Abstract
Secondary earth faults occur frequently in power distribution networks under harsh weather conditions. Owing to its characteristics, a secondary earth fault is typically hidden within the transient of the first fault. Therefore, most researchers tend to focus on a feeder with single fault while disregarding secondary faults. This paper presents a fault feeder identification method that considers secondary earth faults in a non-effectively grounded distribution network. First, the wavelet singular entropy method is used to detect a secondary fault event. This method can identify the moment at which a secondary fault occurs. The zero-sequence current data can be categorized into two fault stages. The first and second fault stages correspond to the first and secondary faults, respectively. Subsequently, a similarity matrix containing the time-frequency transient information of the zero-sequence current at the two fault stages is defined to identify the fault feeders. Finally, to confirm the effectiveness and reliability of the proposed method, we conduct simulation experiments and an adaptability analysis based on an electromagnetic transient program.
THE neutral point of the 6 kV to 66 kV power grid in China is generally either not grounded or grounded by arc-suppression coils. Therefore, the distribution network is also known to be non-effectively grounded [
Many relevant studies regarding feeder fault identification have been conducted. State-of-the-art studies on this topic can be categorized into two groups [
Under the conditions of harsh weather or deteriorated insulation, secondary earth faults occur frequently [
1) The proposed method focuses on secondary earth faults that occur in the same phase but with different feeders in a non-effectively grounded distribution network. Moreover, the features of the transient zero-sequence current of secondary earth faults are analyzed.
2) The peak of the wavelet singular entropy increment is defined as the criterion for identifying the fault time of a secondary earth fault. In addition, the fault process can be categorized into two stages. The first and second stages are for the first and secondary faults, respectively.
3) The similarity matrix contains separate time-frequency information of the fault for the two steps and must be defined to identify the fault feeders. The proposed method can reveal the development process of the fault and correctly identify the origin of the feeder with secondary earth fault.
4) The feeder identification method proposed herein is suitable not only for secondary earth faults, but also for a single-phase grounded fault, rendering it adaptable to different fault scenes.
The remainder of this paper is organized as follows. Section II provides an analysis of the features of the transient zero-sequence current of secondary earth faults. In Section III, the scheme and algorithm of fault feeder identification are presented. The method is tested via simulation, and the associated assessments under different fault conditions are introduced in Section IV. Finally, a brief conclusion is presented in Section V.
When a single-phase-to-ground fault F1 occurs in feeder k of the resonant grounded network, the transient grounding current , as shown in
(1) |

Fig. 1 Current distribution of single-phase grounded fault in resonant grounded distribution network.
where and are the magnitudes of the capacitive and inductive currents, respectively; is the power angular frequency; is the initial phase angle of the phase voltage at the fault time; is the angular frequency of the free oscillation component; and and are the time constants of the capacitance and inductance loops, respectively. In (1), the first part is the steady-state component of the transient grounding current, which is the difference between the steady-state capacitive current and steady-state inductive current. The second and third parts are the transient components of the transient grounding current, which is the sum of the transient free oscillation component of the capacitor current and the transient direct current component of the inductive current. As the two transient currents may be superimposed on each other, the amplitude of is substantially increased.
In
When the secondary earth fault F2 occurs in feeder 1, based on the fault conditions shown in

Fig. 2 Simplified diagram of zero-sequence network for single-phase-to-ground fault with secondary faults.

Fig. 3 Equivalent circuit of zero-sequence network.
Therefore, the zero-sequence current after the secondary earth fault F2 can be expressed as:
(2) |
where is the zero-sequence current; and and are the line impedances of feeders with the first and secondary faults, respectively.
In (2), is similar to because the secondary earth faults occur in the same phase but from different feeders. The zero-sequence current is extremely small. Therefore, it is difficult to detect the feeder with secondary fault. The waveforms of the zero-sequence current with secondary faults in a resonant grounded network with four feeders are presented in

