Abstract
To better utilize the diversity of renewable energies in the U.S., this paper proposes a cross-seam hybrid multi-terminal high-voltage direct current (MTDC) system for the integration of different types of renewable energies in the U.S. Based on a developed station-hybrid converter design, the proposed hybrid MTDC system further investigates the connection methods of renewable energies and develops novel flexible power flow control strategies for realizing uninterrupted integration of renewable energies. In addition, the frequency response control of the hybrid MTDC system is proposed by utilizing the coordination between the converters in the hybrid MTDC system. The feasibility of the hybrid MTDC system and the performance of its corresponding control strategies are conducted in the PSCAD/EMTDC simulation. The simulation results indicate that the proposed hybrid MTDC system could realize the uninterrupted integration of renewable energies and flexible power transmission to both coasts of U.S.
NORTH America features some of the world’s richest hydro, wind, solar, and other types of renewable energy resources [
The location selection of renewable energy generation inevitably depends on the geographical distribution [
At present, the three interconnections of the U.S. power grid, i.e., the Western Interconnection (WI), the Eastern Interconnection (EI), and the Electric Reliability Council of Texas (ERCOT), are almost independently operated with others [

Fig. 1 Modified design based on Interconnection seam study.
For the cross-seam MTDC system shown in
In [
Combining the LCC and VSC technologies, the hybrid HVDC system is an attractive solution to the aforementioned trade-off [
Based on the station-hybrid converter (SHC) proposed in [
1) A novel topology of the hybrid MTDC system is proposed for cross-seam bulk power transmission and integration of large-scale renewable energies.
2) The basic operation control of the hybrid MTDC system and the connection configurations of the renewable energies into a hybrid MTDC system are analyzed.
3) The flexibility of power flow control strategies of the proposed hybrid MTDC system is investigated for realizing the uninterrupted integration of renewable energies.
4) The frequency response control (FRC) strategies of the proposed hybrid MTDC system are explored for improving the frequency stability of the interconnected power systems.

Fig. 2 Topology of proposed hybrid MTDC system.
The basic control of the SHC in the hybrid MTDC system is shown in

Fig. 3 Basic control of SHC.
The VSC control principle is given by (1)-(5), and the LCC control principle is given by (6)-(10).
1) VSC control:
(1) |
(2) |
(3) |
(4) |
(5) |
where and are the reference values of d- and q-axis currents for SHC, respectively; and are the reference and measured values of DC voltage, respectively; and are the reference and measured values of active power, respectively; is the power order generated from FRC; and are the reference and measured values of reactive power, respectively; and are the d- and q-axis reference voltages on the converter side, respectively; and are the d- and q-axis voltages on the AC system side, respectively; is the AC system angular frequency; is the equivalent reactance of AC system; and are the d- and q-axis currents for SHC, respectively; and are the proportional and integral gains of DC voltage controller, respectively; and are the proportional and integral gains of active power controller, respectively; and are the proportional and integral gains of reactive power controller, respectively; and are the proportional and integral gains of d-axis current controller, respectively; and and are the proportional and integral gains of q-axis current controller, respectively.
2) LCC control:
(6) |
(7) |
(8) |
(9) |
where is the firing angle of the LCC rectifier; is the firing angle of the LCC inverter; is the firing advanced angle of the LCC inverter with CC control; is the firing advanced angle of the LCC inverter with CEA control; is the DC voltage for LCC; is the DC current of LCC rectifier; is the DC current of LCC inverter; is the extinction angle of LCC inverter; is the minimum extinction angle of LCC inverter; and are the proportional and integral gains of current controller for LCC rectifer, respectively; and are the proportional and integral gains of current controller for LCC inverter, respectively; and are the proportional and integral gains of extinction angle controller for LCC inverter, respectively; is the DC current reference of the LCC; is the function for DC current bias control (CBC); and the voltage dependent current order limiter (VDCOL) is given by:
(10) |
Owing to the difference in the put-into-operation time of the renewable energies, the connection configurations for integration of renewable energies into the hybrid MTDC system could be sorted into two configurations: direct connection to the hybrid MTDC system and double connection to MTDC system, as shown in

Fig. 4 Connection configurations for integration of renewable energies into hybrid MTDC system. (a) Direct connection. (b) Double connection to MTDC system.
The application scenario of renewable energies direct connection to the hybrid MTDC system with the REC converters mainly includes the newly-installed renewable energies such as offshore wind farm, which are usually in a passive network. In this configuration, the REC converters work at constant FRC and constant AC voltage control to provide stable frequency and AC voltage references for wind turbine (WTs). The basic control logic of REC converter in direct connection configuration is shown in

