Abstract
The commutation failure (CF) mitigation effectiveness is normally restricted by the delay of extinction angle (EA) measurement or the errors of existing prediction methods for EA or firing angle (FA). For this purpose, this paper proposes a CF mitigation method based on the imaginary commutation process. For each sample point, an imaginary commutation process is constructed to simulate the actual commutation process. Then, the imaginary EA is calculated by comparing the imaginary supply voltage-time area and the imaginary demand voltage-time area, which can update the imaginary EA earlier than the measured EA. In addition, the proposed method considers the impacts of commutation voltage variation, DC current variation, and phase angle shift of commutation voltage on the commutation process, which can ensure a more accurate EA calculation. Moreover, the DC current prediction is proposed to improve the CF mitigation performance under the single-phase AC faults. Finally, the simulation results based on CIGRE model prove that the proposed method has a good performance in CF mitigation.
LINE commutated convert based high-voltage direct current (LCC-HVDC) is widely used in power grid due to the growing demand of long-distance bulk power transmission [
There are a lot of studies on the CF mechanism. It can be concluded that CFs are mainly caused by AC voltage disturbance such as AC voltage reduction, phase angle shift, and AC voltage distortion [
The measured-type CEA controller calculates the extinction angle (EA) by measuring the ending time of commutation process and the zero-crossing time of commutation voltage, which can obtain an accurate EA. However, the EA is only updated when the commutation voltage crosses zero, leading to a conspicuous control lag. Thus, the CF mitigation capability of the measured-type CEA controller is poor.
The predicted-type CEA controller calculates the EA using electric quantities such as DC current, commutation voltage, and commutation inductance. The predicted EA can be updated when the electric quantities have a change. Therefore, the predicted-type CEA controller reacts more quickly than the measured-type CEA controller. However, in ABB control, the error between the predicted EA and the actual EA is conspicuous under the fault conditions because the remarkable variation of the voltage-time area is neglected after the fault [
In this paper, a CF mitigation method is proposed based on the imaginary commutation process. Considering the impact of commutation voltage variation, DC current variation, and the phase angle shift of commutation voltage, the imaginary EA is calculated by the imaginary commutation process. Moreover, the DC current prediction is added to the proposed method to predict the imaginary EA in advance. The imaginary EA is selected as the input of CEA controller, together with the measured EA. Under the fault conditions, the proposed method can calculate the EA timely and can decrease the FA through the CEA controller to ensure a sufficient commutation margin.
The remainder of this paper is organized as follows. In Section II, the proposed CF mitigation method is demonstrated based on the commutation process. In Section III, several simulations on the CIGRE benchmark HVDC model are carried out to verify the effectiveness of the proposed method. Finally, Section IV concludes this paper.
According to the commutation voltage-time area [
(1) |
where is the root mean square (RMS) value of the commutation voltage; is the FA; is the OA; is the equivalent commutation reactance; is the angular frequency; is the DC current at time t; and are the beginning and ending time of commutation process, respectively.
The left side of (1) is defined as [
(2) |
where is the supply voltage-time area, which is related to FA, OA, and E.
The right side of (1) is defined as , and we have:
(3) |
where is the demand voltage-time area of the commutation process, which is related to , , and .
After the fault, (2) and (3) can be rewritten as:
(4) |
(5) |
where represents the variables after the fault. The detailed analysis of commutation process is further elaborated in [
As for the deionization process, the EA decreases due to the increase of OA. Besides, the phase angle shift of commutation voltage affects the EA. The EA after the fault can be calculated as:
(6) |
When the fault is severe or the fault is handled inappropriately, would increase excessively. Thus, the EA after the fault is less than the minimum EA , and the CF occurs.
The real commutation process is illustrated in