Fig. 4 Waveforms of zero-sequence current with secondary faults.
In
Although it is difficult to detect the amplitude of the transient zero-sequence current of the secondary fault, the two fault transient components are in the fault current. A new source is added to the first state, resulting in more complex modes of the transient signal, as shown in (2). Therefore, the complexity of the fault network increases after the occurrence of a secondary fault.
Based on the analysis of secondary faults, an indicator is necessitated to quantify the complexity of the zero-sequence current for detecting secondary faults. In this paper, the wavelet singular entropy (WSE) is used to assess the complexity of the transient signal in different fault states. The analyzed zero-sequence current is expressed as a time sequence containing N samples. Next, a wavelet decomposition matrix with orders can be obtained via a wavelet transform. Based on the singular value decomposition theory for signals, the calculated diagonal elements are singular values . Therefore, WSE can be expressed as [
(3) |
where is the incremental WSE of the
(4) |
where is the WSE of the

Fig. 5 WSE of zero-sequence currents. (a) Feeder 1. (b) Feeder 2. (c) Feeder 3. (d) Feeder 4.
The value of the entropy varies with the sliding window, where the two feeders with the closest WSE are selected as the basis for detecting secondary faults.
(5) |
where is the similarity of WSE between feeder and feeder ; and WSEi and WSEj are the WSE of feeder i and feeder j, respectively. Feeder and feeder are any two feeders from the bus. As shown in
(6) |
where is the time of the data window; ; and . As shown in
Based on the detection result of the secondary fault, the fault-time interval can be categorized into two stages. The first stage is for the first single-phase-to-ground fault, whereas the second stage is for the second single-phase-to-ground fault, where is the first fault occurrence time, which typically depends on the zero-sequence voltage exceeding the threshold value [
(7) |
Therefore, based on (7), the time-frequency matrix at the two stages of each feeder can be obtained as:
(8) |
where and are the time-frequency matrices at the first and second stages of the feeder , respectively. The similarity matrix PP can be defined as:
(9) |
where and are the similarities of feeder k and arbitrary feeder j at the first and second stages, respectively; and are the maximum values of the similarity between feeder k and the other feeder at the first and second stages, respectively; and is the total number of feeders. The formula used for this calculation is presented in (10).
(10) |
where is the similarity of time-frequency matrices between feeder and feeder ; and are the elements of time-frequency matrices of feeder and feeder , respectively; and and N are the rows and columns of the time-frequency matrices, respectively. The similarity matrix defined in (9) can be used to identify fault feeders. refers to the value of column of any row in the matrix . If is closer to 1, the feeder is more likely to be a healthy feeder. Otherwise, if the value of is smaller, the feeder is more likely to be a fault feeder. To identify the fault feeder, is compared with a threshold , which is equal to zero in this paper.
The flow chart of the proposed fault line identification process in the distribution network considering secondary faults is shown in

Fig. 6 Flow chart of proposed fault feeder identification process.
The detailed procedures for this process are as follows.
Step 1: when the zero-sequence voltage exceeds the threshold , the fault feeder identification program is initiated. Typically, the fault threshold is set to be 15% of the phase voltage.
Step 2: the process moves into the secondary fault detection stage. The zero-sequence current of each feeder is extracted in two cycles. The wavelet decomposition matrix D is obtained using a wavelet transform.
Step 3: the WSE is calculated using a sliding data window, and the sequence of each feeder is obtained. Subsequently, the root-mean-square (RMS) error of for any two feeders is calculated, and two feeders with the minimum RMS error are selected. The time of the secondary fault at which the value of the entropy increases the most is extracted, and this time is labelled as the second peak of the WSE. If a secondary fault cannot be detected, jump to Step 6.
Step 4: the time section is categorized into two steps, and , and the similarity matrix PP is calculated. If , feeder i is the fault feeder at the first fault stage. Otherwise, feeder i is a healthy feeder. If all , then the first fault occurs on the bus.
Step 5: continue to assess . If , feeder j is the fault feeder at the secondary fault stage. Otherwise, feeder j is a healthy feeder. If all , it implies that a secondary fault occurs on the bus.
Step 6: in the time section , the similarity matrix is calculated, where is a one-dimensional sequence. is defined as the similarity sequence in the condition without secondary fault. If , feeder i is the fault feeder. Otherwise, feeder i is a healthy feeder. If all , it implies that a fault occurs on the bus.
The PSCAD/EMTDC simulation model used for a typical 35 kV distribution network with a resonant grounded network is shown in

