Abstract
Improving the flexibility of combined heat and power (CHP) units is an important way to solve the problem of wind power accommodation in northern China. Firstly, this paper analyzes the principle of an extraction-type CHP unit, calculates its safe operation range, and analyzes its contradiction between heating and peaking. Secondly, the safe operation ranges of the CHP unit with several flexibility modifications are further calculated, which involve two-stage bypass, low-pressure cylinder (LPC) removal, heat storage tank, and electric boiler. Finally, based on the safe operation ranges, their effects on improving the capabilities of deep peak shaving and wind power accommodation are compared, and their adaptabilities to different wind scenarios are analyzed. The results show that: ① all flexibility modifications can improve the deep peak shaving capability of the CHP unit, especially for the two-stage bypass and the electric boiler; ② LPC removal modification can accommodate wind power to some extent, but most of wind power is still abandoned; ③ heat storage tank modification is unstable in different wind scenarios, which is determined by the surplus heating capability during the daytime.
SINCE the climate in northern China is severely cold in winter [
Flexibility modification is an important way to solve this problem. Currently, several flexibility modifications have been carried out in China, mainly including two-stage bypass [
Recently, extensive research works on flexibility modifications have been carried out. Reference [
This paper analyzes the principle of an extraction-type CHP unit, calculates its safe operation range, and analyzes its contradiction in heating and peaking. Based on further analysis of two-stage bypass, LPC removal, heat storage tank, and electric boiler, the safe operation ranges of CHP units with different flexibility modifications are calculated, and their effects on improving deep peak shaving and wind power accommodation capabilities are compared.
The remainder of this paper is organized as follows. Section II analyzes the necessity of flexibility modification of CHP units. Section III calculates several flexibility modifications of CHP unit. Section IV compares each flexibility modification. Section V gives the conclusion.
The exhaust steam from the intermediate-pressure cylinder (IPC) is mainly divided into two parts, as shown in

Fig. 1 Principle of extraction-type CHP unit.
In practical applications, the heating load can be controlled by the extraction valve (EV) and the link valve (LV). The steam pressure in front of LV needs to be monitored, especially under low load conditions. The steam entering the LPC would fail to meet its cooling demand when the pressure is too low.
This paper takes a 330 MW CHP unit of a power plant in Jilin, China, as the research object. The CHP unit is equipped with a subcritical primary-reheating natural circulation boiler and a subcritical primary-reheating water-cooled steam turbine. The design parameters of the boiler and turbine are shown in
In addition to the BMCR, TMCR, and boiler stable combustion (BSC) conditions, the impact of heating load on the safe operation of CHP units should also be considered. In this case, the safe operation range of CHP units is actually a two-dimensional area based on the heating load and power generation load [

Fig. 2 Calculation of safe operation range for CHP unit.
1) Determine the boundary line (AB) of the BMCR condition. It can be observed from
(1) |
where is the power generation load; and is the heating load.
2) Determine the boundary line (DE) of the BSC condition. Based on the boiler operation procedures, the minimum stable combustion load of the boiler is 40% BMCR (142.59 MW), i.e., the coordinate of point E is (0, 142.59 MW). Since the thermoelectric conversion efficiency of a steam turbine is basically the same under any operation conditions, the slope of DE is the same as that of AB. Therefore, the equation of line DE is:
(2) |
3) Determine the boundary lines BC and CD. The safe operation of the steam turbine is mainly limited by the cooling steam flow of LPC. Based on the turbine operation procedures, the minimum cooling steam flow is 140 t/h. Since the maximum extraction steam flow is 550 t/h under the TME condition, the exhaust steam flow of the IPC is at least 690 t/h.
Based on
(3) |
(4) |
where is the exhaust steam flow from IPC; is the main steam flow; and is the inlet steam flow of LPC.
Substituting t/h into (3), t/h. Further substituting into (4), MW, i.e., the coordinate of point b is (0, 326.58 MW). Since the slope of bC and AB are the same, the equation of the straight line bC is:
(5) |
Keeping t/h and substituting it into (5), MW, i.e., the coordinate of point C is (550 t/h, 232.86 MW).
Based on (4), the main steam flow under the minimum BSC condition is 428.16 t/h. Substituting it into (3), t/h. Considering the cooling steam flow of LPC (140 t/h), the actual steam flow entering the heat-supply network is 176.51 t/hour. Substituting into (2), MW, i.e., the coordinate of point D is (176.51 t/h, 112.51 MW). Line CD can be fitted as:
(6) |
In summary, the boundary lines of safe operation range for the CHP unit is as shown in (7).
(7) |
Once the CHP unit supplies heat, it needs to ensure the heating load in priority [
Assuming that the heating load in each period is , the adjustable range of the power generation load is between F and G, as shown in