Fig. 1 Illustration of real commutation process and imaginary commutation process. (a) Waveforms corresponding to real commutation process. (b) Waveforms corresponding to imaginary commutation process considering FA shift .
According to the analysis in Section II-A, the commutation process begins with the firing pulse and ends when exceeds . Thus, the imaginary commutation process is proposed to achieve the continuous EA calculation. The imaginary commutation process and the corresponding waveforms are shown in
Before the fault occurrence, the imaginary supply voltage-time area at time t can be calculated as:
(7) |
where is the FA at time .
Since may change after the fault occurrence, the real-time change of can be considered by rewriting as:
(8) |
where is the RMS value of commutation voltage at time t. In (8), the real-time change of advanced angle and are considered.
Besides, the phase angle shift of commutation voltage caused by the unsymmetrical faults and the active power fluctuation affects the imaginary commutation process. The impacts of phase angle shift on the commutation process can be considered from two aspects. The first impact is that the FA order is not equal to the actual FA, which results in the FA shift . The other impact is that the half period of commutation voltage is not equal to 10 ms, which results in the zero-crossing shift of the commutation voltage .

Fig. 2 Relationship between , , and .
The actual phase angle is the real phase angle of commutation voltage. The system phase angle is the output phase angle of phase-locked loop (PLL) of HVDC system. The normal phase angle is the phase angle calculated with after the commutation voltage crosses zero. Generally, the PLL of HVDC system is the synchronous reference frame phase-locked loop (SRF-PLL) [
In
(9) |
Similarly, the zero-crossing shift of the commutation voltages and can be measured only when the commutation voltage crosses zero. To achieve the continuous zero-crossing shift calculation caused by phase angle shift, at time t can be calculated as:
(10) |
(11) |
where is the time when the commutation voltage crosses zero.
Considering the FA shift at the beginning time of imaginary commutation process, (8) can be rewritten as:
(12) |
At time t, the imaginary demand voltage-time area of the commutation process can be calculated as:
(13) |
The waveforms of and considering the FA shift are illustrated in
(14) |
where denotes the imaginary OA.
Due to the inductances of DC transmission line and inverter-side AC transmission line, the DC current changes smoothly between the fault time and CF time. Therefore, based on the DC current and the rate of DC current variation, it is possible to predict the DC current within a short time before CF. The predicted DC current can be expressed as:
(15) |
where , , and are the predicted DC current, the DC current, and the rate of DC current variation at time ti, respectively; and is the prediction time, which is adjustable.
The DC current prediction loses the accuracy after CF occurs due to the short circuit of DC terminal. However, the DC current prediction is practicable during the transient fault period before CF occurs.
Substituting (15) into (13), the predicted imaginary supply voltage-time area can be calculated as:
(16) |
Similarly, the ending time of predicted imaginary commutation process can be acquired by comparing and . Based on (14), the predicted imaginary EA can be calculated as:
(17) |
The two-terminal HVDC system is the most used structure consisting of a rectifier side and inverter side, each of which has its own control system.

Fig. 3 Block diagram of HVDC control system with the proposed method.
To prevent the CF, the detailed procedure of the proposed method can be described as follows.
The FA shift and the zero-crossing shift of the commutation voltage are calculated based on (13) and (14), respectively. The comparator is used to avoid the output spike near the zero-crossing point. When or is larger than , the output is or , respectively. When or is less than , the output is or , respectively.
The predicted DC current is calculated by (15). is filtered by a moving average filtering (MAF), which has a time constant of 3.33 ms due to the specific harmonic in DC current. is calculated by the derivative (D) of and then filtered by a low-pass filter (LPF), which has a time constant of 2 ms. To better mitigate the CF, is selected to be 0 ms when the amplitude value of zero-sequence voltage is smaller than the threshold (0.02 p.u.), and is selected as 20 ms when is larger than . The reason is explained in detail in Section Ⅲ-C. Moreover, to avoid the DC fluctuation under the single-line-to-ground fault, is selected as 0 ms when is larger than for 0.1 s, which is explained in detail in Section Ⅲ-D. The method proposed in [
The imaginary commutation process starts with the begin pulse at , which means there is an imaginary commutation process beginning at every sampling time of each commutation voltage . Ej is the corresponding RMS value of . The time t, the FA shift , the DC current Id, and the rate of change of DC current at time ti are recorded. Then, the imaginary supply voltage-time area and the predicted imaginary demand voltage-time area are calculated by (12) and (16), respectively. When is larger than , the imaginary commutation process beginning at time is completed. Meanwhile, the end pulse at is generated to record the time t and the zero-crossing shift at time .
The predicted imaginary EA is calculated by (17). Since there is a predicted imaginary EA corresponding to every imaginary commutation process, the predicted imaginary EA can be continuous.
Both the predicted imaginary EA and the measured EA are set as the input of the CEA controller. Besides, to reduce the side effect of the predicted imaginary EA on the recovery process, the proposed method is blocked when the measured EA is larger than 20° for 20 ms and is enabled when the imaginary EA is less than 20°, as shown in