Fig. 7 35 kV distribution network with resonant grounded system.
Six feeders are used in the system, in addition to three overhead lines of 15, 7, and 8 km, and two cable lines of 10 and 6 km. One line includes an overhead line of 5 km and a cable line of 5 km. The zero-sequence parameters of the overhead line are and . The zero-sequence parameters of the cable line are and . For Petersen coil grounding methods, the system is set to overcompensate with an overcompensation degree of 108%. Based on the distribution capacitance of the system to the ground, the Petersen coil inductance L can be calculated using (11), where Call is the equivalent capacitance of total transmission lines. The active power loss of the Petersen coil is 3% of the inductance power loss. Hence, the series resistance can be calculated as:
(11) |
(12) |
To verify the effectiveness of the fault feeder identification method that considers secondary faults, a phase-grounded fault is generated in feeder 1 at 0.215 s, and a secondary fault is generated in feeder 3 at 0.225 s with the same phase. The resistance of each fault is 50 . If the fault feeder identification is performed without the detection of a secondary fault, the similarity index of the time-frequency matrices is used to detect the first fault feeder. The time-frequency matrices of every feeder in one cycle can be calculated as shown in
(13) |

Fig. 8 Time-frequency matrices of every feeder in one cycle. (a) Feeder 1. (b) Feeder 2. (c) Feeder 3. (d) Feeder 4. (e) Feeder 5. (f) Feeder 6.
In this case, only feeder 1 is identified as the fault feeder. Based on the proposed process of fault feeder identification in which the secondary faults are considered, the WSE of every feeder is shown in
(14) |

Fig. 9 WSE of zero-sequence currents considering secondary fault. (a) Feeder 1. (b) Feeder 2. (c) Feeder 3. (d) Feeder 4. (e) Feeder 5. (f) Feeder 6.

Fig. 10 Time-frequency matrices of every feeder at both fault stages. (a) First fault stage. (b) Second fault stage.
The proposed method focuses on secondary faults, which often occur under harsh weather conditions. However, single-phase-to-ground fault occurs frequently in a distribution network. To verify the effectiveness of the fault feeder identification method, a single-phase-to-ground fault is generated in feeder 1 at 0.215 s, and the fault resistance is 100 . The WSE is shown in
(15) |

Fig. 11 WSE of zero-sequence with single fault. (a) Feeder 1. (b) Feeder 2. (c) Feeder 3. (d) Feeder 4. (e) Feeder 5. (f) Feeder 6.
Since , feeder 1 can be regarded as the fault feeder. Based on the simulation analysis above, the feeder identification method is not only suitable for secondary earth faults, but also for a single-phase-to-ground fault, rendering it adaptable to different fault scenes.
The detection results of the secondary faults with different initial fault angles of the fault feeders are shown in
(16) |
Hence, feeders 4 and 5 are detected as the fault feeders at the first and second fault stages, respectively.
Additionally, the proposed method is suitable for bus faults and high-impedance faults (HIFs), as detailed in