Fig. 3 Contradiction between heating and peaking.
It can be observed from

Fig. 4 Principle of extraction-type CHP unit with two-stage bypass.
The design parameters of the bypass system are shown in

Fig. 5 Calculation of safe operation range for CHP unit with two-stage bypass.
1) Theoretically, based on the first law of thermodynamics, the boundary lines and coincide with AB and DE:
(8) |
(9) |
In this case, 175 t/h of main steam is desuperheated and depressurized by 33.5 t/h of desuperheating water when the high-stage bypass is put into operation, which forms 208.5 t/h of reheated steam. And then, this part of the reheated steam is further desuperheated and depressurized by 37.21 t/h of desuperheating water, and eventually forms 245.71 t/h of heating steam. Thus, the maximum steam flow entering the HPC is , which corresponds to the 646.81 t/h of exhaust steam from IPC in (3).
Considering that at least 140 t/h of steam is required to cool the LPC, the steam that can be extracted for heating is 506.81 t/h. With the addition of 245.71 t/h of the heating steam formed by the two-stage bypass, the actual heating capacity is 752.52 t/h. Substituting t/h into (8), the maximum power generation load is 228.25 MW, i.e., the coordinate of point is (752.52 t/h, 228.25 MW).
The operation of the bypass systems has decreased the maximum extraction heating steam from 550 t/h to 506.81 t/h. If the power generation load were further reduced, the heating capacity of the unit would continue to decrease. In this case, point has coincided with point , and the coincident point is represented by in
Considering that the slope of is the same as that of BD, based on point , the equation of the line is:
(10) |
Point is actually the intersection of line and line . Combining (9) and (10), the coordinate of point can be obtained as (318.32 t/h, 88.35 MW).
2) However, according to the second law of thermodynamics, the energy is graded, which is determined by the steam pressure and temperature. The higher the steam pressure and temperature, the higher the grade of energy, and the greater the available energy. If the high-grade energy is artificially converted into low-grade energy, the available energy would be lost. The efficiency of bypass system can be calculated as [
(11) |
(12) |
(13) |
(14) |
where is the efficiency of bypass system; is the lost available energy; is the high-grade steam flow; is the low-grade steam flow; is the available energy of high-grade steam; is the available energy of low-grade steam; is the enthalpy of high-grade steam; is the enthalpy of low-grade steam; is the entropy of high-grade steam; is the steam enthalpy in environmental state, kJ/kg; is the steam entropy in environmental state, ; and is the steam temperature in environmental state, K.
Based on
(15) |
(16) |
Based on the calculation, the coordinate of point is (752.52 t/h, 168.76 MW), and that of is (318.32 t/h, 46.69 MW).
Fitting , , and , the boundary lines of safe operation range for the CHP unit with two-stage bypass is shown in (17).
(17) |
It can be observed from

Fig. 6 Principle of extraction-type CHP unit with LPC removal.
The design parameters of the LPC is shown in
(18) |

Fig. 7 Calculation of safe operation range for CHP unit with LPC removal.
where is the inlet steam flow of LPC; is the inlet steam enthalpy of LPC; is the exhaust steam enthalpy of LPC; is the
The relationship between the power generation load of LPC and its inlet steam flow can be linearly fitted as:
(19) |
1) Considering that the LPC removal does not affect the BMCR and BSC conditions, the boundary lines and coincide with AB and DE, respectively:
(20) |
(21) |
2) Determine the coordinate of point . Firstly, substituting MW into (4), t/h. Substituting it into (3), t/h. Considering the maximum extraction steam flow 550 t/h, the heating steam flow obtained by LPC removal is 200.69 t/h. Substituting it into (19), the power generation load can be reduced by 28.41 MW. In this case, the actually power generation load is 234.34 MW, and the coordinate of point is (750.69 t/h, 234.34 MW).
3) Determine the coordinate of point . Substituting the minimum steam flow of LPC 140 t/h into (19), the power generation load can be reduced by 16.19 MW. In this case, the actually power generation load of the unit is 216.67 MW, i.e., the coordinate of point is (690 t/h, 216.67 MW). It can be observed that point is actually on the line .
4) Determine the coordinate of point . Since 140 t/h of steam flow is cut off, the power generation load of the unit can be reduced by 16.19 MW under the BSC condition. In this case, the coordinate of point is (316.51 t/h, 96.34 MW).
5) Determine the boundary line () under the TME condition. Based on the coordinates of point , , and , the straight line can be fitted as:
(22) |
In summary, the boundary lines of safe operation range for the CHP unit with LPC removal are as shown in (23).
(23) |
In

