Abstract
Featuring low communication requirements and high reliability, the voltage droop control method is widely adopted in the voltage source converter based multi-terminal direct current (VSC-MTDC) system for autonomous DC voltage regulation and power-sharing. However, the traditional voltage droop control method with fixed droop gain is criticized for over-limit DC voltage deviation in case of large power disturbances, which can threaten stable operation of the entire VSC-MTDC system. To tackle this problem, this paper proposes an adaptive reference power based voltage droop control method, which changes the reference power to compensate the power deviation for droop-controlled voltage source converters (VSCs). Besides retaining the merits of the traditional voltage droop control method, both DC voltage deviation reduction and power distribution improvement can be achieved by utilizing local information and a specific control factor in the proposed method. Basic principles and key features of the proposed method are described. Detailed analyses on the effects of the control factor on DC voltage deviation and imbalanced power-sharing are discussed, and the selection principle of the control factor is proposed. Finally, the effectiveness of the proposed method is validated by the simulations on a five-terminal VSC based high-voltage direct current (VSC-HVDC) system.
2021.
THE utilization of sustainable energy has become an inevitable approach to achieve net-zero carbon emission. Facing the intermittent of renewable energy like wind or solar power, the DC technique provides a promising solution in renewable energy integration [
To ensure stable operation of the VSC-MTDC system, DC voltage stability must be guaranteed since the DC voltage is regarded as a dominant indicator of power balance in multi-terminal direct current (MTDC) systems [
Regarding the control framework of VSC-MTDC, the voltage droop control method belongs to the primary control, which commonly employs a proportional controller to maintain system stability during large disturbances as fast as possible [
To cope with the limitations of the traditional fixed droop gain based voltage droop control method, many methods have been proposed in the literature. Basically, most of the existing studies focus on the adaptive voltage droop control method, which adaptively changes the droop gains (coefficients) of the droop-controlled VSCs [
Motivated by the aforementioned problems, this paper proposes an adaptive reference power based voltage droop control method for VSC-MTDC systems. The main contributions of this paper are as follows.
1) Without tuning the droop gain, the local power deviation is utilized to compensate the original reference power, which achieves the movement of the DC voltage to its nominal value and reduction of the DC voltage over-limit risk.
2) A control factor is introduced into the proposed method to indicate the degree of compensation for the original reference power, which also realizes different P-V characteristics in different VSCs. The influences of the control factor on DC voltage deviation and imbalanced power-sharing are discussed, and the selection principle of the control factor is proposed.
3) Besides retaining the high reliability of the traditional voltage droop control method, the proposed method continuously adjusts the reference power for restricting the DC voltage deviation and improving the power distribution in the post-disturbance process.
The remainder of this paper is organized as follows. The control structure of a VSC station and the working principle on the traditional voltage droop control method are introduced in Section II. The adaptive reference power based voltage droop control method and the discussion of the control factor are presented in Section III. In Section IV, the simulations on a five-terminal VSC-HVDC system are conducted in PSCAD/EMTDC to validate the effectiveness of the proposed method. Finally, conclusions are presented in Section V.
II. Control Structure of VSC Station and Working Principle of Traditional Voltage Droop Control Method
The intrinsic characteristics of the traditional voltage droop control method are the theoretical foundation of the proposed method. Therefore, the control structure of a VSC station and the working principle of traditional voltage droop control method are described first. For simplicity, this paper adopts the per-unit system and assumes that the direction of the power injected into the DC system is positive.
The schematic diagram of a VSC station is shown in
(1) |

Fig. 1 Schematic diagram of a VSC station.