Fig. 5 Basic control logic of REC converter in direct connection configuration.
The control principle for REC converter in direct connection configuration is given by (11) and (12).
(11) |
(12) |
where and are the reference values of d- and q-axis currents for REC converter in direct connection configuration, respectively.
For the operating renewable energy projects, adopting the direct connection configuration to replace the existed AC connection is wasteful and unpractical. Considering the flexibility of the hybrid MTDC system, in this paper, the double connection configuration to MTDC system is proposed for the existing renewable energy project to improve their controllability and stability. In this configuration, the renewable energy projects connect to the hybrid MTDC system via a DC intertie while keeping the connection to the AC system. This configuration could significantly optimize the power flow distribution of the renewable energies, thereby reducing the potential power congestion in their connected AC system and improving the operating economy.
Different from the direct connection configuration for the integration of renewable energies, in the double connection configuration, the REC converter could work at CAPC to realize the accuracy control of power injection to the hybrid MTDC system. In addition, the REC converter in the double connection configuration needs to have the ability to provide frequency and AC voltage references under the AC connection outage, for guaranteeing the operation stability of the renewable energy generations under the contingencies. Considering the control requirements of the REC converter in the double connection configuration, the power synchronization loop (PSL) is implemented for the REC converter control. The basic control logic of the REC converter in double connection configuration is shown in

Fig. 6 Basic control logic of REC converter in double connection configuration.
As shown in
(13) |
(14) |
(15) |
where and are the reference values of d- and q-axis currents for REC converter in double connection configuration, respectively; and and are the reference and measured active power on the PCC bus, respectively.
With the complete basic control structure, the hybrid MTDC system could integrate various types and operation modes of renewable energies. Moreover, the hybrid MTDC system could meet different requirements of the system operator for various operation conditions by the control coordination of multiple terminals. The system-level control strategies of the hybrid MTDC system are introduced in the following sections.
In the analysis of [
According to the potential operation conditions of the hybrid MTDC system for North America cross-seam interconnection, its operation modes could be summarized as

Fig. 7 Operation modes of hybrid MTDC system. (a) East to West. (b) West to East. (c) Renewable energies to both sides.
In the steady state, if the power reference is set smaller than the capacity of LCCs, the power on the hybrid MTDC system only flows through the LCCs. If the power reference is set larger than the capacity of LCCs, the VSCs transmit the rest power of the power reference. This transmission strategy could reduce the transmission loss. Moreover, the VSCs could keep the capacity for supporting emergency operation conditions.
During the operation mode conversion, the hybrid MTDC system must keep the system operation because the integration of renewable energies cannot be terminated.
For satisfying the flexible and uninterrupted integration of renewable energies, a flexible power flow control is proposed in this paper. The flexible power flow control strategies with the example power flow direction changes between SHC1 and SHC2 are shown in

Fig. 8 Flexible power flow control strategies with example power flow direction changes between SHC1 and SHC2. (a) Initial condition. (b) Step I. (c) Step II. (d) Step III.
In

Fig. 9 Operation conditions of RS mechanism. (a) RSa. (b) RSb. (c) RSc. (d) RSd.
As shown in
Moreover, owing to that the integrating capacity of the renewable energies is smaller than the SHC capacity, during the power flow reversal process, the power flow injection of renewable energies is the same as normal operation conditions. Therefore, different from the topology and corresponding control strategies [
The reliability service sharing between the interconnections brings diversity to the service choosing, which benefits both interconnections and their market participators. Owing to the excellent controllability and flexible operation modes, the proposed hybrid MTDC system could provide multiple reliability services, which achieves the adequate employment of the system and creates additional values. Sharing frequency response reserves through the MTDC system is expected to provide large potential benefits to its connected interconnections. Each interconnection could rely, in part, on the spinning reserves, inertia, and governor response of the neighboring interconnection to provide FRS during an event through the proposed hybrid MTDC system. Recent DOE study has also proved that the frequency response sharing could provide 25% of the economic benefits, which is the second large part of the economic benefit behind load diversity [
The advantage of the LCC is that it could provide overload capacity support. According to the practical experience, the long-term overload capacity of the LCC is designed with 10%-20% capacity and the transient overload capacity of LCC could be up to 40%-50% capacity [
(16) |
(17) |
(18) |
(19) |
(20) |

