Abstract
We present the ferroresonance overvoltage mitigation concerning the power systems of the grid-connected wind energy conversion systems (WECSs). WECS is considered based on a doubly-fed induction generator (DFIG). Ferroresonance overvoltage associated with a single-pole outage of the line breaker is mitigated by fast regulating the reactive power using the static compensator (STATCOM). STATCOM controller is introduced, in which two incorporated proportional-integral (PI) controllers are optimally tuned using a modified flower pollination algorithm (MFPA) as an optimization technique. To show the capability of the proposed STATCOM controller in mitigating the ferroresonance overvoltage, two test cases are introduced, which are based on the interconnection status of the power transformer used with the grid-connected DFIGs. The results show that the ferroresonance disturbance can occur for the power transformers installed in the wind farms although the transformer terminals are interconnected, and neither side of the transformer is isolated. Furthermore, as a mitigation method of ferroresonance overvoltage, the proposed STATCOM controller succeeds in improving the system voltage profile and speed profile of the wind turbine as well as protecting the system components against the ferroresonance overvoltage.
OWING to the fossil fuel and pollution problems as well as the clean and green generation, many renewable energy resources have been profusely integrated into the power grid [
In the wind farms, the doubly-fed induction generator (DFIG) is one of the most important grid-connected energy conversion systems. However, they were sensitive to the wind speed variations, causing power fluctuations which badly affected the power quality [
Ferroresonance phenomena usually occurred due to the interaction between the system capacitances and non-linear inductances, in which they could be initiated by abnormal switching operations such as single-pole switching, transmission line clearing faults, and transformer energization. This contributed to slow transient overvoltage with non-sinusoidal or distortion waveforms affecting the power grid components. Therefore, the ferroresonance overvoltage mitigation was highly required to protect the power grid components against the damage. The mitigation could be classified according to the type of the considered transformer, i.e., voltage transformer or power transformer. For the voltage transformer, there were three main types of mitigation methods called active, passive, and control methods. These methods were widely covered in the literature [
The ferroresonance overvoltage in wind farms occured due to the same reasons for the traditional power grids, where the elements of ferroresonance dynamic interactions were available such as the non-linear inductive elements and capacitances. The power transformers associated with the induction machines in the wind farms provided non-linear inductive elements. Besides, there were capacitive effects due to the overhead lines and underground cables distributed in the wind farms to transmit and collect the generated power toward the power grid. Furthermore, distributed reactive power supported capacitors might be installed, e.g., with the single-fed induction generators. In [
We introduce a new application for exploiting STATCOM to mitigate the ferroresonance overvoltage of the grid-connected WECS based on DFIG. STATCOM is used to controllably inject or absorb reactive power to interact with the ferroresonance instance. Therefore, it mitigates the corresponding overvoltage due to ferroresonance occurrences. The considered STATCOM is controlled via two optimized proportional-integral (PI) controllers, which are optimized by the modified flower pollination algorithm (MFPA). Two different scenarios for the ferroresonance occurrence in the power grid including WECS, and the designed STATCOM are simulated using MATLAB/Simulink. One scenario is for the unloaded transformer, while the second one is for the loaded transformer. Based on the results, two different ferroresonance types are investigated, in which the second scenario produces higher overvoltage although the power transformer terminals at both sides are in service. Therefore, the reactive power participation of STATCOM is higher for the second scenario. Generally, the fast response from the STATCOM successfully mitigates the ferroresonance overvoltage and makes the system in safe operation.
The power system under study consists of six WECSs in DFIG-based wind farm, each rated in 1.5 MW, and is connected to the power grid via two transformers and transmission lines as shown in

Fig. 1 Power system under study with ferroresonance.
In the DFIG-based wind farm, the distributed capacitances and non-linear inductances of the transformers and induction machines enhance the ferroresonance occurrence, even if the transformer is in service. In this paper, two different scenarios with ferroresonance overvoltage are considered when a single pole of the breaker opens. The first ferroresonance test case is the common one, where the power transformer is connected to the system through a 30 km transmission line, while its secondary side is isolated. In this test case, the ferroresonance phenomenon is stimulated by opening the pole of phase a for the breaker installed at point M, where the breaker pole stray capacitance is considered to be 0.01 , and the status of breaker installed at point N is closed. The other test case for simulating the ferroresonance is that the pole of phase a for the breaker at point N is opened as shown in
The single-pole switching of the circuit breaker is considered in this paper. The equivalent analytical circuit is shown in

