheme combines the error in the distributed capacitance and the relative transient error of the improved algorithm to determine the distance protection. When the fault point is far from the set point and the error is not sufficiently high to cause the protection to refuse to operate or incorrectly operate, the scheme determines the distance protection operation. When the fault point is close to the set point, the voltage and current are gradually calculated to the front of the fault point by the iterative scheme on the premise of ensuring that the calculation point will not cross the fault point. This can eliminate the transient- and steady-state errors caused by the distributed capacitance to the maximum extent. On the basis of the above calculations, the final fault location is obtained to determine the distance protection.
When the transition resistance is large and the branch coefficient CF can no longer be regarded as a real number, it is the most unfavorable situation for the R-L model. In this case, there may be a large error in the fault location. Therefore, the threshold is usually set for the calculated value of the transition resistance . However, when the threshold is set to be a small value, it may cause the protection to refuse to operate with the transition resistance fault in the protection zone. When the threshold is set to be a large value, it may cause the protection to operate incorrectly when the fault occurs outside the protection zone. For the R-L model, if the resistance and reactance are solved as two unknowns, as in (35), the impedance trajectory of the fault loop is calculated and compared with the setting impedance circle, and the fault zone can be better determined in the case of high-resistance faults, thus solving the above problems to a certain extent.
(35) |
where Rx and Lx are the lumped equivalent resistance and inductance of the fault loop, respectively.
However, the solution of (35) is not as stable as that of (1). The convergence speed is poor. Therefore, for the scheme proposed in this paper, the calculation for solving (35) is carried out after the Bergeron iteration is completed. This can greatly reduce the influence of the transient process on the calculated solution. Using the improved algorithm in this paper can make the calculated result more stable and converge faster. The final results for the impedance calculation can be expressed as:
(36) |
where and are the equivalent impedance and inductive reactance of the fault loop during the fault location calculation, respectively; and and are the equivalent resistance and inductance of the fault loop calculated by (35) with the voltage and current at on the line, respectively.
The value of the fault impedance calculated with (36) is compared with that of the setting impedance circle to determine the distance protection operation.
(37) |
where ; and is the setting impedance of the distance protection. On the basis of the above improved algorithm and the simulation examples in the following section, is set to be a smaller value of 300 to prevent the protection from incorrect operation in the case of external faults.
In PSCAD/EMTDC, the equivalent model for 100% integration of a wind farm into the power grid is built, as shown in
Parameter | Value |
---|---|
Rated power | 5 MW |
Number of DFIGs | 100 |
Rated voltage | 690 V |
Rated stator frequency | 50 Hz |
Stator resistance | 0.0054 p.u. |
Stator leakage inductance | 0.10 p.u. |
Wound rotor inductance | 0.00607 p.u. |
Wound rotor leakage inductance | 0.11 p.u. |
Rated wind speed | 10.5 m/s |
Parameter | Value |
---|---|
Positive- or negative-sequence resistance | 0.0208 Ω/km |
Positive- or negative-sequence inductance | 0.8984 mH/km |
Positive- or negative-sequence capacitance | 0.0129 μF/km |
Zero-sequence resistance | 0.1148 Ω/km |
Zero-sequence inductance | 2.2886 mH/km |
Zero-sequence capacitance | 0.0052 μF/km |
In the analysis and calculation of the cases in this paper, the fault is set at the voltage peak at 3 s, the simulated sampling rate is 10 kHz, the sampled data are filtered through a 120 Hz Butterworth third-order low-pass filter, and the distance protection I segment is set to be 90% of the line length.
To verify the effectiveness of using the Bergeron model to reduce the steady-state error and transient process, a single-phase grounding metallic fault is set at 300 km on the transmission line. Using the Bergeron model in (27) and phase-to-mode transformation, the voltage and current at the protection position are calculated at 90, 180, and 270 km on the transmission line, respectively. The above Bergeron calculation points are used as the starting points of the R-L model to fit the fault distance. The calculation results of fault distance at different points by Bergeron model are shown in

Fig. 6 Calculation results of fault distance at different points by Bergeron model.
When the fault points are far away from the protection setting point and the transition resistance is less than the threshold, it can be concluded that the error range meets the protection operation requirements in the proposed protection scheme. Thus, the Bergeron iteration will not be triggered. To verify the effectiveness of the improved R-L algorithm for solving the differential equations of the R-L model, a single-phase metallic grounding fault is set at 100, 200, and 300 km on the transmission line. When performing least-squares fitting and solving, the data windows used for calculation are selected to be 0.8, 5, and 10 ms, respectively. The latter two are the length of the data windows commonly used in other papers when fitting and solving the differential equations of the R-L model [

Fig. 7 Fitting results for different fault distances and different data windows. (a) 100 km. (b) 200 km. (c) 300 km.