Fig. 2 Control structure of a VSC station.
where Req, Leq, and Ceq are the equivalent resistance, inductance, and capacitance of the VSC, respectively; id and iq are the d and q components of the current flowing from the AC system to the converter side, respectively; is the angular frequency of the AC system; and are the d and q components of the reference output AC voltage of VSC, respectively; and vd and vq are the d and q components of the AC voltage at PCC, respectively.
The reactive power control class contains the constant reacitve power control and constant AC voltage control. The active power control class contains the constant active power, constant DC voltage, and voltage droop control. Particularly, both constant voltage control and constant power control can be regarded as extreme cases of the voltage droop control method. In other words, the voltage droop control method is a tradeoff between them.
As depicted in
(2) |

Fig. 3 P-V characteristic curves of traditional voltage droop control method.
where and P are the reference and the measured exchanged active power injected into the DC side from the AC system, respectively; and are the reference and measured DC voltages, respectively; and is the droop gain, which is defined as the ratio of the change in active power to the change in DC voltage.
Given that the VSC-MTDC system is an ideal lossless grid, two VSCs (VSC1 and VSC2) adopt the traditional voltage droop control method and no other converters participate in DC voltage control. Since there are no power losses in this VSC-MTDC system, the DC voltages of the two VSCs are identical. As shown in
(3) |
where is the imbalanced power; is the imbalanced power shared by VSCi; is the DC voltage deviation between the operating points before and after disturbances of the VSCi and all the are equal to ; and and are the droop gains of VSC1 and VSC2, respectively. Thus, the shared imbalanced power of each VSC is:
(4) |
According to (4), in an ideal lossless grid, the imbalanced power is shared by droop-controlled converters in proportion to their droop gains. Consequently, the dispatcher can design the droop gain according to the power-sharing with post-disturbance. However, when considering the resistance of the transmission line, DC line voltage drops in the VSC-MTDC system will cause non-uniform variation of the DC bus voltage, which in turn affects the imbalanced power redistribution among droop-controlled converters [
When adopting the voltage droop control method with fixed droop gain (denoted as fixed method), the gap between the measured DC voltage and the reference DC voltage should be smaller when the measured power gets close to the reference power. Therefore, the direct approach to reducing the DC voltage deviation is to adjust the reference power of the setpoint. Furthermore, the adjustment of the reference power can be described as a movement of the P-V droop characteristic curve of the voltage droop control method on the P-V plane. Based on these analyses, changing the reference power adaptively should be an effective approach to achieve the improvement of the VSC-MTDC system with large disturbances.
As illustrated in
(5) |

Fig. 4 P-V characteristics, setpoints, and operating points of proposed method with different compensation factors.
where is the new reference power; is the initial-setting reference power; K is the compensation factor; and is the power deviation, which is defined as:
(6) |
In accordance with the characteristic of the traditional voltage droop control method, the larger DC voltage deviation is, the more imbalanced power needs to be compensated to limit the DC voltage deviation. Therefore, the novel expression of the compensation factor proposed in this paper can be represented as:
(7) |
where is the control factor, which is an important constant that determines the compensation degree and is discussed in detail in Section III-C and D; and is the DC voltage deviation, which can be expressed as:
(8) |
where Vdcn is the nominal DC voltage. Combing (5), (6), and (7), the adaptive reference power can be expressed as:
(9) |

Fig. 5 P-V characteristics, setpoints, and operating points of proposed method and fixed method.
Taking (2), (8), and (9) into consideration, the block diagram of the proposed method is depicted in

