Journal of Modern Power Systems and Clean Energy

ISSN 2196-5625 CN 32-1884/TK

网刊加载中。。。

使用Chrome浏览器效果最佳,继续浏览,你可能不会看到最佳的展示效果,

确定继续浏览么?

复制成功,请在其他浏览器进行阅读

Line Aging Assessment in Distribution Network Based on Topology Verification and Parameter Estimation  PDF

  • Zhi Wu 1 (Member, IEEE)
  • Huan Long 1
  • Chang Chen 2
the School of Electrical Engineering, Southeast University, NanjingChina; Maintenance Branch Company, State Grid Jiangsu Electric Power Company Ltd., NanjingChina

Updated:2022-11-20

DOI:10.35833/MPCE.2021.000165

  • Full Text
  • Figs & Tabs
  • References
  • Authors
  • About
CITE
OUTLINE

Abstract

The aging of lines has a strong impact on the economy and safety of the distribution network. This paper proposes a novel approach to conduct line aging assessment in the distribution network based on topology verification and parameter estimation. In topology verification, the set of alternative topologies is firstly generated based on the switching lines. The best-matched topology is determined by comparing the difference between the actual measurement data and calculated voltage magnitude curves among the alternative topologies. Then, a novel parameter estimation approach is proposed to estimate the actual line parameters based on the measured active power, reactive power, and voltage magnitude data. It includes two stages, i.e., the fixed-step aging parameter (FSAP) iteration, and specialized Newton-Raphson (SNR) iteration. The theoretical line parameters of the best-matched topology are taken as a warm start of FSAP, and the fitted result of FSAP is further renewed by the SNR. Based on the deviation between the renewed and theoretical line parameters, the aging severity risk level of each line is finally quantified through the risk assessment technology. Numerous experiments on the modified IEEE 33-bus and 123-bus systems demonstrate that the proposed approach can effectively conduct line aging assessment in the distribution network.

I. INTRODUCTION

THE lines in the power grid have a limited service life and inevitable aging due to various factors such as hydrolysis, oxidation, and pyrolysis [

1]. The aging of lines has a harmful impact on the distribution network, which can be reflected in system reliability and state estimation. If the aging lines in the distribution network are not replaced in time, their insulation layer may be destroyed during power transmission. It seriously affects the normal power supply and causes substantial economic losses [2]-[4]. Thus, line aging assessment and localization in the distribution network are essential to enhance the system reliability and ensure the economic benefit of electric power companies.

References [

5]-[9] on line aging assessment mainly focus on the modeling and the influencing factor. In [7], a 10 kV distribution line aging mathematical model is established. The impedance changes of various lines with different operating years are fitted based on actual measurement data. The equivalent resistance method is used to analyze the effect of line aging on the power loss in the distribution network. In [8], several long-term operating and aging conductors are taken as the samples. Time-temperature experiments are conducted to evaluate the current carrying capacity and resistivity. The deviation degree of line parameters can be used to measure the aging degree of lines. In [10], a novel methodology is proposed for spatial analysis of thermal aging of overhead transmission conductors, which could be performed at three different levels: point, line, and area. In [11], a novel method is proposed to calculate the aging failure probability of power transmission lines based on the dynamic heat balance equation and Weibull distribution. However, the experiments of the above modeling methods are complicated and time-consuming, and many actual environmental impact factors are ignored. Moreover, since the line aging assessment is only conducted for individual lines, these methods fail to locate the aging lines in the actual distribution network.

Thus, to deal with the actual situation, the actual information of the grid topology and line parameters is the premise of locating the aging lines in the distribution network. It is noted that the topology of the distribution network is usually changed through the switching lines to optimize the network operation [

12]. It brings great difficulties in obtaining accurate topology information. Fortunately, with the development of the smart grid, massive operation data are continuously generated, which provide a basis to achieve the actual topology and line parameters.

Currently, the actual topology can be achieved based on topology verification [

13]-[16] or topology identification [17]-[20]. In topology verification, the existing line infrastructure and the theoretical line parameters can be obtained. The actual topology is determined based on alternative operating structures and the actual operating measurement data. In [13], a meter placement strategy is developed to allow distribution system operators to deploy only a few real-time meters, ensuring unique recovery of the true distribution network topology in real time. In [14], a voting-based topology detection method is presented, working with active power, reactive power, voltage magnitude, and voltage phase angle data. In [15], a statistical learning framework is put forth for verifying grid structures using active power, reactive power, and non-synchronized voltage angle data. In [16], a sensor placement strategy is proposed to identify the energized grid topology by exploiting real-time active power, reactive power, and voltage magnitude data collected at partial buses. Different from the topology verification, the task of topology identification is to find both the line connections and line parameters. In [17], the error-in-variables model in a maximum-likelihood estimation framework for joint line parameter and topology estimation is proposed. The PaToPa approach uses a full set of active and reactive power, voltage magnitude, and voltage phase angle data to estimate the parameters. In [18], a two-step framework is developed to identify the topology and estimate line parameters with the active power, reactive power, and voltage magnitude data. The specialized Newton-Raphson (SNR) is proposed to use the pseudo power calculation without the voltage phase angle data to estimate the line parameters. In [19], smart inverters are employed to perturb the distribution network to actively infer its topology and estimate line parameters. In [20], a mixed-integer linear programming method is employed based on McCormick relaxation for the topology identification of distribution network using inverter probing.