When the fault point is close to the setting point of distance protection, the proposed scheme triggers Bergeron iteration. To verify the effectiveness of the proposed scheme in reducing the transient- and steady-state errors, a single-phase metallic grounding fault is set at 342, 350, and 378 km on the transmission line, respectively.
The power frequency algorithm based on Fourier transform (referred to as Fourier algorithm), the traditional R-L algorithm, the improved R-L algorithm, and the proposed scheme are used to calculate the fault distance, respectively. The results are shown in

Fig. 8 Results of fitting calculation for fault distances when a single-phase metallic grounding fault is set at 342, 350, and 378 km on transmission line. (a) 342 km. (b) 350 km. (c) 378 km.
When the fault occurs at 95% of the protection setting value (342 km), the traditional R-L algorithm fluctuates up and down at this value, resulting in incorrect operation. The Fourier algorithm has the largest error and fluctuation. The improved R-L algorithm is stable below the setting value, and the proposed scheme converges near the actual value of the fault distance. In case of terminal fault in the protection zone, the improved R-L algorithm and the proposed scheme can correctly operate. When the fault occurs at 350 km on the transmission line, the fault distance calculated by the traditional R-L algorithm completely exceeds the setting value because the distributed capacitance is ignored, or it exceeds the full length of the transmission line. The proposed scheme can quickly converge near the actual value of the fault distance, and the protection can correctly operate. When the fault occurs at 105% of the protection setting value (378 km), each algorithm can ensure that the protection does not malfunction, whereas the proposed scheme can obtain a more accurate and stable fault distance.
To verify the anti-transition resistance capability of the proposed scheme, a single-phase grounding fault with a transition resistance is set at 300 and 378 km on the transmission line, respectively. The impedance trajectory of the fault loop is calculated by the proposed scheme and directly calculated by (35) (defined as scheme 1), respectively. The comparison is shown in

Fig. 9 Impedance trajectory of fault loop when a single-phase grounding fault with a 300 Ω transition resistance is set at 300 and 378 km on transmission line. (a) 300 km. (b) 378 km.
Taking a single-phase grounding fault as an example, more simulation examples and data for the proposed scheme are summarized in Table III. “Y” means that the calculated impedance trajectory is inside the setting impedance circle. “N” means that the calculated impedance trajectory is outside the setting impedance circle. “-” means that the calculated value of the transition resistance is less than the threshold value (300 ) and no impedance calculation is required. “√” indicates that the distance protection operates or does not operate correctly. “” indicates that the distance protection fails to operate or incorrectly operates. “t” represents the time required for distance protection to make a judgement. It can be observed from the data in Table III that the proposed scheme can obtain a quick judgment in about 15 ms for all types of faults. Moreover, the proposed scheme has a strong ability to resist the transition resistance.
Fault type | Fault location (km) | RF (Ω) | xn (km) | () | Impedance trajectory | Distance protection | t (ms) |
---|---|---|---|---|---|---|---|
Internal fault | 100 | 0 | 100.65 | 0.00 | - | √ | 13.70 |
50 | 103.36 | 69.80 | - | √ | 13.50 | ||
100 | 105.96 | 139.66 | - | √ | 13.40 | ||
200 | 110.84 | 279.55 | - | √ | 13.40 | ||
300 | 110.21 | 419.65 | Y | √ | 14.80 | ||
200 | 0 | 203.71 | 0.00 | - | √ | 14.50 | |
50 | 206.70 | 101.69 | - | √ | 13.30 | ||
100 | 209.33 | 203.53 | - | √ | 13.20 | ||
200 | 208.71 | 407.60 | Y | √ | 14.77 | ||
300 | 214.15 | 610.40 | Y | √ | 14.88 | ||
300 | 0 | 299.10 | -0.03 | - | √ | 15.65 | |
50 | 299.33 | 186.93 | - | √ | 15.14 | ||
100 | 301.63 | 301.63 | Y | √ | 14.95 | ||
200 | 308.58 | 746.85 | Y | √ | 15.03 | ||
300 | 316.05 | 1119.80 | Y | √ | 15.12 | ||