Fig. 8 Principle of extraction-type CHP unit with heat storage tank.
This paper calculates the increased heating capacity by the heat storage tank as shown in (24), and expands the safe operation range of the CHP unit. The design parameters of heat storage tank is shown in
(24) |

Fig. 9 Calculation of safe operation range for CHP unit with heat storage tank.
where is the specific heat capacity of water; th is the hot water temperature; tc is the cold water temperature; Dtank is the circulating water flow of the tank; is the exhaust steam enthalpy from IPC; and is the saturated water enthalpy corresponding to the exhaust steam pressure of IPC.
Taking , , , t/h, kJ/kg, and kJ/kg, the increased heating capacity is t/h.
The safe operation range of the CHP unit with heat storage tank should be shifted to the right by (332.97 t/h, 0) during the heat release process. In this case, the coordinates of points , , , and are (332.97 t/h, 356.48 MW), (882.97 t/h, 262.75 MW), (882.97 t/h, 232.86 MW), and (509.48 t/h, 112.51 MW), respectively. Similarly, it should be shifted to the left by (332.97 t/h, 0) during the heat store process. Considering that the heating load of point D is only 176.51 t/h, it can be stored completely. Therefore, point D can be translated to the y-axis as point F with coordinates of (0, 112.51 MW).
In summary, the boundary lines of safe operation range for the CHP unit with heat storage tank is shown in (25).
(25) |
In

Fig. 10 Principle of extraction-type CHP unit with electric boiler.
The increased heating capacity of the electric boiler can be calculated by (26). The design parameters of the electric boiler are shown in
(26) |

Fig. 11 Calculation of safe operation range for CHP unit with electric boiler.
where is the electricity-heat conversion efficiency; is the heat exchanger efficiency; and is the rated load of electric boiler.
Taking kJ/kg, kJ/kg, , , and MW, the increased heating capacity of the electric boiler is t/h.
The safe operation range of the CHP unit with electric boiler should be shifted to the right by (173.15 t/h, 125 MW). In this case, the coordinates of points , , , and are (723.15 t/h, 137.75 MW), (723.15 t/h, 107.86 MW), (381.76 t/h, -12.49 MW), and (173.15 t/h, 17.59 MW), respectively.
In summary, the boundary lines of safe operation range for the CHP unit with electric boiler is shown in (27).
(27) |
All flexibility modifications can improve the DPSC of the CHP unit to some extent, as shown in
(28) |
1) Since the two-stage bypass modification fails to affect the BSC condition, the DPSC of the CHP unit with the two-stage bypass remains unchanged when the heating load varies from 0 to 100 t/h. However, it is significantly increased when the heating load varies from 200 t/h to 700 t/h. In particular, when the heating load reaches 600 t/h, the DPSC of the CHP unit with the two-stage bypass is increased from 0% to 61.86%. Therefore, the two-stage bypass modification can greatly improve the DPSC of the CHP unit. In addition, the minimum power generation load of the CHP unit with two-stage bypass can be reduced as low as 55.21 MW, thereby freeing up more space for wind power accommodation.
2) Same as the two-stage bypass, LPC removal modification has almost the same effect, which can also improve the DPSC of the CHP unit and reduce the minimum power generation load.
3) Although the heat storage tank modification fails to affect the BSC condition, it can still reduce the minimum power generation load when the heating load varies from 0 to 100 t/h. This is because the heat storage tank can also play the role of a controllable-virtual heat user to store heat under the low load condition. The safe operation range of the CHP unit with heat storage tank has been greatly expanded, which improves its DPSC in a large scale. However, the heat storage tank modification fails to further reduce the minimum power generation load (112.51 MW).
4) The electric boiler uses part of the power output to heat the return water, which not only increases the heating capacity, but also reduces the power generation load of the unit. In this case, the electric boiler modification can greatly reduce the minimum power generation load of the unit, even below zero. Compared with the other flexible modifications, the electric boiler significantly improves the DPSC of the CHP unit.
From the above subsection, the flexibility modification can improve the DPSC of the CHP unit to varying degrees. What are their effects on wind power accommodation? This paper has conducted a detailed analysis as follows.
From

Fig. 12 Effect of two-stage bypass modification on wind power accommodation. (a) Daily power generation load demand. (b) Safe operation range.
From