The above topology identification methods [

17]-[20] not only recover the actual topology structure, but also estimate line parameters. However, they need the voltage angle data or require high measurement accuracy, which causes great measurement costs. In most cases, the theoretical topology profile can be obtained. Thus, the topology verification without voltage angle measurement data is considered. Since the SNR [18] is sensitive to the voltage magnitude measurement error, it is easy to be trapped in the non-convergence problem. The fixed-step aging parameter (FSAP) algorithm is proposed in this paper to estimate the line parameters, which can be the initial value of SNR to improve its robustness of the measurement noise.

After topology verification, it is also a key point to measure the aging degree of all lines in the distribution network to locate the specific aging line and send the aging warning. In this paper, the risk assessment technology of the distribution network is employed to measure the line aging risk severity level. The risk assessment has been gradually applied to various power industry areas, mainly including operational risk monitoring, equipment management, etc. [

21]-[24]. In [22], the risk assessment technology is utilized to quantify the stability degree of power system under hidden faults and cascading faults. In [23], a hierarchical risk assessment method is introduced to properly consider the impacts of active distribution networks on the risk analysis of the transmission system. The values of line parameters can directly reflect the impact of aging lines [8]. Thus, the risk assessment is suitable for line aging assessment to locate the aging lines based on the reasonable severity utility function.

In this paper, a novel approach for line aging assessment is proposed, which consists of three parts, i.e., topology verification, parameter estimation, and line aging assessment. The alternative topologies are generated based on the different connections of switching lines. Based on voltage magnitude and power injection data, the best-matched topology is selected by comparing the actual voltage magnitude curves with the calculated ones of the alternative topologies. The theoretical line parameters of the best-matched topology are taken as a warm start of line parameter estimation. The line parameters are renewed to best fit the actual measurement data based on the proposed FSAP-SNR iteration method, which reduces the high requirements of voltage magnitude measurement of SNR in [

18]. To further assess the aging lines, the aging severity risk level of each line is quantified based on the deviation between the renewed and theoretical line parameters. The main contributions of this paper can be concluded as follows.

1) The framework of line aging assessment in the distribution network is proposed.

2) A new parameter estimation approach, FSAP-SNR iteration, is proposed, which only requires the voltage magnitude and active and reactive power measurement data, and is robust for the measurement noise.

3) A severity utility function based on the admittance is developed for line aging assessment.

The remainder of this paper is as follows. Section II introduces the structure and details of the proposed approach. Section III presents the case study by using the proposed approach based on the modified IEEE 33-bus and IEEE 123-bus systems. The conclusion and future work are given in Section IV.

II. Structure and Details of Proposed Approach

In this section, the structure and details of the proposed approach are presented, and the details of each part are described later.

A. Structure of Proposed Approach

The proposed line aging assessment approach in the distribution network is composed of topology verification, parameter estimation, and line aging assessment, as presented in Fig. 1. In the stage of topology verification, the alternative network topology set is firstly generated based on the switching lines. The best-matched topology is then selected based on the difference of actual and calculated voltage magnitudes. In the stage of parameter estimation, the actual line parameters of the best-matched topology are estimated based on the proposed FSAP-SNR iteration. In the stage of line aging assessment, the aging severity risk level of each line is assessed based on the proposed severity utility function by comparing the deviation of the estimated and theoretical line parameters. The aging lines are finally detected based on the values of the severity utility function.

Fig. 1  Flowchart of proposed line aging assessment approach.

B. Topology Verification

The purpose of topology verification is to determine the best-matched topology among different possible topologies by minimizing the difference between the actual and calculated voltage magnitudes. A pseudo-code of the topology verification algorithm is provided in Algorithm 1.

Assume that a radial distribution grid with Nb buses can be admitted to operate with NGT alternative grid topologies due to the different connected switching lines. The theoretical line parameter profile Φ includes conductance and susceptance. The measured data over T time instances include the voltage magnitude Va={Vta, t=1, 2, , T}, active power injection Pa={Pta, t=1, 2, , T}, and reactive power injection, Qa={Qta, t=1, 2, , T}. In the nth alternative grid topology, the calculated voltage magnitude, Vnc={Vt,nc, t=1, 2, , T}, is obtained by power flow calculation f(·) (line 2 to line 4). Considering that the fluctuation degree of voltage magnitude is mainly related to the node injection and grid topology, the smallest difference between Va and Vnc can infer the best-matched topology. By comparing the similarity of fluctuation of Va and Vnc at the buses in Ψn, the best-matched topology Ω' is obtained, which is considered as the actual topology (line 5 to line 8).