350 | 0 | 350.43 | -0.06 | - | √ | 16.88 | |
50 | 340.72 | 316.82 | Y | √ | 15.46 | ||
100 | 334.64 | 633.68 | N | × | 15.53 | ||
200 | 327.04 | 1265.95 | N | × | 15.59 | ||
300 | 324.90 | 1888.65 | N | × | 15.68 | ||
External fault | 378 | 0 | 377.80 | -0.10 | - | √ | 12.99 |
50 | 341.60 | 522.66 | N | √ | 15.95 | ||
100 | 326.60 | 1023.15 | N | √ | 15.81 | ||
200 | 322.19 | 2030.07 | N | √ | 13.53 | ||
300 | 400.64 | 3036.14 | N | √ | 13.33 |
Owing to the weak feed-in characteristic of the wind farm, the opposite terminal source exhibits a strong feed-in function during faults. Obviously, this is similar to the case of a heavily loaded line with a strong infeed from the remote source, where the assumption that the branching coefficient CF is a real number is no longer applicable. At this time, the calculation error caused by the above assumption is large. In order to avoid the incorrect operation of distance protection, the proposed scheme sets a threshold . If the calculated exceeds , the impedance trajectory is calculated, and the impedance circle is introduced to identify the fault position. Therefore, in the simulation cases in Table III, the impedance trajectories exceed the impedance circle for the high-impedance faults at the end of the protection zone (e.g., at 350 km), and the proposed scheme refuses to operate. In regards to the above situation, the proposed scheme needs further research and improvement, which will be developed in the future work.
To simulate a real situation, white Gaussian noise is added to the sampled signal. In the case of different signal-to-noise ratios (SNRs), the proposed scheme is compared with the traditional time-domain distance protection scheme. A single-phase metallic grounding fault is set at 100 and 350 km on the transmission line as examples for comparison. The SNR is set to be 30 and 20 dB, respectively. A comparison between the proposed and traditional schemes is shown in

Fig. 10 Influence of noise when a single-phase metallic ground fault is set at 100 and 350 km on transmission line. (a) 100 km. (b) 350 km.
The proposed scheme is also applicable to other types of faults. Line-to-line faults and three-phase-to-ground faults at 100 km on the transmission line are used as examples. The proposed scheme is compared with the traditional R-L algorithm and the Fourier algorithm. The simulation results are shown in

Fig. 11 Simulation results of phase-to-phase fault and three-phase fault at 100 km on transmission line. (a) Phase-to-phase fault. (b) Three-phase fault.
For the time-domain distance protection scheme used for transmission lines connected to wind farms, the location error of the R-L model caused by ignoring the distributed capacitance of the transmission line is deduced in this paper, and its influence on distance protection is analyzed. The analysis shows that the operation of distance protection may fail when ignoring the distributed capacitance of the transmission line as the system voltage level and transmission distance increase. In this paper, the precise range over which distance protection fails to operate is theoretically analyzed.
For the time-domain distance protection scheme based on the R-L model, an algorithm for improving the error weights based on a short-term data window, which converges faster than the commonly used long-term data window, is proposed in this paper, and the stability of the calculated results is significantly improved.
Further, a new scheme for time-domain distance protection that uses the Bergeron model for iteration is proposed in this paper. Compared with the traditional scheme that directly uses the R-L model, the calculation error is significantly reduced. Moreover, the calculation speed and stability and the robustness to the transition resistance are improved. Obviously, compared with the traditional time-domain distance protection scheme, the dead zone for the operation of the proposed protection scheme is much smaller. However, it is noted that the proposed scheme cannot reliably operate when a high-resistance fault occurs at the end of the line. This problem will be further studied in our future work.