Fig. 4 Generation of enable signal of proposed method.
To validate the effectiveness of the proposed method, several simulations have been performed in the CIGRE benchmark HVDC model based on the PSCAD/EMTDC [

Fig. 5 Waveforms of imaginary EA ( and ) and measured EA under different faults. (a) A-G faults with different Lf. (b) ABC-G faults with different .
Referring to
Due to the measurement delay and phase-locked error, the calculation error of imaginary EA is inevitable. However, the variation tendency of the imaginary EA coincides with that of the measured EA after the fault. Because the rate of DC current variation is not zero after the fault, the imaginary EA when ms changes earlier than that when ms. Since the imaginary EA changes earlier than the measured EA, it is possible for CEA controller to reduce the FA earlier to prevent CF. The spike of the imaginary EA in
It should be noted that the imaginary EA is updated earlier than the measured EA all the time. So, with the proposed method, the FA decreases at the beginning of the fault to improve the CF mitigation performance. However, it would slow down the recovery process since the FA increases later. Thus, to reduce the side effect of the proposed method during the recovery process, the proposed method is blocked when the measured EA is larger than for a duration of 20 ms, which makes sure that the HVDC system is under recovery process and at a low risk of CF. Moreover, the proposed method is enabled immediately after the imaginary EA is less than . This is because the measured EA is usually larger than immediately after the fault and tends to be smaller than when the HVDC system is recovering to equilibrium operation point.

Fig. 6 System response under different faults with different control methods. (a) A-G fault. (b) ABC-G fault.
When an A-G fault occurs, the risk of CF increases under the joint action of voltage drop, DC current rise, and phase angle shift of the commutation voltage. With the CIGRE control, the measured EA updates when the commutation voltage crosses zero, resulting in a distinct delay. Referring to the blue lines in
Referring to the red lines in
To investigate the impact of fault time on the CF mitigation performance of the proposed method, several simulations are conducted. The AC faults are applied at different time, which varies from 1.500 s to 1.509 s with the time step of 0.001 s.
The simulation results under A-G and ABC-G faults with different control methods are shown in Fig. and (b), respectively, where denotes the minimum value of fault inductance, corresponding to the most severe fault when the CF does not occur. It can be observed from

Fig. 7 Performance of CF mitigation under different faults with different control methods. (a) A-G faults. (b) ABC-G faults.
Under the A-G faults, the CF mitigation of CIGRE control or the proposed method with different acts differently at different fault time.
As can be observed from
Moreover, the DC current prediction time Tpre is selected as 20 ms considering the DC current measurement delay caused by MAF, the variation rate of DC calculation delay caused by LPF, and the fact that CF mitigation ability depends on CP10 and CP11 when the fault time is around CP4 and CP5, which has a time interval of about 10 ms.
Under the A-G faults, the proposed method with can update EA earlier and quicklier than that with or 0 ms. Thus, even if the fault initial time is far from CP4 such as 1.500 s, the FA with will be decreased to mitigate the upcoming CF of CP4. With the proposed method with , the CF mitigation ability is largely increased when the fault initial time ranged during 1.500-1.502 s and 1.506-1.509 s. However, if Tpre is selected larger than 25 ms, the CF mitigation performance of the proposed method would be worse. It is because the excessively reduced FA decreases the AC voltage and then increases the DC current, and the FA control does more harm than good in this situation. Still, the CF mitigation can be improved with DC current control or reactive power compensation equipment since the CF time is largely postponed.
Under the ABC-G faults, the commutation process of every valve is equally affected by the fault time. The voltage drop and the phase angle shift of every commutation voltage are equally changed as well. In this situation, the EA corresponding to every commutation process tends to decrease. If or 5 ms, the predicted imaginary EA updates a little earlier than the measured EA. Thus, the FA generated by CEA controller is appropriate to mitigate CF. When , the predicted imaginary EA updates earlier and decreases more than that when or 5 ms. Thus, the FA is reduced more and earlier, which tends to increase the DC current and decrease the AC voltage. Moreover, both the voltage sag and the DC current increment are severer than that of A-G faults. The FA is reduced more when or 5 ms than .