Fig. 6 Block diagram of proposed method.
According to (8) and (9), the basic features of the proposed method are described as follows.
1) When a droop-controlled VSC works at the rectifier mode, the DC voltage will decrease as the rectifier power increases. After adopting the proposed method, the reference power Pref will increase when the measured power P is greater than the initial-setting value Pref0, which means the P-V characteristic curve rises for compensating for the DC voltage drop.
2) When a droop-controlled VSC works in the inverter mode, the DC voltage will increase as the inverter power increases. After adopting the proposed method, the reference power Pref will decrease when the measured power P is smaller than the initial-setting value Pref0, which means the P-V characteristic curve drops for compensating for the DC voltage rising.
3) When the absolute value of DC voltage deviation is small enough, the value of the denominator in (9) will be big enough. Therefore, the adjustment value of the reference power will also be small, and vice versa.
4) Assuming the control factors and DC voltage deviations of different VSCs are identical, the VSC with a higher power loading rate will share less imbalanced power.
5) The control factor determines the compensation degree of the original reference power. In general, the control factor is related to the DC voltage deviation and initial-setting reference power. Moreover, different VSCs can regulate their control factors independently to achieve better performance.
In summary, the proposed method can enhance the ability of converters to sustain the DC voltage.
The control factor in (9) plays a significant role in the proposed method. Therefore, the range of the control factor should be discussed in detail.
First of all, the steady-state power of VSC is calculated. Since the input of the proportional-integral (PI) regulator in
(10) |
Apparently, . Besides, one of the most important requirements of the voltage droop control method is to ensure the derivative of the exchanged power to DC voltage deviation is monotonous (negative in this paper). Otherwise, it is impossible for the MTDC system to achieve a new steady state mathematically, which indicates that:
(11) |
Considering the adjustment margin in (5) and avoiding the instability caused by the excessive adjustment, the range of the compensation factor K in (5) should be 0 to 1. Thus, it is reasonable to assume in (10).
If , substituting (10) into (11) yields:
(12) |
If , substituting (10) into (11) yields:
(13) |
Therefore, the range of control factor is:
(14) |
As a conservative condition, it is assumed that . For simplicity and convenience, it is further assumed that is set as the limit of the DC voltage deviation . Therefore, the lower limit of the control factor can be simplified as:
(15) |
where is usually ranged between 5% and 10%.
Moreover, some other conditions should also be satisfied to maintain stable operation of the VSC-MTDC system. For example, the power loading rate of the droop-controlled VSC should be 1 when the DC voltage deviation hits its limit . Therefore, the control factor should meet the following requirement.
(16) |
where S is the nominal capacity of the VSC.
Whereas, (16) is established in the case that the VSC station operates in both inverter and rectifier modes. The range of the control factor is excessive for the VSC that only operates in inverter or rectifier mode. Hence, for the droop-controlled inverter station, the following conditions should be satisfied.
1) When the DC voltage deviation is , the exchanged power of the droop-controlled inverter station is -1.
2) When the DC voltage deviation is , the exchanged power of the droop-controlled inverter station is 0.
Thus, the requirement of control factor is expressed as:
(17) |
Similarly, the requirement of control factor for the droop-controlled rectifier is expressed as:
(18) |
It should be noted that the premise of (16) is:
(19) |
Furthermore, the premise of (17) and (18) is:
(20) |
When (19) and (20) are not satisfied, the upper limit of the control factor is positive infinity.
In summary, the ranges of the control factor should satisfy (15) and the requirements of loading ratios simultaneously. The exact value of the control factor can be chosen flexibly based on the above discussion. It can be tuned according to the converter capacity and the actual grid topology.
According to (11), if , then , which means that the proposed method degenerates to the fixed method. In this part, a simple case is studied to demonstrate the influence of the control factor on the proposed method. The basic parameters of this simple case are listed in
Description | Value (p.u.) |
---|---|
Initial-setting reference power | -0.3 |
Reference DC voltage | 1 |
Droop gain | 10 |
Limit of voltage deviation | 0.05 |
Assuming that the VSC station only operates in the inverter mode and taking the parameters listed in

Fig. 7 P-V characteristic curves of proposed method with different control factors. (a) P-V characteristic curves at a given setpoint. (b) Influence of control factors on exchanged power.
The influence of the control factor on exchanged power with identical DC voltage deviation is illustrated in
To validate the proposed method, simulations of a ±200 kV five-terminal VSC-HVDC system are investigated using PSCAD/EMTDC. As shown in