Fig. 10 Control strategy of FRC. (a) Control strategy. (b) Reallocation.
As shown in
Different from the traditional HVDC transmission system, the FRC makes full use of the advantages of a hybrid MTDC system. The regulating range of the hybrid MTDC system at frequency response is enlarged through the overloading capacity of LCC. In addition, the supported power reallocation could reduce the transmission loss after the event, meantime, realizing the fast recovery of the emergency regulating capacity of the VSC can increase the resilience of the hybrid MTDC system to enhance the security against the continuous faults.
In this section, a hybrid MTDC test system, as depicted in
In the initial state, the LCC1 works at CC, the LCC2 works at CEA, and the VSC1 and VSC2 work at CAPC. The reference DC voltage of LCC2 is set as 460 kV in order to keep the DC voltage of the LCC1 at 500 kV (1 p.u.).
The test scenario for the interrupted integration of renewable energies is conducted to verify the integrating capacity of the hybrid MTDC system for renewable energies. In practice, the HVDC system power regulation under the normal operation is slow, which is up to 100 MW/min [

Fig. 11 Performance of hybrid MTDC system in case 1. (a) Voltage. (b) Frequency of PCC with REC2. (c) Active power through SHC1. (d) Active power through SHC2. (e) Active power of REC converters. (f) Active power of renewable energies.
The test scenario for flexible power flow control is conducted to verify that the proposed flexible power flow control could achieve the bidirectional power flow control while realize the uninterrupted integration of renewable energies. In order to shorten the simulation process, the power ramping rate is set as 1000 MW/s, the same as case 1. In this case, the hybrid MTDC system transmits 2500 MW power from SHC1 to SHC2. The REC converters adopt the direct connection configuration for renewable energies. It is assumed that the connected renewable energies work at rated power and the REC converters transmit 1500 MW power to SHC2. The operation sequence of the proposed flexible power flow control of the hybrid MTDC system is as follows.
1) s-3.5 s, the LCC1 decreases from 2500 MW to the minimum value with a constant ramping rate, then the LCC1 is blocked.
2) s-4.5 s, the LCC1 is disconnected from the MTDC system by the mechanical switch, then the voltage polarity of LCC1 is reversed via RS mechanism. After the voltage polarity reversal, the LCC1 is reconnected to the MTDC system.
3) s-5.0 s, the LCC2 changes to CC and the power order adopts its operation power, and the VSC2 changes to CDVC to control the DC voltage. Then, LCC2 decreases to the minimum value while LCC1 is unblocked and increases with the same ramping rate until LCC2 is automatically blocked.
4) s-6.0 s, the LCC2 is disconnected from the MTDC system by the mechanical switch, then the voltage polarity of LCC2 is reversed via RS mechanism. At the same time, the LCC1 further increases power until the power flow through the REC converters is transmitting to SHC1.
5) s-9.5 s, the LCC2 is reconnected to the MTDC system with a mechanical switch. The LCC2 is unblocked and the LCC2 changes its operation mode to CEA. Meantime, the VSC2 also changes its operation mode to CDVC, and the power order adopts its operation power. Then the LCC1, VSC1, and VSC2 increase the active power to the power reference.

Fig. 12 Performance of hybrid MTDC system in case 2. (a) DC voltage. (b) Active power through SHC1. (c) Active power through SHC2. (d) Active power of REC converters.
The test scenario for FRC is implemented to verify the regulating range and flexible controllability of the hybrid MTDC system under contingencies. The initial condition is as follows. Before s, the hybrid MTDC system transmits 2000 MW power from SHC1 to SHC2 and the output of renewable energy is 1500 MW. At s, a 1000 MW generator is tripped at East. In this case, the response of the generator in the interconnections is not considered. In practice, the power regulation of HVDC system under the event could be up to 200 MW/s [
1) -3.75 s, since the support power direction of the FRC is the same as the power flow direction of the hybrid MTDC system but the VSC2 has reached its maximum value 1000 MW, for meeting the support requirement, the VSC1 increases the power from 0 MW to 1000 MW (the maximum capacity). Although the power increase is over the capacity of LCC2, owing to the overloading capacity of LCC, the power flow through the LCC2 could be increased from 2200 MW to 3200 MW.
2) s-7.0 s, when the frequency is stable, the reallocation control in FRC is activated. The VSC1 decreases its power from 1000 MW to 0 MW, and at the same time, the LCC1 increases its power from 2000 MW to 3000 MW. The ramping rates of the power increase of VSC and the power decrease of LCC are 1000 MW/s, which is the normal power regulation rate.