Fig. 8 System response under different faults with different control methods. (a) A-G fault. (b) ABC-G fault.
It can be observed from
In this paper, the imaginary commutation process is analyzed by commutation voltage-time area, and a CF mitigation method based on the imaginary commutation process is proposed. In the proposed method, the variation of AC voltage, DC current, FA shift, and the zero-crossing shift are considered. By analyzing the simulation results of the CIGRE benchmark model built in PSCAD/EMTDC, it can be concluded that:
1) The proposed calculation method of imaginary EA can calculate the EA quickly and accurately during the transient fault process.
2) The proposed method can improve the system CF mitigation capability under AC faults, especially under A-G faults. Under the A-G faults, the system has better CF mitigation performance when ms than 0 ms. Under the ABC-G faults, the system has better CF mitigation performance when ms than 20 ms.
3) The proposed method can also mitigate subsequent CF.
Appendix
In Table AI, kY/D and kY/Y are the transformer ratios of Y/D transformer and Y/Y transformer, respectively; iVn is the currents flowing through valve ; and the subscripts D and Y represent the variables of Y/D and Y/Y transformers, respectively.

Fig. A1 Twelve-pulse converter at inverter side.

Fig. A2 Commutation process.
References
T. Wu, Y. Zheng, Q. Liu et al., “Continuous commutation failure suppression method based on self-adaptive auto-disturbance rejection proportional-integral controller for HVDC transmission system,” Journal of Modern Power Systems and Clean Energy, vol. 8, no. 6, pp. 1178-1187, Nov. 2020. [Baidu Scholar]
L. Jing, Bin Wang, X. Dong et al., “An overview of continuous commutation failure in HVDC transmission system,” Electric Power Automation Equipment, vol. 39, no. 9, pp. 116-122, Jan. 2019. [Baidu Scholar]
C. Guo, B. Liu, and C. Zhao, “Improved coordinated control approach for evolved CCC-HVDC system to enhance mitigation effect of commutation failure,” Journal of Modern Power Systems and Clean Energy, vol. 9, no. 2, pp. 338-346, Mar. 2021. [Baidu Scholar]
S. Ruan, K. Xu, D. Liu et al., “Statistical analysis and suggestions on resistance measures for commutation failures of HVDC transmission system,” Automation of Electric Power Systems, vol. 43, no. 18, pp. 13-17, Sept. 2019. [Baidu Scholar]
B. Rehman, C. Liu, H. Li et al., “Analysis on local and concurrent commutation failure of multi-infeed HVDC considering inter-converter interaction,” Journal of Modern Power Systems and Clean Energy, vol. 10, no. 4, pp. 1050-1059, Jul. 2022. [Baidu Scholar]
Q. Tao and Y. Xue, “Quantitative assessment for commutation security based on extinction angle trajectory,” Journal of Modern Power Systems and Clean Energy, vol. 9, no. 2, pp. 328-337, Mar. 2021. [Baidu Scholar]
H. Xiao, Y. Li, J. Zhu et al., “Efficient approach to quantify commutation failure immunity levels in multi-infeed HVDC systems,” IET Generation, Transmission & Distribution, vol. 10, no. 4, pp. 1032-1038, Mar. 2016. [Baidu Scholar]
L. Zeng, Y. Li, Y. Zhang et al., “Research on mechanism and control strategy of continuous commutation failures in HVDC system caused by asymmetrical fault in inverter-side AC system,” Proceedings of the CSEE, vol. 39, no. 11. pp. 3159-3168, Jun. 2019. [Baidu Scholar]