Algorithm 1  : topology verification

Input: given datasets Va, Pa, Qa, Φ, Ωn, and Ψn, n=1, 2, , NGT

Output: best-matched grid topology Ω'

1:

for n1 to NGT do

2:

  for t1 to T do

3:

   Vt,nc=f(Ωn,Φ,Pta,Qta)

4:

  end for

5:

ρ(n)=11+1TNnt=1Tk=1Nn[(Vt,n,ψH,n,kc-Vt,n,ψE,n,kc)-(Vt,n,ψH,n,ka-Vt,n,ψE,n,ka)]2

6:

end for

7:

Ω'=Ωargmax(ρ)

8:

return Ω'

C. Parameter Estimation

In order to further detect and locate the aging lines in the best-matched topology Ω', the actual line parameter profile of the topology Ω' is estimated based on the measurement data Va, Pa, and Qa. This paper proposes a novel parameter estimation approach, FSAP-SNR, which is robust to the measurement noise without the information of voltage phase angle. It should be noted that the FSAP algorithm renews the line parameters by the fixed step, which is suitable for the small distribution network. In large-scale distribution network, the SNR algorithm is utilized to further renew the parameters based on the result of FSAP. The flowchart of parameter estimation is shown in Fig. 2.

Fig. 2  Flowchart of parameter estimation.

1) FSAP

The FSAP algorithm is a parameter estimation algorithm with the fixed iteration step. Considering that the voltage magnitude measurement error εv is usually smaller than the load measurement error εpq in the actual distribution system, the FSAP algorithm selects voltage magnitude as the iterative convergence condition to guarantee the robustness. A pseudo-code of the FSAP algorithm is provided in Algorithm 2.

Algorithm 2  : FSAP

Input: given dataset Va, Pa, Qa, Φ={gl, bl} (lΩ'), Ω', α, β, and σ

Output: best estimated ĝ and b̂

1:

Δgl=αglsgn(gla-gl),Δbl=βblsgn(bla-bl)

2:

while ΔVσ do

3:

ĝl=ĝl+Δgl,b̂l=b̂l+Δbl

4:

  for t1 to T do

5:

   Vtc=f(Ω', ĝ, b̂ ,Pta, Qta)

6:

  end for

7:

ΔV=1TNbt=1Ti=1NbVt,ic-Vt,ia

8:

end while

9:

return ĝ and b̂

Let g𝓁+jb𝓁 and g𝓁a+jb𝓁a be the theoretical and actual admittance of the 𝓁th line (𝓁=1, 2, , N𝓁), respectively. Renew g𝓁 and b𝓁 based on the corresponding Δg𝓁 and Δb𝓁, as shown in line 1 in Algorithm 2. The power flow calculation f(·) is then employed to calculate the voltage magnitudes Vc of all buses based on the topology Ω', renewed line parameters {ĝ𝓁, b̂𝓁}, Pa, and Qa. The sum of voltage magnitude differences ΔV of all buses over T time slots is compared with the pre-setting threshold σ. When ΔV is smaller than σ, the corresponding ĝl and b̂l are considered as the best estimates.

Based on Algorithm 2, it is clear that the iterative direction of each line, sgn(g𝓁a-g𝓁) and sgn(b𝓁a-b𝓁), are essential for the performance of estimation.

Since the value of the resistance inevitably increases in the aging lines and the values of the reactance of lines are small, sgn(g𝓁a-g𝓁) and sgn(b𝓁a-b𝓁) can be obtained by the relationship between resistance and reactance.

It is assumed that the theoretical and actual impedances of the th line (𝓁Ω') satisfy r𝓁a=λ𝓁r𝓁 (λ𝓁>1) and x𝓁a=x𝓁. The difference between g𝓁(b𝓁) and gla(bla) is given in (1) and (2).

g𝓁a-g𝓁=Re1r𝓁+jx𝓁-Re1r𝓁a+jx𝓁a=r𝓁(λ𝓁-1)(x𝓁2-λ𝓁r𝓁2)(λ𝓁2r𝓁2+x𝓁2)(r𝓁2+x𝓁2) (1)
b𝓁a-b𝓁=Im1r𝓁+jx𝓁-Im1r𝓁a+jx𝓁a=x𝓁r𝓁2(λ𝓁2-1)(λ𝓁2r𝓁2+x𝓁2)(r𝓁2+x𝓁2) (2)

In (2), it is obvious that sgn(b𝓁a-b𝓁)=1 due to λ𝓁>1. In (1), three conditions can be discussed as follows.