Fig. 8 Diagram of a five-terminal VSC-HVDC system.
Description | Value |
---|---|
Nominal capacity of VSC1 | 200 MVA |
Nominal capacity of VSC2 | 600 MVA |
Nominal capacity of VSC3 | 400 MVA |
Nominal capacity of VSC4 | 600 MVA |
Nominal capacity of VSC5 | 600 MVA |
Initial-setting reference power of VSC1 | -60 MW |
Initial-setting reference power of VSC2 | -180 MW |
Initial-setting reference power of VSC3 | -120 MW |
Droop gain of VSC1, VSC2, and VSC3 | 10 p.u. |
Limit of voltage deviation (δmax) | 5% |
Control factor of VSC1 (α1) | 0.15 |
Control factor of VSC2 (α2) | 0.04 |
Control factor of VSC3 (α3) | 0.08 |
Valve-side AC voltage | 230 kV |
Nominal DC voltage | ±200 kV |
Proportional gain of outer-loop PI controller | 2 |
Integral time constant of outer-loop PI controller | 0.1 s |
Proportional gain of inner-loop PI controller | 0.6 |
Integral time constant of inner-loop PI controller | 0.01 s |
As discussed in the previous section, smaller control factors result in VSCs sharing more imbalanced power in case of power disturbances. Consequently, considering the capacity of each VSC station, the control factor of VSC1 should be large and the control factor of VSC2 should be small. According to (15), (17), and the parameters in
The large power fluctuation of renewable energy and the VSC station outage are common disturbances to the VSC-MTDC system.
Since this paper focuses on the regulation performance of DC voltage and exchanged power, the complicated fault process is omitted and the ideal DC circuit breaker that can isolate DC faults immediately is assumed. Therefore, the power step and VSC station outage are selected as the disturbances in this case and the detailed description is presented as follows.
1) Disturbance F1: at 2.2 s, the output power of wind farm 1 steps from 200 MW to 500 MW, and the output power of wind farm 2 steps from 260 MW to 460 MW.
2) Disturbance F2: at 3.2 s, VSC1 is disconnected from the system, which is depicted at F in
The comparison between the fixed method and the proposed method is studied. The simulation results of DC voltage and exchanged power of the droop-controlled VSCs during the above two disturbances are illustrated in

Fig. 9 Simulations of DC voltage with proposed method and fixed method.

Fig. 10 Simulations of exchanged power with proposed method and fixed method.
Situation | Method | Loading ratio (%) | ||
---|---|---|---|---|
VSC1 | VSC2 | VSC3 | ||
Before F1 | Proposed | 31.68 | 27.08 | 31.12 |
Fixed | 31.57 | 27.18 | 31.02 | |
After F1 and before F2 | Proposed | 67.92 | 64.83 | 71.23 |
Fixed | 73.48 | 63.17 | 71.25 | |
After F2 | Proposed | 0.00 | 79.38 | 82.39 |
Fixed | 0.00 | 77.46 | 85.78 |
The DC voltages and exchanged power of all VSCs with these two methods are almost the same before 2.2 s. It indicates that the proposed method has a similar performance with the fixed method in the case of a small absolute value of DC voltage deviation.
When F1 occurs, the output power of the windfarms steps from 460 MW to 960 MW, which raises the total power injected into the VSC-MTDC system. As the DC voltage rises, the droop-controlled VSCs start compensating for the imbalanced power after F1.
The DC voltage of VSC1 with fixed method exceeds the safety limit during the dynamic process. On the contrary, the DC voltages of droop-controlled VSCs with the proposed method are within the specified range and have lower DC voltage deviations compared with those of the VSCs adopting the fixed method.
The results in
At 3.2 s, VSC1 outage occurs and the DC circuit breaker activates quickly. After F2, the exchanged power of VSC1 decreases to zero, which indicates the reduction in power absorbed from the entire VSC-MTDC system. Consequently, the positive power mismatch causes the increase of DC voltage.
As shown in