References
M. I. Blanco, “The economics of wind energy,” Renewable & Sustainable Energy Reviews, vol. 13, no. 6-7, pp. 1372-1382, Aug.-Sept. 2011. [Baidu Scholar]
Z. Zhuo, N. Zhang, X. Xie et al., “Key technologies and developing challenges of power system with high proportion of renewable energy,” Automation of Electric Power Systems, vol. 45, no. 9, pp. 171-191, Mar. 2021. [Baidu Scholar]
P. B. Eriksen, T. Ackermann, H. Abildgaard et al., “System operation with high wind generation,” IEEE Power and Energy Magazine, vol. 3, no. 6, pp. 65-74, Oct. 2005. [Baidu Scholar]
L. Zhang, T. Ye, Y. Xin et al., “Problems and measures of power grid accommodating large scale wind power,” Proceedings of the CSEE, vol. 30, no. 25, pp. 1-9, Sept. 2010. [Baidu Scholar]
Q. Tu, S. Miao, F. Yao et al., “Forecasting scenario generation for multiple wind farms considering time-series characteristics and spatial-temporal correlation,” Journal of Modern Power Systems and Clean Energy, vol. 9, no. 4, pp. 837-848, Jul. 2021. [Baidu Scholar]
S. Chandrasekar and R. Gokaraju, “Dynamic phasor modeling of type 3 DFIG wind generators (including SSCI phenomenon) for short-circuit calculations,” IEEE Transactions on Power Delivery, vol. 30, no. 2, pp. 887-897, Oct. 2015. [Baidu Scholar]
J. Morren and S. W. H. de Haan, “Ride through of wind turbines with doubly-fed induction generator during a voltage dip,” IEEE Transactions on Energy Conversion, vol. 20, no. 2, pp. 435-441, Jun. 2005. [Baidu Scholar]
D. F. Howard, T. G. Habetler, and R. G. Harley, “Improved sequence network model of wind turbine generators for short-circuit studies,” IEEE Transactions on Energy Conversion, vol. 27, no. 4, pp. 968-977, Dec. 2012. [Baidu Scholar]
E. Muljadi, N. Samaan, V. Gevorgian et al., “Different factors affecting short circuit behavior of a wind power plant,” IEEE Transactions on Industry Applications, vol. 49, no. 1, pp. 284-292, Jan.-Feb. 2013. [Baidu Scholar]
S. A. Saleh, A. S. Aljankawey, R. Meng et al., “Impacts of grounding configurations on responses of ground protective relays for DFIG-based WECSs–Part I: solid ground faults,” IEEE Transactions on Industry Applications, vol. 51, no. 4, pp. 2804-2818, Jul.-Aug. 2015. [Baidu Scholar]
S. A. Saleh, A. S. Aljankawey, R. Meng et al., “Impacts of grounding configurations on responses of ground protective relays for DFIG-based WECSs–Part II: high-impedance ground faults,” in Proceedings of 2015 IEEE/IAS 51st Industrial & Commercial Power Systems Technical Conference (I&CPS), Calgary, Canada, Sept. 2015, pp. 1-9. [Baidu Scholar]
Y. Zheng, T. Wu, F. Hong et al., “Transmission line distance protection under current transformer saturation,” Journal of Modern Power Systems and Clean Energy, vol. 9, no. 1, pp. 68-76, Jan. 2021. [Baidu Scholar]
S. Maihemuti, W. Wang, H. Wang et al., “Voltage security operation region calculation based on improved particle swarm optimization and recursive least square hybrid algorithm,” Journal of Modern Power Systems and Clean Energy, vol. 9, no. 1, pp. 138-147, Jan. 2021. [Baidu Scholar]
C. Zhou, Z. Wang, P. Ju et al., “High-voltage ride through strategy for DFIG considering converter blocking of HVDC system,” Journal of Modern Power Systems and Clean Energy, vol. 8, no. 3, pp. 491-498, May 2020. [Baidu Scholar]
K. Jia, Y. Li, Y. Fang et al., “Transient current similarity based protection for wind farm transmission lines,” Applied Energy, vol. 225, pp. 52-59, May 2018. [Baidu Scholar]
B. Li, J. Liu, X. Wang et al., “Fault studies and distance protection of transmission lines connected to DFIG-based wind farms,” Applied Sciences, vol. 8, no. 4, pp. 562, Apr. 2018. [Baidu Scholar]
A. Han, Z. Zhang, X. Yin et al., “Research on fault characteristic and grid connecting-point protection scheme for wind power generation with doubly-fed induction generator,” Transactions of China Electrotechnical Society, vol. 27, no. 4, pp. 233-239, Apr. 2012. [Baidu Scholar]
A. K. Pradhan and G. Joos, “Adaptive distance relay setting for lines connecting wind farms,” IEEE Transactions on Energy Conversion, vol. 22, no. 1, pp. 206-213, Mar. 2007. [Baidu Scholar]