1) If x𝓁r𝓁, then sgn(g𝓁a-g𝓁)=-1.

2) If x𝓁>r𝓁 and 1<λ𝓁<xl2/rl2, then sgn(g𝓁a-g𝓁)=1.

3) If x𝓁>r𝓁 and λ𝓁>xl2/rl2, then sgn(g𝓁a-g𝓁)=-1.

2) SNR Iteration

Since FSAP is a parameter estimation algorithm with fixed iterative step size, it is difficult to select the suitable iterative step size in large-scale distribution network. The SNR algorithm proposed in [

18], which is an iteration approach with variable step size, is used to further renew the line parameters based on the results of FSAP. The data requirement of SNR is the same as that of FSAP, including voltage magnitude and active/reactive power injection data.

A pseudo-code of SNR is provided in Algorithm 3. Since the voltage angle measurement is unavailable, the SNR first utilizes the pseudo-power flow calculation to estimate the voltage phase angle data in [

18]. In the pseudo-power flow calculation, all the buses (except reference bus) are regarded as PQ nodes. The missing voltage phase angle Θ are estimated based on Pa, Qa, ĝ', and b̂' through the pseudo-power flow calculation pf(). The initial ĝ' and b̂' come from the results of FSAP.

Then, ĝ' and b̂' are updated according to (3):

Δg'Δb'ΔΘ'=PgQgPbQbPΘQΘΔPΔQ=ADBECFΔPΔQ (3)

where † represents generalized inverse. The partitioned matrices A, B, D, and E are the power-branch partitioned matrices. C and F are the power-angle partitioned matrices. The details of partitioned matrices and the generalized inverse of Jacobian matrix calculation based on multiple samples can be referred in [

18].

Algorithm 3  : SNR

Input: given dataset Va, Pa, Qa, Ω', ĝ, b̂, and φ2

Output: best-estimated ĝ' and b̂'

1:

ĝ'=ĝ, b̂'=b̂

2:

while ΔSφ2 do

3:

  Θ=pf(Ω', ĝ', b̂', Pa, Qa)

4:

  Δg'Δb'ΔΘ'=ADBECFΔPΔQ

5:

  ĝ'b̂'=ĝ'b̂'+Δg'Δb'

6:

  ΔS=1TNbi=1TNb(ΔPi2+ΔQi2)

7:

end while

8:

return ĝ' and b̂'

The convergence criterion of the SNR is the sum of squares of the deviation between the actual and calculated values of the load power smaller than the pre-setting threshold φ2.

It should be noted that the SNR is sensitive to the voltage magnitude measurement data. If SNR is employed alone based on the theoretical line parameter profile, the SNR may suffer non-convergence when εv is large. The estimated results of FSAP provide a good initial solution for SNR to benefit its convergence. Thus, the FSAP can be conducted alone, which is suitable for the small-scale distribution network, and the FSAP-SNR is preferred in large-scale distribution network.

Significantly, the step size of SNR can also provide an alternative choice for FSAP to guarantee its convergence performance. To simultaneously conduct the FSAP and SNR based on the initial theoretical line parameters, the step size of FSAP is determined by min{Δg,Δg'} and min{Δb,Δb'} in each iteration.

D. Aging Line Risk Assessment

In this subsection, the aging severity risk level of each line is quantified to assess the aging lines in the distribution network. The aging lines with obsolete equipment can easily cause grid failures and affect the stable operation and economic benefits of the distribution network, which is reflected in the variation of line parameters. Two risk indexes are constructed, i.e., the conductance offset δg𝓁, and the susceptance offset δb𝓁, in the topology Ω', which significantly impacts the aging degree of each line , as expressed in (4).

δg𝓁=ĝ𝓁-g𝓁 /g𝓁δb𝓁=b̂𝓁-b𝓁 /b𝓁 (4)

In order to measure the aging severity risk level of each line , the severity utility function is utilized as (5), which represents that the degree of abnormity severity increases with the sum of δgl and δbl.

S(𝓁)=δg𝓁+δb𝓁 (5)

III. Case Study

The performance of the proposed approach, including topology verification, parameter estimation, and line aging assessment, is validated in the modified IEEE 33-bus and IEEE 123-bus systems in this section.

A. Data Description

The topology structures of modified IEEE 33-bus and IEEE 123-bus systems with 10 and 14 switching lines, are illustrated in Fig. 3 and Fig. 4, respectively.

Fig. 3  Topology structure of modified IEEE 33-bus system.

Fig. 4  Topology structure of modified IEEE 123-bus system.

To simulate aging of lines, the unit resistance of the aged conductors is increased by 4%-14% compared with the new ones in the IEEE 33-bus and 123-bus systems based on [

8]. Thus, λ𝓁 is randomly set to be 1.04-1.14 for line . In this paper, the active and reactive load profiles for power consumers sampled per 5 min are collected from Tianjin Electric Power Company in China on March 1, 2019. The voltage magnitude is obtained through power flow calculation based on the above load profiles and simulated aging line parameters.