Fig. 2 Equivalent analytical circuit.
For the first ferroresonance scenario considered, the inductance is only for the transformer as it is isolated at the secondary side, which is shown in
Using the STATCOM to enhance the integration of WECSs into the power grid provides a promising performance if they are properly controlled. Many controllers are introduced to drive the STATCOM as reported in [
Driving the STATCOM for the WECS to mitigate the ferroresonance is a non-linear problem. Accurate adjustment and tuning of the control parameters are needed to control the STATCOM using PI controllers. Evolutionary computing (EC) techniques are used for the optimal tuning of the PI control parameters in many applications. Genetic algorithm, particle swarm optimization, cuckoo search optimization, harmony search (HS), bacterial foraging optimization (BFO), MFPA, and electromagnetic field optimization (EFO) are utilized to find optimal PI control parameters for wide applications in the power grid [
By regulating the reactive power flows between the STATCOM and the power grid at PCC, the voltage at PCC can be controlled to mitigate the ferroresonance overvoltage for grid-connected wind farms. The ferroresonance phenomena cause a sudden increase in the system voltage instantaneously and in the form of repetitive transients and power frequency waveform distortion as the ferroresonance repeatedly occurs within positive and negative half-cycles.
STATCOM is introduced to regulate the voltage and mitigate the effects of ferroresonance on the power grid. STATCOM is composed of two converters linked to DC capacitor as shown in

Fig. 3 Circuit and block diagram representation of STATCOM. (a) Single-phase STATCOM circuit. (b) Block diagram of STATCOM controlled by two PI controllers.
The STATCOM is controlled by two PI controllers. The parameters of the two PI controllers are tuned by the optimization technique of MFPA. MFPA is used to minimize the integral of the square of error (ISE) between the reference voltage (1 p.u.) and the actual grid voltage at PCC. Then, the STATCOM successfully regulates the system voltage during the ferroresonance occurrence. The block diagram of the STATCOM controlled by the two PI controllers is shown in
As shown in
Controller A has two parameters KpA and KIA, and controller B has the other two parameters KpB and KIB. MFAP is used to optimally tune the parameters of two PI controllers while minimizing the objective function J, which is the integrated square error (ISE) function of as:
(1) |
The STATCOM is not used as an exact PCC voltage controller but it allows the voltage to vary in an accepted range proportional to the compensated current. Without allowing the voltage variation, a zero slope or droop is achieved which causes a poorly defined operation point and tendency to oscillation. In addition, the maximum capacitive and inductive ratings of the STATCOM could not be extended if the droop control is activated. The droop controller is used to allow the voltage to be more than the no-load voltage at inductive compensation and, conversely, for capacitive compensation as shown in

Fig. 4 Characteristics of current and voltage for STATCOM with droop controller. (a) Capacitive mode. (b) Inductive mode.
MFPA is an amendment for the flower pollination algorithm (FPA) that depends on the application of clonal component animated from the clonal selection algorithm. Random walks are utilized to put in place of the Levy flights for their speedy convergence. The random walks are picked from a non-uniform distribution between 0 and 1. Besides, the local pollination is updated by step-size scaling factor y2.
The pollination in flowers is a natural process, in which the pollinators are carried out by two types of carriers: biotic and abiotic. Biotic pollination refers to the process when the carriers are living organisms like insects. Abiotic pollination refers to the process when the carriers are non-living organisms such as air [
In the global type, the best generation is ensured by the ability of insects to travel for long distances, and the fittest is represented as . is the objective function to be minimized as defined in (1). Then, the flower fastness and the first rule can be mathematically expressed by:
(2) |
where is a solution set at iteration t of the
(3) |
where represents a uniform distribution between 0 and 1; is the iteration k; and is the step size scaling factor. The pollination may be local or global, then a switch probability P is used to discriminate them. The flowchart of MFPA optimization is illustrated in

Fig. 5 Flowchart of MFPA optimization.
MPFA is used to determining the optimal two PI control parameters of the STATCOM for mitigating the ferroresonance overvoltage of DFIG-based WECS through minimizing ISE between the reference and actual voltage as presented in (1). Through 25 flowers and 100 iterations, the population of the flowers is initialized by a random selection of the four control parameters KpA, KIA, KpB, and KIB and positive values. Based on this random selection of the control parameters and the increasable voltage due to the ferroresonance, the objective function is determined for each flower and the global flower is selected from the populations in (2). For each flower, a random number is selected within the probability. Otherwise, the flower is randomly selected for local pollination. Pollinating the flower with global ones based on (3) is finished for each flower. For 100 iterations, all these processes are repeated, and the optimal four control parameters are recorded based on the minimum objective function.
To demonstrate the effectiveness of the proposed MFPA optimization technique for optimal tuning of the PI control parameters, another optimization technique namely particle swarm optimization (PSO) is considered for comparison. The PSO is stimulated by the behavior of some living organisms in groups like birds, fishes, and ants [
MFPA and PSO are compared through minimizing the objective function given in (1), the four PI control parameters using MFPA and PSO are given in