Fig. 11 Simulations of reference power of droop-controlled VSCs with proposed method.
In summary, compared with the fixed method, the proposed method maintains the DC voltages of droop-controlled VSCs within their safety limits during large power variation and VSC outage. Besides, it alleviates the improper distribution of the imbalanced power.
In the light of the inherent characteristics of the traditional voltage droop control, the adaptive reference power based voltage droop control method is proposed. The proposed method revises the reference power to compensate the power deviation for the droop-controlled VSC to reduce the DC deviation of the VSC-MTDC system. The compensation degree is determined by the control factor, DC voltage deviation, and initial-setting reference power. Based on P-V characteristic curves, the intrinsic principle and basic features of the proposed method are described. Furthermore, the selection principle of the control factors is studied and detailed analyses regarding the effects of the control factor on DC voltage deviation and exchanged power are discussed. Besides retaining the high reliability of the traditional voltage droop control method, the proposed method restricts the DC voltage of droop-controlled VSCs within the safety limit and adjusts the DC voltage to its rated value. Moreover, the proposed method rationalizes the imbalanced power redistribution and realizes the diversity of power-sharing among VSCs in post-disturbance process by setting different control factors. Finally, a case study of a five-terminal VSC-HVDC system integrated with two wind farms validates the effectiveness of the proposed method. Future studies will focus on the integration of optimal dispatch with the proposed method for VSC-MTDC systems.
References
N. R. Watson and J. D. Watson, “An overview of HVDC technology,” Energies, vol. 13, no. 17, p. 4342, Aug. 2020. [Baidu Scholar]
B. Yang, L. Jiang, T. Yu et al., “Passive control design for multi-terminal VSC-HVDC systems via energy shaping,” International Journal of Electrical Power & Energy Systems, vol. 98, pp. 496-508, Jun. 2018. [Baidu Scholar]
Y. Zhang, J. Ravishankar, J. Fletcher et al., “Review of modular multilevel converter based multi-terminal HVDC systems for offshore wind power transmission,” Renewable and Sustainable Energy Reviews, vol. 61, pp. 572-586, Aug. 2016. [Baidu Scholar]
E. Karami, G. B. Gharehpetian, H. Mohammadpour et al., “Generalised representation of multi-terminal VSC-HVDC systems for AC-DC power flow studies,” IET Energy Systems Integration, vol. 2, no. 1, pp. 50-58, Mar. 2020. [Baidu Scholar]
B. Li, Q. Li, Y. Wang et al., “A novel method to determine droop coefficients of DC voltage control for VSC-MTDC system,” IEEE Transactions on Power Delivery, vol. 35, no. 5, pp. 2196-2211, Oct. 2020. [Baidu Scholar]
S. Khan and S. Bhowmick, “A generalized power-flow model of VSC-based hybrid AC-DC systems integrated with offshore wind farms,” IEEE Transactions on Sustainable Energy, vol. 10, no. 4, pp. 1775-1783, Oct. 2019. [Baidu Scholar]
Z. Yuan, Y. Wang, Y. Yi et al., “Fast linear power flow algorithm for the study of steady-state performance of DC grid,” IEEE Transactions on Power Systems, vol. 34, no. 6, pp. 4240-4248, Nov. 2019. [Baidu Scholar]
J. A. Ansari, C. Liu, and S. A. Khan, “MMC based MTDC grids: a detailed review on issues and challenges for operation, control and protection schemes,” IEEE Access, vol. 8, pp. 168154-168165, Jun. 2020. [Baidu Scholar]
H. Rao, “Architecture of Nan’ao multi-terminal VSC-HVDC system and its multi-functional control,” CSEE Journal of Power and Energy Systems, vol. 1, no. 1, pp. 9-18, Mar. 2015. [Baidu Scholar]
H. Pang and X. Wei, “Research on key technology and equipment for Zhangbei 500 kV DC grid,” in Proceedings of 2018 International Power Electronics Conference, Niigata, Japan, May 2018, pp. 2343-2351. [Baidu Scholar]
Z. Liu and X. Guo, “Control strategy optimization of voltage source converter connected to various types of AC systems,” Journal of Modern Power Systems and Clean Energy, vol. 9, no. 1, pp. 77-84, Jan. 2021. [Baidu Scholar]