Furthermore, to simulate the measurement error in the actual distribution network, the measurement noise of the load and voltage magnitude profiles are modeled by zero-mean Gaussian with a 3-sigma deviation matching εpq and εv of the original values, respectively. Take the modified IEEE 33-bus system as an example. The value of λ𝓁 is set to be 1.14. The relative errors between g𝓁a and g𝓁b, and b𝓁a and b𝓁b are shown in Fig. 5(a). εpq and εv are set to be 5% and 0.5%, respectively, as an example. The relative errors of loads and voltages between the values with measurement noise are presented in Fig. 5(b) and (c), respectively.

Fig. 5  Relative errors of line parameters, load, and voltage magnitude. (a) Line parameters. (b) Load. (c) Voltage magnitude.

B. Line Aging Assessment on Modified IEEE 33-bus System

1) Topology Verification

The accuracy of topology verification, αTV, is evaluated by:

αTV=NcNGT×100% (6)

Based on the switching lines, the modified IEEE 33-bus system in Fig. 3 has 87 alternative topologies. The switching lines (1), (3), (6), (8), and (10) in Fig. 3 are set to be connected, and the rest of the switching lines to be disconnected, and this topology is assumed to be the actual topology Ω'. The parameters are set to be εpq=5%, εv=0.5%, and λ𝓁=1.14. The sampling frequency Ts is set to be 15 min. In this case, ρ of each alternative topology structure is depicted in Fig. 6. In Fig. 6, each circle represents ρ of the corresponding alternative topology structure. It is clear that the 1st topology structure with the largest ρ is regarded as the best-matched topology.

Fig. 6  ρ of each alternative topology structure in modified IEEE 33-bus system.

The sensitivity analysis of the effects of εpq, εv, and λ𝓁 on αTV is also conducted. In this paper, the default settings of topology verification are εpq=5%, εv=0.5%, λ𝓁=1.14, and Ts=15 min. The result of sensitivity analysis with varying settings is depicted in Fig. 7. When εpq is less than 10%, αTV is stable and more than 90%. Once εpq exceeds 10%, αTV drops rapidly. Compared with the effect of εpq on αTV, εv within the normal measurement error range has a more obvious impact on αTV. The smaller εv is, the higher αTV will be. λ𝓁 changes from 1.04 to 1.36 with the step size of 0.04, and αTV also decreases accordingly.

Fig. 7  Result of sensitivity analysis with varying settings. (a) εpq. (b) εv. (c) λ𝓁.

2) Parameter Estimation

The validity of FSAP and FSAP-SNR is evaluated by the mean absolute percentage error (MAPE) of conductance g and susceptance b, as shown in (7) and (8), respectively.

MAPE(g)=1N𝓁𝓁Ω'ĝ𝓁-g𝓁ag𝓁a×100% (7)
MAPE(b)=1N𝓁𝓁Ω'b̂𝓁-b𝓁ab𝓁a×100% (8)

The settings of parameter estimation are given as εpq=5%, εv=0.5%, λ𝓁=1.14, TN=10, α=0.1, β=0.22, and Ts=15 min. The objective function error in each iteration is presented in Fig. 8. The FSAP-SNR takes 55 iterations until convergence, and the final values of MAPE(g) and MAPE(b) are 2.344% and 3.212%, respectively. The best estimates and relative error between the renewed and actual values of line parameters of each line are shown in Fig. 9.

Fig. 8  Objective function error in each iteration.

Fig. 9  Best estimates and relative error between renewed and actual values of line parameters of each line in modified IEEE 33-bus system. (a) Conductance. (b) Susceptance. (c) Relative error.

In order to further verify the validity of the proposed approach for parameter estimation in this paper, the comparison experiments of FSAP, FSAP-SNR, and SNR are conducted with varying values of εpq, which are set to be 0.5%, 1.0%, 3.0%, and 5.0%, respectively. The result is presented in Table I, where the SNR algorithm based on the initial parameter profiles needs high measurement accuracy of voltage and fails to converge when εv0.5%. Thus, the results of SNR are not given in Table I. When εpq is small, the FSAP-SNR has better results than the FSAP. The FSAP enables the parameter estimation to reach a good result, and then the SNR fine-tunes the parameters to achieve more accurate result. However, when εpq increases, the SNR makes the estimation result worse. This is because the convergence condition of the SNR is that the sum of ΔP2 and ΔQ2 should be smaller than φ2. When εpq is large, the parameter estimation may deviate the real values to meet the convergence condition. Thus, the parameter estimation accuracy of FSAP is acceptable for the simple distribution network.