Y. Xue and X. Zhang, “Reactive power and AC voltage control of LCC HVDC system with controllable capacitors,” IEEE Transactions on Power Systems, vol. 32, no.1, pp. 753-764, Jan. 2017. [Baidu Scholar]
Q. Meng, Z. Liu, L. Hong et al., “A suppression method based on nonlinear VDCOL to mitigate the continuous commutation failure,” Power System Protection and Control, vol. 47, no. 7, pp. 119-127, Apr. 2019. [Baidu Scholar]
H. Zhou, W. Yao, C. Li et al., “A predictive voltage dependent current order limiter with the ability to reduce the risk of first commutation failure of HVDC,” High Voltage Engineering, doi: 10.13336/j.1003-6520.hve.20210532. [Baidu Scholar]
Z. Wei, W. Fang, and J. Liu, “Variable extinction angle control strategy based on virtual resistance to mitigate commutation failures in HVDC system,” IEEE Access, vol. 8, pp. 93692-93704, May 2020. [Baidu Scholar]
M. O. Faruque, Y. Zhang, and V. Dinavahi, “Detailed modeling of CIGRE HVDC benchmark system using PSCAD/EMTDC and PSB/SIMULINK,” IEEE Transactions on Power Delivery, vol. 21, no. 1, pp. 378-387, Jan. 2006. [Baidu Scholar]
S. Wang, S. Lu, Y. Hou et al., “Improvement of HVDC commutation failure response based on compound phase-shifting control,” Journal of Engineering, vol. 2017, pp. 1473-1477, Dec. 2017. [Baidu Scholar]
S. Mirsaeidi and X. Dong, “An enhanced strategy to inhibit commutation failure in line-commutated converters,” IEEE Transactions on Industrial Electronics, vol. 67, no. 1, pp. 340-349, Jan. 2020. [Baidu Scholar]
H. Wang, Y. Huang, and Q. Zhou, “Analysis of commutation failure response strategies and prediction control technology in HVDC,” Power System Protection and Control, vol. 42, no. 21, pp. 125-131, Nov. 2014. [Baidu Scholar]
L. Zhang and L. Dofnas, “A novel method to mitigate commutation failures in HVDC systems,” in Proceedings of International Conference on Power System Technology, Kunming, China, Oct. 2002, pp. 51-56. [Baidu Scholar]
J. Wang, Zi. Wang, X. Xuan et al., “Extinction angle control based on predictive calculation and its improvement,” Power System Technology, vol. 42, no. 12, pp. 3985-3991, Dec. 2018. [Baidu Scholar]
L. Liu, S. Lin, P. Sun et al., “A calculation method of Pseudo extinction angle for commutation failure mitigation in HVDC,” IEEE Transactions on Power Delivery, vol. 34, no. 2, pp. 777-779, Apr. 2019. [Baidu Scholar]
R. Zhu, X. Zhou, H. Xia et al., “A commutation failure prediction and mitigation method,” Journal of Modern Power Systems and Clean Energy, vol. 10, no. 3, pp. 779-787, May 2022. [Baidu Scholar]
R. Zhu, X. Zhou, H. Yin et al., “Commutation failure analysis considering the frequency response of transmission line,” in Proceedings of 2021 IEEE 2nd China International Youth Conference on Electrical Engineering (CIYCEE), Chengdu, China, Dec. 2021, pp. 1-6. [Baidu Scholar]
Q. Wu, C. Fu, Y. Gong et al., “Comparative analysis of three kinds of HVDC synchronous firing control systems,” Power System Technology, vol. 44, no. 12, pp. 4744-4754, Dec. 2020. [Baidu Scholar]
M. Ciobotaru, R. Teodorescu, and F. Blaabjerg, “A new single-phase PLL structure based on second order generalized integrator,” in Proceedings of IEEE Power Electronics Specialists Conference (PESC’06), Jeju, South Korea, Jun. 2006, pp. 1-6, [Baidu Scholar]
L. Xiong, F. Zhuo, M. Zhu et al., “Research on fast phase synchronization in single-phase power systems,” Proceedings of the CSEE, vol. 35, no. 9, pp. 2209-2216, May 2015. [Baidu Scholar]