Fig. 6 Convergence curves for MFPA and PSO.
The grid-connected WECS is tested with and without installing the STATCOM when the ferroresonance occurs. Two cases are investigated including different services of the power transformer as follows.
The ferroresonance is simulated in this case, while the interconnection of the transformer of bus 1 is isolated as depicted in

Fig. 7 Ferroresonance occurrence without STATCOM. (a) Three-phase voltage waveforms of bus 1. (b) Three-phase voltage waveforms of bus 2. (c) Three-phase current waveforms of bus 1.
When the controlled STATCOM is installed and evaluated toward mitigating the waveform distortion due to the ferroresonance occurrences as shown in

Fig. 8 Ferroresonance mitigation with STATCOM (case 1). (a) Three-phase voltage waveforms of bus 1. (b) Three-phase voltage waveforms of bus 2. (c) Three-phase current waveforms of bus 1.
Due to the ferroresonance occurrence, the rotor speed increases by 16% which can damage the rotor shaft, and the speed values could not be retained to be lower value as depicted in

Fig. 9 Rotor speed of DFIG with and without STATCOM (case 1).

Fig. 10 Reactive power of STATCOM (case 1).
The pole of phase of the breaker at point N of the transmission line connecting the WECSs into the power grid is opened at 1 s to simulate case 2. The ferroresonance is stimulated, while the transformer is in service to interconnect the WECSs into the power grid as shown in

Fig. 11 Performance with ferroresonance occurrence. (a) Three-phase voltage waveforms at PCC. (b) Three-phase voltage waveforms at bus 4. (c) Three-phase current waveforms at PCC.
When the PI control parameters are optimized by MFPA and used to mitigate the ferroresonance overvoltage, the corresponding performance is shown in

Fig. 12 Ferroresonance mitigation with STATCOM (case 2). (a) Three-phase voltage waveforms at PCC. (b) Three-phase voltage waveforms of bus 4. (c) Three-phase current waveforms of PCC.
The optimal control of the STATCOM is attained to keep the rotor speed at a minimum disturbance compared with the speed values without using the STATCOM as shown in

Fig. 13 Rotor speed of DFIG with and without STATCOM (case 2).

Fig. 14 Reactive power of STATCOM (case 2).
Ferroresonance modes are classified into four types: fundamental, subharmonic, quasi-periodic, and chaotic [