TABLE I  Result of Comparison Experiments in Modified IEEE 33-bus System
εpq (%)FSAPFSAP-SNR
MAPE(g)MAPE(b)MAPE(g)MAPE(b)
0.5 2.466 3.594 2.344 3.212
1.0 2.517 3.616 2.396 3.379
3.0 2.535 3.678 2.493 4.399
5.0 2.597 3.988 3.222 6.695

3) Line Aging Assessment

To assess the aging severity of each line in the modified topology in Fig. 3, the risk assessment is employed based on the determined topology and renewed line parameters.

The result of line aging assessment is shown in Fig. 10. The more serious the line aging, the higher the δgl, δbl, and S(𝓁). The distribution network operators can set the aging warning value Vaw according to the actual situation. If S(𝓁) exceeds Vaw, the electric power company should replace the line as soon as possible. In this paper, Vaw is set to be 0.18. As presented in Fig. 10, there are 5 lines exceeding Vaw, which needs to be alerted.

Fig. 10  Result of line aging assessment of modified IEEE 33-bus system. (a) S(𝓁). (b) Topology structure.

C. Line Aging Assessment on Modified IEEE 123-bus System

The proposed method is further conducted on the modified IEEE 123-bus system to validate its performance on the complex distribution network.

1) Topology Verification

Based on the switching lines in the modified IEEE 123-bus system in Fig. 4, it has 161 alternative topologies. The switching lines (1), (2), (3), (4), (6), and (14) in Fig. 4 are set to be connected, and the rest of the switching lines are set to be disconnected, and this topology is assumed as the actual topology Ω'. The default settings of topology verification are the same as those of the IEEE 33-bus system. In this case, ρ of each alternative topology is depicted in Fig. 11. The topology with the highest value of ρ is the best-matched topology.

Fig. 11  ρ of each alternative topology in modified IEEE 123-bus system.

The sensitivity analysis of the effects of εpq, εv, λ𝓁, Ts, and the length of hours selected for topology verification Lh on αTV is conducted. The default settings are εpq=5%, εv=0.5%, λ𝓁=1.14, Ts=15 min, and Lh=2. The result of the sensitivity analysis with varying settings is depicted in Fig. 12. Like the IEEE 33-bus system, αTV falls with the increase of εpq, εv, and λ𝓁. When Lh=1 and Ts=1 hour, αTV is 90.683%. As the sample size is too small and only one sample is used in topological verification, the result is random and inaccurate. As Lh is set between 2 and 7, Ts and Lh do not have particularly obvious effects on αTV, which are stable between 93% and 94%. When Lh is larger than 7, the lower Ts, the lower αTV. The reason is that too many samples may bring in large measurement errors, which leads to inaccurate results of topology verification.

Fig. 12  Result of sensitivity analysis with varying settings in modified IEEE 123-bus system. (a) εpq. (b) εv. (c) λ𝓁. (d) Lh.

2) Parameter Estimation

Take the topology structure in Fig. 4 as an example. The settings of parameter estimation are εpq=5%, εv=0.5%, λ𝓁=1.14, α=0.05, β=0.19, and Ts=30 min. The final values of MAPE(g) and MAPE(b) are 2.577% and 3.199%, respectively. The best estimates of line parameters and relative error between the renewed and actual values of line parameters of each line are shown in Fig. 13.

Fig. 13  Best estimates and relative error between renewed and actual values of line parameters of each line in modified IEEE 123-bus system. (a) Conductance. (b) Susceptance. (c) Relative error.

In order to further verify the validity of the proposed algorithm in large-scale distribution network, the comparison experiment is conducted with varying values of εpq, which are set to be 0.5%, 1.0%, 3.0%, 5.0%, and 10%, respectively. The result is presented in Table II. In Table II, it is clear that the FSAP-SNR achieves better estimation results than FSAP. It implies that the result of FSAP with fixed iteration step is not enough for the complex distribution network. All line parameters must be fine-tuned in combination with SNR to make the results more accurate. Thus, FSAP-SNR is preferred for large-scale distribution network.

Table II  Result of Comparison Experiments in Modified IEEE 123-bus System
εpq (%)FSAPFSAP-SNR
MAPE(g)MAPE(b)MAPE(g)MAPE(b)
0.5 3.085 3.670 2.577 3.199
1.0 3.099 3.685 2.625 3.358
3.0 3.101 3.725 2.685 3.485
5.0 3.104 3.797 2.742 3.632
10.0 3.106 3.810 2.787 3.650

3) Line Aging Assessment

The risk assessment is employed to assess the aging severity of each line in the modified topology in Fig. 4. The result is shown in Fig. 14. Vaw is set to be 0.12, and there are 5 lines exceeding Vaw, which needs to be alerted.

Fig. 14  Result of line aging assessment of modified IEEE 123-bus system. (a) S(𝓁). (b) Topology structure.