Fig. 13 Performance of hybrid MTDC system in case 3. (a) Frequency and DC voltage. (b) Active power through SHC1. (c) Active power through SHC2. (d) Active power of REC converters.
As shown in the simulation results, with the proposed FRC, the frequency nadir is significantly improved, which prevents the distributed system from working into an unacceptable condition. In addition, due to the LCC overloading capacity, the LCC2 could keep the 3200 MW until the generation of renewable energies reduces or the power flow dispatch is adjusted by the dispatching center. Moreover, the DC voltage of the hybrid MTDC system is still stable during the FRC process. It indicates that the frequency response support does not influence the normal operation of hybrid MTDC system. In addition, it could be seen from
A hybrid MTDC transmission system is proposed in this paper for increasing the utilization and penetration of the national abundant renewable energies in the U.S. The main contributions of the paper are as follows.
1) Cost-effective bulk-power transmission
The capacity ratio between the LCC and VSC in the SHC is determined by system design requirements, and the rated capacity of LCC could be 2-3 times that of VSC. Therefore, the hybrid MTDC system could be cost-affordable for long-distance bulk power transmission system with intermediate converter stations for the integration of large-scale renewable energies.
2) Flexible delivery of large-scale renewable energies
The hybrid MTDC system could realize the flexible and interruptible power delivery of the interconnected renewable energies to SHC on either side or SHCs on both sides.
3) Flexible operation modes
With the co-existence of the LCC and VSC in both two SHCs, there is a flexible choice of operation modes of the proposed hybrid MTDC system. It could work as a full LCC system (blocking the VSCs in both two SHCs), full VSC system (blocking the LCCs in both two SHCs), terminal-hybrid system (blocking LCC in one SHC while blocking VSC in the other SHC), and pole-hybrid system (one pole only connected with LCCs and the other pole connected with VSCs).
4) Ancillary sharing between interconnections
The advantage of the LCC is that it could provide over-capacity support by its inherent overloading capacity, and the VSC could realize the fast power flow reversal and reactive power support. The hybrid MTDC system could combine both advantages of LCC and VSC at frequency responses, thereby providing a better frequency regulation service to the interconnections.
In future work, the DC fault ride-through capability of the proposed hybrid MTDC system, and the coordinated control of SHCs and renewable power plants connected to the hybrid MTDC system will be investigated.
References
IRENA. (2021, Apr.). North America renewable source. [Online]. Available: https://www.irena.org/northamerica [Baidu Scholar]
C2ES. (2021, Apr.). Renewable energy. [Online]. Available: https://www.c2es.org/content/renewable-energy/ [Baidu Scholar]
K. Sun, K. Li, W. J. Lee et al., “VSC-MTDC system integrating offshore wind farms based optimal distribution method for financial improvement on wind producers,” IEEE Transactions on Industry Applications, vol. 55, no. 3, pp. 2232-2240, May-Jun. 2019. [Baidu Scholar]
NREL. (2021, Apr.). Wind maps. [Online]. Available: https://www.nrel.gov/gis/wind.html [Baidu Scholar]
NREL. (2021, Apr.). Solar maps. [Online]. Available: https://www.nrel.gov/gis/solar.html [Baidu Scholar]
H. Zhao, Q. Wu, S. Hu et al., “Review of energy storage system for wind power integration support,” Applied Energy, vol. 137, pp. 545-553, Jan. 2015. [Baidu Scholar]
NREL. (2021, Apr.). Interconnections seam study. [Online]. Available: https://www.nrel.gov/analysis/seams.html [Baidu Scholar]
D. Jovcic and K. Ahmed. High Voltage Direct Current Transmission: converters, Systems and DC grids. New York: John Wiley & Sons, 2015. [Baidu Scholar]