Fig. 13 Effect of LPC removal modification on wind power accommodation. (a) Daily power generation load demand. (b) Safe operation range.
As shown in

Fig. 14 Effect of heat storage tank modification on wind power accommodation. (a) Daily power generation load demand. (b) Safe operation range.
From

Fig. 15 Effect of electric boiler modification on wind power accommodation. (a) Daily power generation load demand. (b) Safe operation range.
All flexibility modification can accommodate wind power to varying degrees. However, there are differences in adaptabilities to wind power accommodation. This paper further simulates and analyzes their adaptabilities in different wind scenarios. If the daily average load rate is less than 50%Pe, it would be regarded as a strong wind scenario; otherwise, it would be regarded as a small wind scenario. The following variables are defined: is the heating load demand; is the heating load output from the CHP unit; is the auxiliary heating load output from the flexible devices; is the actual heating load sent to the heat-supply network; is the power generation load demand; is the power generation load output from the CHP unit; is the abandoned wind power load; and is the actual power generation load sent to the power system.
From Figs.

Fig. 16 Adaptabilities to strong wind scenario. (a) Two-stage bypass. (b) LPC removal. (c) Heat storage tank. (d) Electric boiler.

Fig. 17 Adaptabilities to small wind scenario. (a) Two-stage bypass. (b) LPC removal. (c) Heat storage tank. (d) Electric boiler.
However, the LPC removal fails to adapt to neither strong nor small wind scenarios, resulting in a large part of abandoned wind power (
In order to further illustrate the adaptability of these flexibility modifications, this paper calculates the abandoned wind power in different scenarios as shown in
From the table, the bypass and electric boiler modifications can realize the full accommodation of wind power. The LPC removal modification can reduce abandoned wind power to some extent, but most of the wind power is still abandoned. The heat storage tank modification is unstable in wind power accommodation. Only 2.79 MWh of wind power is abandoned under small wind scenario, while 474.96 MWh of wind power is abandoned under strong wind scenario. Since the electric boiler can convert electricity to heat, the full accommodation of wind power can be realized.
All flexibility modifications can improve the DPSC of the CHP unit to varying degrees. Among them, the effect of the electric boiler is the most significant, and the proper electric boiler modification can completely decouple the constraints of “ordering power by heat” for the CHP unit. Compared with other flexibility modifications, the heat storage tank modification fails to further reduce the minimum power generation load of the CHP unit.
All flexibility modifications can consume wind power to varying degrees. Among them, the electric boiler can achieve full accommodation of wind power. Although the heat storage tank modification greatly expands the safe operation range, its actual effect on wind power accommodation is limited by the surplus heating capability during the daytime. The more heat stored in the heat storage tank during the daytime, the stronger the wind power accommodation capability during the nighttime.
The electric boiler and bypass modifications can adapt well to both strong and small wind scenarios, especially for the electric boiler modification, which can realize the full accommodation of wind power. The LPC removal modification can reduce the abandoned wind power to some extent, but most of the wind power is still abandoned. The heat storage tank modification is unstable in wind power accommodation, which can only adapt to small wind scenario.
REFERENCES
L. Yang, J. C. Lam, and J. P. Liu, “Analysis of typical meteorological years in different climates of China,” Energy Conversion and Management, vol. 48, no. 2, pp. 654-668, Feb. 2017. [Baidu Scholar]
W. Wang, Z. Li, J. Lv et al., “An overview of the development history and technical progress of China’s coal-fired power industry,” Frontiers in Energy, vol. 13, pp. 417-426, Apr. 2019. [Baidu Scholar]
W. Zheng, Y. Zhang, J. Xia et al., “Cleaner heating in northern China: potentials and regional balances,” Resources Conservation and Recycling, vol. 160, pp. 1-15, Sept. 2020. [Baidu Scholar]