D. Discussion

Combining the results of the modified IEEE 33-bus and 123-bus systems, the FSAP displays its outstanding and robust performance in fast parameter estimation. In small distribution network, the accuracy of FASP is acceptable in line parameter estimation. In the large-scale distribution network, the FSAP is combined with SNR to further guarantee the accuracy of parameter estimation.

Especially, when the voltage measurement error is high, simply employing the SNR algorithm alone may lead to non-convergence. To solve this problem, the estimated results of FSAP provide a good initial solution for SNR to benefit its convergence.

IV. Conclusion and Future Work

In this paper, a novel approach is proposed for line aging assessment in the distribution network comprised of three stages: topology verification, parameter estimation, and line aging assessment.

In topology detection, the best-matched topology is determined based on the voltage magnitude and power injection data. In parameter estimation, the theoretical line parameters of the best-matched topology are renewed to best fit the actual measurement data based on the proposed FSAP-SNR approach. In line aging assessment, the risk assessment technology is utilized to quantify the aging severity risk level of each line in the distribution network. Experiments are conducted using the dataset from the Tianjin Electric Power Company in China on the modified IEEE 33-bus and 123-bus systems. The experiment results suggest that the proposed approach could effectively conduct line aging assessment in the distribution network. Besides, case studies of parameter estimation show that FSAP is suitable for the simple distribution network. In the large-scale distribution network, FSAP-SNR is preferred.

NOMENCLATURE

Symbol —— Definition
α, β —— Iterative step coefficients of conductance and susceptance of fixed-step aging parameter (FSAP)
αTV —— Accuracy of topology verification
δg𝓁, δb𝓁 —— Conductance and susceptance offset of the th line
εpq —— Load measurement error
εv —— Voltage magnitude measurement error
—— Index of lines (𝓁=1, 2, , N𝓁)
λ —— Aging coefficient of unit resistance of the th line
ρ —— Similarity between alternative and actual topologies in topology verification
Φ —— Theoretical line parameter profile
ΨH,n, ΨE,n —— Sets of head buses and end buses of Ψn
Ψn —— Set of connected switching lines in the nth alternative grid topology
Ω' —— Best-matched topology
Ωn —— Topology in the nth alternative grid topology
g, b —— Theoretical admittance of the th line
ĝ𝓁, b̂𝓁 —— Renewed line parameters
g𝓁a, b𝓁a —— Actual admittance of the th line
k —— Index of connected switching lines in the nth alternative grid topology (k=1, 2, , Nn)
Lh —— Length of hours selected for topology verification
n —— Index of alternative grid topologies (n=1, 2, , NGT)
Nb —— Number of buses of actual topology
Nc —— Number of topologies that are correctly matched
NGT —— Number of alternative grid topologies
Nn —— Number of connected switching lines in the nth alternative grid topology
Pa, Pc —— Actual and calculated active power injection data
Qa, Qc —— Actual and calculated reactive power injection data
S() —— Degree of abnormity severity of the th line
t —— Index of time slots (t=1, 2, , T)
Ts —— Sampling frequency of measurement data
Va, Vc —— Actual and calculated voltage magnitude data
Vaw —— Aging warning value

REFERENCES

1

Y. Wang, C. Peng, R. Liao et al., “Aging risk assessment based on fuzzy logic for overhead transmission line,” in Proceedings of 46th Annual Conference of the IEEE Industrial Electronics Society, Singapore, Oct. 2020, pp. 2606-2611. [Baidu Scholar] 

2

P. Musilek, J. Heckenbergerova, and M. M. I. Bhuiyan, “Spatial analysis of thermal aging of overhead transmission conductors,” IEEE Transactions on Power Delivery, vol. 27, no. 3, pp. 1196-1204, Jul. 2012. [Baidu Scholar] 

3

A. Bosisio, A. Berizzi, E. Amaldi et al., “Optimal feeder routing in urban distribution networks planning with layout constraints and losses,” Journal of Modern Power Systems and Clean Energy, vol. 8, no. 5, pp. 1005-1014, Sept. 2020. [Baidu Scholar] 

4

H. Long, C. Chen, W. Gu et al., “A data-driven combined algorithm for abnormal power loss detection in the distribution network,” IEEE Access, vol. 8, pp. 24675-24686, Jan. 2020. [Baidu Scholar] 

5

G. Montanari, D. Fabiani, and F. Ciani, “Partial discharge and aging of AC cable systems under repetitive voltage transient supply,” in Proceedings of 2016 IEEE Electrical Insulation Conference (EIC), Montreal, Canada, Aug. 2016, pp. 379-382. [Baidu Scholar] 

6

L. Förstel and L. L. Lampe, “Grid diagnostics: monitoring cable aging using power line transmission,” in Proceedings of 2017 IEEE International Symposium on Power Line Communications and Its Applications (ISPLC), Madrid, Spain, Apr. 2017, pp. 1-6. [Baidu Scholar] 