K. Sun, H. Xiao, J. Pan et al., “Cross-seam hybrid MTDC system for integration and delivery of large-scale renewable energy,” Journal of Modern Power Systems and Clean Energy, vol. 9, no. 6, pp. 1352-1362, Nov. 2021. [Baidu Scholar]
T. K. Vrana, J. Beerten, R. Belmans et al., “A classification of DC node voltage control methods for HVDC grids,” Electric Power Systems Research, vol. 103, pp. 137-144, Oct. 2013. [Baidu Scholar]
J. Beerten, S. Cole, and R. Belmans, “Modeling of multi-terminal VSC HVDC systems with distributed DC voltage control,” IEEE Transactions on Power Systems, vol. 29, no. 1, pp. 34-42, Jan. 2014. [Baidu Scholar]
Z. Wang, J. He, Y. Xu et al., “Distributed control of VSC-MTDC systems considering tradeoff between voltage regulation and power sharing,” IEEE Transactions on Power Systems, vol. 35, no. 3, pp. 1812-1821, May 2020. [Baidu Scholar]
H. Li, C. Liu, G. Li et al., “An enhanced DC voltage droop-control for the VSC-HVDC grid,” IEEE Transactions on Power Systems, vol. 32, no. 2, pp. 1520-1527, Mar. 2017. [Baidu Scholar]
R. H. Renner and D. van Hertem, “Potential of using DC voltage restoration reserve for HVDC grids,” Electric Power Systems Research, vol. 134, pp. 167-175, May 2016. [Baidu Scholar]
Y. Wang, B. Li, Z. Zhou et al., “DC voltage deviation-dependent voltage droop control method for VSC-MTDC systems under large disturbances,” IET Renewable Power Generation, vol. 14, no. 5, pp. 891-896, Mar. 2020. [Baidu Scholar]
X. Chen, L. Wang, H. Sun et al., “Fuzzy logic based adaptive droop control in multiterminal HVDC for wind power integration,” IEEE Transactions on Energy Conversion, vol. 32, no. 3, pp. 1200-1208, Sept. 2017. [Baidu Scholar]
Y. Wang, W. Wen, C. Wang et al., “Adaptive voltage droop method of multiterminal VSC-HVDC systems for DC voltage deviation and power sharing,” IEEE Transactions on Power Delivery, vol. 34, no. 1, pp. 169-176, Feb. 2019. [Baidu Scholar]
N. R. Chaudhuri and B. Chaudhuri, “Adaptive droop control for effective power sharing in multi-terminal DC (MTDC) grids,” IEEE Transactions on Power Systems, vol. 28, no. 1, pp. 21-29, Feb. 2013. [Baidu Scholar]
A. Moawwad, E. F. El-Saadany, and M. S. E. Moursi, “Dynamic security-constrained automatic generation control (AGC) of integrated AC/DC power networks,” IEEE Transactions on Power Systems, vol. 33, no. 4, pp. 3875-3885, Jul. 2018. [Baidu Scholar]
M. N. Ambia, K. Meng, W. Xiao et al., “Adaptive droop control of multi-terminal HVDC network for frequency regulation and power sharing,” IEEE Transactions on Power Systems, vol. 36, no. 1, pp. 566-578, Jan. 2021. [Baidu Scholar]
S. Song, R. A. McCann, and G. Jang, “Cost-based adaptive droop control strategy for VSC-MTDC system,” IEEE Transactions on Power Systems, vol. 36, no. 1, pp. 659-669, Jan. 2021. [Baidu Scholar]
R. Wang, Q. Sun, W. Hu et al., “Stability-oriented droop coefficients region identification for inverters within weak grid: an impedance-based approach,” IEEE Transactions on Systems, Man, and Cybernetics: Systems, vol. 51, no. 4, pp. 2258-2268, Apr. 2021. [Baidu Scholar]
K. Shinoda, A. Benchaib, J. Dai et al., “Over- and under-voltage containment reserves for droop-based primary voltage control of MTDC grids,” IEEE Transactions on Power Delivery. doi: 10.1109/TPWRD.2021.3054183 [Baidu Scholar]
Y. Zhang, X. Meng, A. M. Shotorbani et al., “Minimization of AC-DC grid transmission loss and DC voltage deviation using adaptive droop control and improved AC-DC power flow algorithm,” IEEE Transactions on Power Systems, vol. 36, no. 1, pp. 744-756, Jan. 2021. [Baidu Scholar]
T. M. Haileselassie and K. Uhlen, “Impact of DC line voltage drops on power flow of MTDC using droop control,” IEEE Transactions on Power Systems, vol. 27, no. 3, pp. 1441-1449, Aug. 2012. [Baidu Scholar]
A. Marten, F. Sass, and D. Westermann, “Continuous P-V-characteristic parameterization for multi-terminal HVDC systems,” IEEE Transactions on Power Delivery, vol. 32, no. 4, pp. 1665-1673, Aug. 2017. [Baidu Scholar]