W. Yang, B. Zeng, and Y. Jia, “Simulation analysis of split connection mode system control for XiMeng to TaiZhou UHVDC project,” in Procedings of 2018 International Conference on Power System Technology (POWERCON), Guangzhou, China, Nov. 2018, pp. 2972-2977. [Baidu Scholar]
A. Egea-Alvarez, S. Fekriasl, F. Hassan et al., “Advanced vector control for voltage source converters connected to weak grids,” IEEE Transactions on Power Systems, vol. 30, no. 6, pp. 3072-3081, Nov. 2015. [Baidu Scholar]
H. Xiao, Z. Xu, G. Tang et al., “Complete mathematical model derivation for modular multilevel converter based on successive approximation approach,” IET Power Electronics, vol. 8, no. 12, pp. 2396-2410, Dec. 2015. [Baidu Scholar]
M. H. Nguyen, T. K. Saha, and M. Eghbal, “Master self-tuning VDCOL function for hybrid multi-terminal HVDC connecting renewable resources to a large power system,” IET Generation, Transmission & Distribution, vol. 11, no. 13, pp. 3341-3349, Oct. 2017. [Baidu Scholar]
H. Xiao, K. Sun, J. Pan et al., “Review of hybrid HVDC Systems combining line communicated converter and voltage source converter,” International Journal of Electrical Power & Energy Systems, vol. 129, pp. 106713, Jul. 2021. [Baidu Scholar]
H. Xiao, K. Sun, J. Pan et al., “Operation and control of hybrid HVDC system with LCC and full-bridge MMC connected in parallel,” IET Generation, Transmission & Distribution, vol. 14, no. 7, pp. 1344-1352, Jan. 2020. [Baidu Scholar]
HVDC News China. (2021, Apr.). Luxi hybrid BTB converter station. [Online]. Available: https://hvdcnewschina.blogspot.com/2017/09/luxi-hybrid-btb-converter-station.html [Baidu Scholar]
B. Qahraman, A. M. Gole, and I. Fernando, “Hybrid HVDC converters and their impact on power system dynamic performance,” in Proceedings of 2006 IEEE Power Engineering Society General Meeting, Montreal, Canada, Oct. 2006, pp. 1-6. [Baidu Scholar]
Z. Xu, S. Wang, and H. Xiao, “Hybrid high-voltage direct current topology with line commutated converter and modular multilevel converter in series connection suitable for bulk power overhead line transmission,” IET Power Electronics, vol. 9, no. 12, pp. 2307-2317, Oct. 2016. [Baidu Scholar]
X. Chen, H. Sun, J. Wen et al., “Integrating wind farm to the grid using hybrid multiterminal HVDC technology,” IEEE Transactions on Industry Applications, vol. 47, no. 2, pp. 965-972, Mar.-Apr. 2011. [Baidu Scholar]
K. Sun, H. Xiao, J. Pan et al., “A station-hybrid HVDC system structure and control strategies for cross-seam power transmission,” IEEE Transactions on Power System, vol. 36, no. 1, pp. 379-388, Jan. 2021. [Baidu Scholar]
Y. Guo, H. Gao, and Q. Wu, “A combined reliability model of VSC-HVDC connected offshore wind farms considering wind speed correlation,” IEEE Transactions on Sustainable Energy, vol. 8, no. 4, pp. 1637-1646, Oct. 2017. [Baidu Scholar]
Y. Jiang-Häfner and Ludvika, “HVDC system and method to control a voltage source converter in a HVDC system,” U.S. Patent 20090279328 A1, Nov. 12, 2009. [Baidu Scholar]
W. Xiang, W. Lin, L. Xu et al., “Enhanced independent pole control of hybrid MMC-HVDC system,” IEEE Transactions on Power Delivery, vol. 33, no. 2, pp. 861-872, Apr. 2018. [Baidu Scholar]
H. Rao, W. Wei, T. Miao et al., “Frequency control at the power sending side for HVDC asynchronous interconnections between Yunnan power grid and the rest of CSG,” CSEE Journal of Power and Energy Systems, vol. 7, no. 1, pp. 105-113, Jan. 2021. [Baidu Scholar]
M. Szechtman, T. Wess, and C.V. Thio, “First benchmark model for HVDC control studies,” Electra, vol. 135, pp. 54-73, Apr. 1991. [Baidu Scholar]
M. Guan and Z. Xu, “Modeling and control of a modular multilevel converter-based HVDC system under unbalanced grid conditions,” IEEE Transactions on Power Electronics, vol. 27, no. 12, pp. 4858-4867, Dec. 2012. [Baidu Scholar]
P. Belkin, “HVDC and power electronic systems for overhead line and insulated cable applications,” in Proceedings of 2012 CIGRE San Francisco Colloquium, San Francisco, USA, Mar. 2012, pp. 1-6. [Baidu Scholar]