Fig. 15 FFT analyses of ferroresonance. (a) Phase voltage of case 1. (b) Phase voltage of case 2.
We introduce two PI controllers of the STATCOM using MFPA, where the interaction of STATCOM is successfully utilized to mitigate the ferroresonance phenomena of the DFIG-based grid-connected WECSs. The proposed optimal controllers mitigate the ferroresonance disturbances due to the rapid regulated injections or absorptions of the reactive power based on STATCOM. Accordingly, the system waveforms are restored to the sinusoidal shapes. However, the single-pole openning of the breaker has still caused a system disturbance. Considering the performance with DFIG, the voltage profile is improved and the generator rotor speed during ferroresonance phenomena is achieved successfully. By evaluating the ferroresonance overvoltage waveforms of grid-connected wind farm, the ferroresonance type is found as the quasi-periodic mode for the unloaded transformer and chaotic mode for the loaded transformer, in which it is numerically processed using FFT. In this paper, the ferroresonance occurrence is confirmed for the power transformer installed in the wind farms although they are fully in service. Accordingly, the mitigation method has been introduced using the STATCOM, which has efficiently mitigated the ferroresonace in the wind farms.
Appendix
References
Y. Tang, H. He, J. Wen et al., “Power system stability control for a wind farm based on adaptive dynamic programming,” IEEE Transactions on Smart Grid, vol. 6, no. 1, pp. 166-177, Jan. 2015. [Baidu Scholar]
M. Mosaad, M. A. El-Raouf, M. Al-Ahmar et al., “Optimal PI controller of DVR to enhance the performance of hybrid power system feeding a remote area in Egypt,” Sustainable Cities and Society, vol. 47, pp. 1-8, May 2019. [Baidu Scholar]
J. Liua, Y. Lia, C. Rehtanz et al., “An OLTC-inverter coordinated voltage regulation method for distribution network with high penetration of PV generations,” Electrical Power and Energy Systems, vol. 113, pp. 991-1001, May 2019. [Baidu Scholar]
W. Hassanein, M. Ahmed, M. A. El-Raouf et al., “Performance improvement of off-grid hybrid renewable energy system using dynamic voltage restorer,” Alexandria Engineering Journal, vol. 59, no. 3, pp. 1567-1581, Jun. 2020. [Baidu Scholar]
Y. Gounder, D. Nanjundappan, and V. Boominathan, “Enhancement of transient stability of distribution system with SCIG and DFIG based wind farms using STATCOM,” IET Renewable Power Generation, vol. 10, no. 8, pp. 1171-1180, Sept. 2016. [Baidu Scholar]
M. Mosaad, “Model reference adaptive control of STATCOM for grid integration of wind energy systems,” IET Electric Power Applications, vol. 12, no. 5, pp. 605-613, May 2018. [Baidu Scholar]
J. Ruan, Z. Lu, Y. Qiao et al., “Analysis on applicability problems of the aggregation-based representation of wind farms considering DFIGs’ LVRT behaviors,” IEEE Transactions on Power Systems, vol. 31, no. 6, pp. 4953-4965, Nov. 2016. [Baidu Scholar]
M. Mosaad, “Direct power control of SRG-based WECSs using optimised fractional-order PI controller,” IET Electric Power Applications, vol. 14, no. 3, pp. 409-417, Mar. 2020. [Baidu Scholar]
N. Hingorani and L. Gyugyi, Understanding FACTS Concepts and Technology of Flexible AC Transmission Systems, New York: Wiley-IEEE Press, 2000. [Baidu Scholar]
M. Mosaad, A. Abu-Siada, and M. Elnaggar, “Application of superconductors to improve the performance of DFIG-based WECS,” IEEE Access, vol. 7, no. 1, pp. 103760-103769, Jul. 2019. [Baidu Scholar]
Y. Alharbi, A. Yunus, and A. A. Siada, “Application of UPFC to improve the LVRT capability of wind turbine generator,” in Proceedings of 22nd Australasian Universities Power Engineering Conference (AUPEC), Bali, Indonesia, Sept. 2012, pp. 26-29. [Baidu Scholar]
A. Abdou, H. Pota, A. Abu-Siada et al., “Application of STATCOM-HTS to improve DFIG performance and FRT during IGBT short circuit,” in Proceedings of Australasian Universities Power Engineering Conference (AUPEC), Perth, Australia, Sept. 2014, pp. 1-5. [Baidu Scholar]
C. Wessels, N. Hoffmann, M. Molinas et al., “STATCOM control at wind farms with fixed-speed induction generators under asymmetrical grid faults,” IEEE Transactions on Industrial Electronics, vol. 60, no. 7, pp. 2864-2873, Jul. 2013. [Baidu Scholar]
M. Navaei, A. Abdoos, and M. Shahabi, “A new control unit for electronic ferroresonance suppression circuit in capacitor voltage transformers,” Electrical Power and Energy Systems, vol. 99, pp. 281-289, Jul. 2018. [Baidu Scholar]
M. Yang, W. Sima, L. Chen et al., “Suppressing ferroresonance in potential transformers using a model-free active-resistance controller,” Electric Power and Energy Systems, vol. 95, pp. 384-393, Feb. 2018. [Baidu Scholar]