A. Hooshyar, M. A. Azzouz, and E. F. El-Saadany, “Distance protection of lines connected to induction generator-based wind farms during balanced faults,” IEEE Transactions on Sustainable Energy, vol. 5, no. 4, pp. 1193-1203, Oct. 2014. [Baidu Scholar]
H. Zhang, W. Wang, L. Zhu et al., “An adaptive setting method for distance protection of transmission lines connecting wind farms,” Power System Technology, vol. 33, no. 3, pp. 89-93, Feb. 2009. [Baidu Scholar]
H. Sadegh, “A novel method for adaptive distance protection of transmission line connected to wind farms,” International Journal of Electrical Power & Energy Systems, vol. 43, no. 1, pp. 1376-1382, Apr. 2012. [Baidu Scholar]
T. Wang, F. Li, and S. He, “Factors impacting distance protection for tie line of wind farm and corresponding countermeasures,” Power System Technology, vol. 38, no. 5, pp. 1420-1424, May 2014. [Baidu Scholar]
C. Su,F. Li, and Y. Wu, “An analysis on short-circuit characteristic of wind turbine driven doubly fed induction generator and its impact on relay setting,” Automation of Electric Power Systems, vol. 35, no. 6, pp. 86-91, Mar. 2011. [Baidu Scholar]
M. Khoddam and H. K. Karegar, “Effect of wind turbines equipped with doubly-fed induction generators on distance protection,” in Proceedings of 2011 International Conference on Advanced Power System Automation and Protection, Beijing, China, Oct. 2011, pp. 1349-1353. [Baidu Scholar]
A. Hooshyar, M. A. Azzouz, and E. F. El-Saadany, “Distance protection of lines emanating from full-scale converter-interfaced renewable energy power plants–Part I: problem statement,” IEEE Transactions on Power Delivery, vol. 30, no. 4, pp. 1770-1780, Aug. 2015. [Baidu Scholar]
S. de Rijcke, P. S. Pérez, and J. Driesen, “Impact of wind turbines equipped with doubly-fed induction generators on distance relaying,” in Proceedings of IEEE PES General Meeting, Minneapolis, USA, Jul. 2010, pp. 1-10. [Baidu Scholar]
L. Chen, J. Zhang, J. Du et al., “Applicability of phase-comparison distance protection based on polarized voltage for outgoing transmission line of DFIG-based wind farm,” Electric Power Automation Equipment, vol. 36, no. 9, pp. 74-79, Sept. 2016. [Baidu Scholar]
B. Zhang, J. Zhang, B. Yuan et al., “Impact of wind farm integration on relay protection (6): analysis of distance protection for wind farm outgoing transmission line,” Electric Power Automation Equipment, vol. 33, no. 6, pp. 1-6, Jun. 2013. [Baidu Scholar]
Z. Yang, X. Kong, L. Wang et al., “Distance protection scheme for interconnection line of doubly-fed induction generator based wind farm,” Transactions of China Electrotechnical Society, vol. 31, no. 24, pp. 252-260, Dec. 2016. [Baidu Scholar]
Y. Fan, J. Hou, Q. Yao et al., “Time-domain equation model deviation correction distance protection for cluster wind power transmission line with anti-transient ability,” Electric Power Automation Equipment, vol. 38, no. 1, pp. 10-18, Jan. 2018. [Baidu Scholar]
Y. Chen, M. Wen, X. Yin et al., “Distance protection for transmission lines of DFIG-based wind power integration system,” International Journal of Electrical Power & Energy Systems, vol. 100, pp. 438-448, Sept. 2018. [Baidu Scholar]
Y. Fan and J. Hou, “Time domain distance protection for long distance outgoing line of wind power system based on distributed parameter model,” Power System Protection and Control, vol. 46, no. 19, pp. 26-33, Oct. 2018. [Baidu Scholar]
Q. Yang, “Microprocessor based distance protection,” Ph.D. dissertation, Department of Electrical Engineering and Computer Science, University of New South Wales, Sydney, Australia, 1981. [Baidu Scholar]
X. Kong, Z. Zhang, X. Yin et al., “Study of fault current characteristics of the DFIG considering dynamic response of the RSC,” IEEE Transactions on Energy Conversion, vol. 29, no. 2, pp. 278-287, Jun. 2014. [Baidu Scholar]
J. Ouyang and X. Xiong, “Dynamic behavior of the excitation circuit of a doubly-fed induction generator under a symmetrical voltage drop,” Renewable Energy, vol. 71, pp. 629-638, Nov. 2014. [Baidu Scholar]
B. LI, J. He, W. Chang et al., “Bergeron model based distance protection for long transmission lines,” Automation of Electric Power Systems, vol. 34, no. 23, pp. 52-56, Dec. 2010. [Baidu Scholar]