7

L. Ding, “Research on the influence of aging and high resistance grounding fault on 10 kV line,” Jiangxi Electric Power, vol. 44, no. 8, pp. 35-38, Aug. 2020. [Baidu Scholar] 

8

L. Chen, X. Bian, S. Wan et al., “Influence of temperature character of AC aged conductor on current carrying capacity,” High Voltage Engineering, vol. 40, no. 5, pp. 1499-1506, May 2014. [Baidu Scholar] 

9

M. Buhari, V. Levi, and S. K. Awadallah, “Modelling of ageing distribution cable for replacement planning,” IEEE Transactions on Power Systems, vol. 31, no. 5, pp. 3996-4004, Nov. 2015. [Baidu Scholar] 

10

P. Musilek, J. Heckenbergerova, and M. M. I. Bhuiyan, “Spatial analysis of thermal aging of overhead transmission conductors,” IEEE Transactions on Power Delivery, vol. 27, no. 3, pp. 1196-1204, Jul. 2012. [Baidu Scholar] 

11

Y. Guo, R. Chen, J. Shi et al., “Determination of the power transmission line ageing failure probability due to the impact of forest fire,” IET Generation, Transmission & Distribution, vol. 12, pp. 3812-3819, Sept. 2018. [Baidu Scholar] 

12

D. Pál, Ľ. Beňa, J. Urbanský et al., “The impact of reconfiguration on power losses in smart networks,” in Proceedings of 2020 21st International Scientific Conference on Electric Power Engineering (EPE), Prague, Czech, Oct. 2020, p. 9269189. [Baidu Scholar] 

13

G. Cavraro, A. Bernstein, V. Kekatos et al., “Real-time identifiability of power distribution network topologies with limited monitoring,” IEEE Control Systems Letters, vol. 4, no. 2, pp. 325-330, Apr. 2020. [Baidu Scholar] 

14

R. Arghandeh, M. Gahr, A. von Meier et al., “Topology detection in microgrids with micro-synchrophasors,” in Proceedings of 2015 IEEE PES General Meeting, Denver, USA, Sept. 2015, p. 7286053. [Baidu Scholar] 

15

G. Cavraro, V. Kekatos, and S. Veeramachaneni, “Voltage analytics for power distribution network topology verification,” IEEE Transactions on Smart Grid, vol. 10, no. 1, pp. 1058-1067, Jan. 2019. [Baidu Scholar] 

16

R. A. Sevlian, Y. Zhao, R. Rajagopal et al., “Outage detection using load and line flow measurements in power distribution systems,” IEEE Transactions on Power Systems, vol. 33, no. 2, pp. 2053-2069, Mar. 2018. [Baidu Scholar] 

17

J. Yu, Y. Weng, and R. Rajagopal, “PaToPa: a data-driven parameter and topology joint estimation framework in distribution grids,” IEEE Transactions on Power Systems, vol. 33, no. 4, pp. 4335-4347, Jul. 2018. [Baidu Scholar] 

18

J. Zhang, Y. Wang, Y. Weng et al., “Topology identification and line parameter estimation for non-PMU distribution network: a numerical method,” IEEE Transactions on Smart Grid, vol. 11, no. 5, pp. 4440-4453, Sept. 2020. [Baidu Scholar] 

19

G. Cavraro and V. Kekatos, “Inverter probing for power distribution network topology processing,” IEEE Transactions on Control of Network Systems, vol. 6, no. 3, pp. 980-992, Sept. 2019. [Baidu Scholar] 

20

S. Taheri, V. Kekatos, and G. Cavraro, “An MILP approach for distribution grid topology identification using inverter probing,” in Proceedings of IEEE PowerTech, Milan, Italy, Jun. 2019, p. 8810900. [Baidu Scholar] 

21

M. Z. A. Bhuiyan, G. J. Anders, J. Philhower et al., “Review of static risk-based security assessment in power system,” IET Cyber-Physical Systems: Theory & Applications, vol. 4, no. 3, pp. 233-239, Sept. 2019. [Baidu Scholar] 

22

L. Li, L. Liu, H. Wu et al., “Identification of Critical Hidden Failure Line Based on State-failure-network,” Journal of Modern Power Systems and Clean Energy, vol. 10, no. 1, pp. 40-49, Jan. 2022. [Baidu Scholar] 

23

H. Jia, W. Qi, Z. Liu et al., “Hierarchical risk assessment of transmission system considering the influence of active distribution network,” IEEE Transactions on Power Systems, vol. 30, no. 2, pp. 1084-1093, Mar. 2015. [Baidu Scholar] 

24

C. Wang, C. Yan, G. Li et al., “Risk assessment of integrated electricity and heat system with independent energy operators based on Stackelberg game,” Energy, vol. 198, p. 117349, May 2020. [Baidu Scholar]