T. Mellik, F. Painter, D. Shipp et al., “Proactive study and novel mitigation of MV power system damage due to sub-power-frequency ferro-resonance for a gas plant,” IEEE Transactions on Industry Applications, vol. 54, no. 4, pp. 3991-4000, Jul. 2018. [Baidu Scholar]
Y. Wang, X. Liang, I. Pordanjani et al., “Investigation of ferroresonance causing sustained high voltage at a de-energized 138 kV bus: a case study,” IEEE Transactions on Industry Applications, vol. 55, no. 6, pp. 5675-5686, Nov. 2019. [Baidu Scholar]
E. Bayona, F. Azcondo, C. Brañas et al., “Electronic resistor emulators forferroresonance damping in MV transformers,” IET Renewable Power Generations, vol. 13, no. 1, pp. 201-208, Jul. 2019. [Baidu Scholar]
U. Karaagac, J. Mahseredjian, and L. Cai, “Ferroresonance conditions in wind parks,” Electric Power Systems Research, vol. 138, pp. 41-49, Sept. 2016. [Baidu Scholar]
H. Radmanesh and G. Gharehpetian, “Ferroresonance suppression in power transformers using chaos theory,” Electric Power and Energy Systems, vol. 45, no. 1, pp. 1-9, Feb. 2013. [Baidu Scholar]
H. Radmanesh, “Distribution network protection using smart dual functional series resonance-based fault current and ferroresonance overvoltage limiter,” IEEE Transactions on Smart Grid, vol. 9, no. 4, pp. 3070-3078, Jul. 2018. [Baidu Scholar]
H. Fordoei, H. Heydari, and S. Afsari, “Elimination of chaotic ferroresonance in power transformer by ISFCL,” Electrical Power and Energy Systems, vol. 68, pp. 132-141, Jun. 2015. [Baidu Scholar]
A. Akinrinde, A. Swanson, and R. Tiako, “Dynamic behavior of wind turbine generator configurations during ferroresonant conditions,” Energies, vol. 12, no. 4, pp. 1-12, Feb. 2019. [Baidu Scholar]
M. Siahpoosh, D. Dorrell, and L. Li, “Ferroresonance assessment in a case study wind farm with 8 units of 2 MVA DFIG wind turbines,” in Proceedings of 20th International Conference of Electrical Machines and Systems (ICEMS), Sydney, Australia, Aug. 2017, pp. 1-5. [Baidu Scholar]
J. Marti and A. Soudack, “Ferroresonance in power systems: fundamental solutions,” IEE Proceedings: Generation, Transmission and Distribution, vol. 138, no. 4, pp. 321-329, Jul. 1991. [Baidu Scholar]
S. Mohod and M. Aware, “A STATCOM-control scheme for grid connected wind energy system for power quality improvement,” IEEE Systems Journal, vol. 4, no. 3, pp. 346-352, Sept. 2010. [Baidu Scholar]
Y. Zhang, M. Cheng, and Z. Chen, “Load mitigation of unbalanced wind turbines using PI-R individual pitch control,” IET Renewable Power Generation, vol. 9, no. 3, pp. 262-271, Apr. 2015. [Baidu Scholar]
F. Freijedo, A. Vidal, A. Yepes et al., “Tuning of synchronous-frame PI current controllers in grid-connected converters operating at a low sampling rate by MIMO root locus,” IEEE Transactions on Industrial Electronics, vol. 62, no. 8, pp. 5006-5017, Aug. 2015. [Baidu Scholar]
M. Mosaad and F. Salem, “Adaptive voltage regulation of self-excited induction generator using FACTS controllers,” International Journal of Industrial Electronics and Drives, vol. 1, no. 4, pp. 219-226, Dec. 2014. [Baidu Scholar]
M. Mosaad and H. Ramadan, “Power quality enhancement of grid-connected fuel cell using evolutionary computing techniques,” International Journal of Hydrogen Energy, vol. 43, no. 25, pp. 11568-11582, Jun. 2018. [Baidu Scholar]
E. Nabil, “A modified flower pollination algorithm for global optimization,” Expert System Application, vol. 57, pp. 192-203, Sept. 2016. [Baidu Scholar]
W. Ongsakui and P. Jirapong, “Optimal allocation of FACTS devices to enhance total transfer capability using evolutionary programming,” in Proceedings of IEEE International Symposium on Circuits and Systems, Kobe, Japan, May 2005, pp. 23-26. [Baidu Scholar]
M. Mosaad, A. Alenany, and A. Abu-Siada, “Enhancing the performance of wind energy conversion systems using unified power flow controller,” IET Generation, Transmission & Distribution, vol. 14, no. 10, pp. 1922-1929, May 2020. [Baidu Scholar]
P. Ferracci. (1998, Mar.). Ferroresonance Cahier Technique Schneider no. 190, the Groupe Schneider’s. [Online]. Available: https://www.studiecd.dk/cahiers_techniques/Ferroresonance.pdf [Baidu Scholar]
Mohamed I. Mossad received the B. Sc. and M. Sc. degrees from Zagazig University, Zagazig, Egypt, and the Ph.D. degree from Cairo University, Cairo, Egypt, all in electrical engineering. Currently he is an Associate Professor in the Department of Electrical and Electronic Engineering Technology, Yanbu Industrial College (YIC), Yanbu, Saudi Arabia. He is the Editor-in-Chief for Yanbu Journal of Engineering and Sciences (YJES). His research interests include power system stability, control and renewable energy. [Baidu Scholar]