J. Yin, G. Huang, Y. Xie et al., “Carbon-subsidized inter-regional electric power system planning under cost-risk tradeoff and uncertainty: a case study of Inner Mongolia, China,” Renewable and Sustainable Energy Reviews, vol. 135, pp. 1-15, Sept. 2020. [Baidu Scholar]
N. Zhang, X. Lu, M. B. McElroy et al., “Reducing curtailment of wind electricity in China by employing electric boilers for heat and pumped hydro for energy storage,” Applied Energy, vol. 184, pp. 987-994, Dec. 2016. [Baidu Scholar]
W. Wei, X. Yan, Y. Ni et al., “Power system flexibility scheduling model for wind power integration considering heating system,” in Proceedings of 2017 IEEE PES General Meeting, Chicago, USA, Jul. 2017, pp. 1-5. [Baidu Scholar]
Y. Gao, Y. Hu, D. Zeng et al., “Modeling and control of a combined heat and power unit with two-stage bypass,” Energies, vol. 11, no. 6, pp. 1-20, May 2018. [Baidu Scholar]
G. Tian, L. Liu, Z. Huang et al., “Reconstruction scheme of removing low pressure cylinder and heating for 350 MW unit analysis of peak regulation performance,” Turbine Technology, vol. 61, pp. 457-460, Dec. 2019. [Baidu Scholar]
F. Lai, S. Wang, M. Liu et al., “Operation optimization on the large-scale CHP station composed of multiple CHP units and a thermocline heat storage tank,” Energy Conversion and Management, vol. 211, pp. 1-12, May 2020. [Baidu Scholar]
X. Huang, Z. Xu, Y. Sun et al., “Heat and power load dispatching considering energy storage of district heating system and electric boilers,” Journal of Modern Power Systems and Clean Energy, vol. 6, no. 5, pp. 992-1003, Sept. 2018. [Baidu Scholar]
J. Wang, S. You, Y. Zong et al., “Investigation of real-time flexibility of combined heat and power plants in district heating applications,” Applied Energy, vol. 237, pp. 196-209, Mar. 2019. [Baidu Scholar]
Y. Gao, D. Zeng, L. Zhang et al., “Research on modeling and deep peak regulation control of a combined heat and power unit,” IEEE Access, vol. 8, pp. 91546-91557, May 2020. [Baidu Scholar]
X. Chen, C. Kang, M. O’Malley et al., “Increasing the flexibility of combined heat and power for wind power integration in China: modeling and implications,” IEEE Transactions on Power Systems, vol. 30, no. 4, pp. 1848-1857, Jul. 2015. [Baidu Scholar]
S. Katulic, M. Cehil, and Z. Bogdan, “A novel method for finding the optimal heat storage tank capacity a cogeneration power plant,” Applied Thermal Engineering, vol. 65, no. 1-2, pp. 530-538, Apr. 2014. [Baidu Scholar]
T. Wang and L. Tian, “Calculation method for safe operation zone of heat supply units based on uniform design,” Journal of North China Electric Power University (Natural Science Edition), vol. 43, pp. 88-93, Sept. 2016. [Baidu Scholar]
Y. Zhang, Q. Lv, Y. Li et al., “Analysis on operation flexibility of combined heat and power plant with four improved power-heat decoupling schemes,” Automation of Electric Power Systems, vol. 44, no. 2, pp. 164-172, Nov. 2020. [Baidu Scholar]
Y. Zhang, Q. Lv, N. Zhang et al., “Cooperative operation of power-heat regulation resources for wind power accommodation,” Power System Technology, vol. 44, no. 4, pp. 1350-1362, Jan. 2020. [Baidu Scholar]
Y. Wang, D. Zeng, and K. Chen, “Characteristic analysis for combined heat and power units with thermal storage device based on graph method,” Thermal Power Generation, vol. 46, pp. 57-60, Nov. 2017. [Baidu Scholar]
Y. Gao, D. Zeng, B. Ping et al., “Calculation of safe operation area for CHP units with absorption heat pump,” Thermal Power Generation, vol. 49, no. 2, pp. 58-64, Feb. 2020. [Baidu Scholar]
Y. Dai, L. Chen, Y. Min et al., “Dispatch model of combined heat and power plant considering heat transfer process,” IEEE Transactions on Sustainable Energy, vol. 8, no.3, pp. 1225-1236, Jul. 2017. [Baidu Scholar]
Q. Hu, P. Ge, Q. Wu et al., “Increasing operational flexibility of integrated energy systems by introducing power to hydrogen,” IET Renewable Power Generation, vol. 14, no. 3, pp. 372-380, Jan. 2020. [Baidu Scholar]
J. Kiviluoma and P. Meibom, “Influence of wind power, plug-in electric vehicles, and heat storages on power system investments,” Energy, vol. 35, no. 3, pp. 1244-1255, Mar. 2010. [Baidu Scholar]
J. Liu, “Calculation method of coal consumption in heat supply with temperature and pressure relief,” Shaanxi Electric Power, vol. 43, pp. 82-85, Jul. 2015. [Baidu Scholar]
B. Liu, J. Li, S. Zhang et al., “Economic dispatch of combined heat and power energy systems using electric boiler to accommodate wind power,” IEEE Access, vol. 8, pp. 41288-41297, Jan. 2020. [Baidu Scholar]