Fig. 12 WSE of zero-sequence currents with bus faults. (a) Feeder 1. (b) Feeder 2. (c) Feeder 3. (d) Feeder 4. (e) Feeder 5. (f) Feeder 6.
As the WSEs of feeders 5 and 6 are the most similar, the
(17) |
Based on the criterion , feeder 1 is regarded as the fault feeder at the first fault stage. At the second fault stage, none of the feeders exhibit a value less than 0 in the time-frequency matrices PP. Thus, we can conclude that a secondary fault occurs at bus M.
Notably, two parameters exhibit values less than 0 in some cases, whereas only one parameter exhibits a value less than 0 in some cases at the second fault stage. This is because two fault feeders are used at the second fault stage, one for the first fault stage and the other for the second fault stage. If the fault transient produced from the first fault stage continues to the second fault stage, the values of the two parameters will be less than 0 in . Otherwise, if the fault transient produced from the first fault has been attenuated to a certain extent, only one secondary fault feeder will be detected at the second fault stage. In fact, the transient duration and magnitude are affected by the fault resistance, fault time, and transmission lines. Therefore, the number of parameters less than 0 in depends on the transient component at the first fault stage.
However, regardless of whether contains the fault feeder at the first fault stage, it will have one element whose value is less than 0, which thereby corresponds to the fault feeder of the secondary fault. Combined with , we can obtain the development process of the secondary fault.
This section presents the detection of secondary faults with different grounding resistance values. As shown in
This subsection presents the detection of secondary faults under noisy conditions. The faults occur in feeders 1 and 2. The Gaussian white noise (10-70 dB) is added to the simulation signal. The results in
The time at which the secondary fault occurs is detected using the WSE. The result shows that the detected time deviated from the actual fault time. As shown in
However, if the time at which the secondary fault is detected lags behind the actual fault time, the error may affect the accuracy of identification of the secondary fault feeder. As shown in
A fault feeder identification method that considers secondary earth faults in a non-effectively grounded system is proposed herein. The proposed method can be categorized into two processes: fault time detection of secondary earth faults using WSE, and fault feeder identification using a time-frequency similarity matrix. A simulation model with six feeders of a resonant grounded system in PSCAD/EMTDC is used to test the proposed method. The simulation results indicate that the proposed method can overcome the effects of differences in the initial phase angle and fault resistance. Moreover, the method demonstrates excellent anti-noise ability.
However, if the time at which the secondary fault is detected lags behind the actual fault time by 2% or more, the accuracy of secondary fault feeder identification may be affected. Therefore, by reducing the time window length to improve the detection accuracy of the secondary fault time, the misidentification of a fault feeder with a secondary fault can be reduced.
REFERENCES
J. Chen, E. Chu, Y. Li et al., “Faulty feeder identification and fault area localization in resonant grounding system based on wavelet packet and bayesian classifier,” Journal of Modern Power Systems and Clean Energy, vol. 8, no. 4, pp. 760-767, Jul. 2020. [Baidu Scholar]
T. Zhang, C. Wang, F. Luo et al., “Analytical calculation method of reliabilty sensitivity indexes for distribution systems based on fault incidence matrix,” Journal of Modern Power Systems and Clean Energy, vol. 8, no. 2, pp. 325-333, Mar. 2020. [Baidu Scholar]
Y. Wang, X. Yin, W. Xu et al., “Fault line selection in cooperation with multi-mode grounding control for the floating nuclear power plant grid,” Protection and Control of Modern Power Systems, vol. 5, no. 16, pp. 1-10, Jul. 2020. [Baidu Scholar]
S. Zhang, Z. He, and R. Mai, “Single-phase-to-ground fault feeder identification based on the feature between voltage and integration of current,” IEEJ Transactions on Electrical and Electronic Engineering, vol. 12, pp. 683-691, May 2017. [Baidu Scholar]
X. Lin, J. Sun, I. Kursan et al., “Zero-sequence compensated admittance based faulty feeder selection algorithm used for distribution network with neutral grounding through Peterson-coil,” Electrical Power and Energy Systems, vol. 63, pp.747-752, Jun. 2014. [Baidu Scholar]
Y. Du, Y. Liu, Q. Shao et al., “Single line-to-ground faulted line detection of distribution systems with resonant grounding based on feature fusion framework,” IEEE Transactions on Power Delivery, vol. 34, no. 4, pp. 1766-1775, Aug. 2019. [Baidu Scholar]
P. Liu and C. Huang, “Detecting single-phase-to-ground fault event and identifying faulty feeder in neutral ineffectively grounded distribution system,” IEEE Transactions on Power Delivery, vol. 33, no.5, pp. 2265-2272, Oct. 2018. [Baidu Scholar]
X. Dong and S. Shi, “Identifying single-phase-to-ground fault feeder in neutral non-effectively grounded distribution system using wavelet transform,” IEEE Transactions on Power Delivery, vol. 23, no.4, pp. 1829-1837, Oct. 2008. [Baidu Scholar]
H. Hasanvand and A. Parastar, “A comparison between S-transform and CWT for fault location in combined overhead line and cable distribution networks,” in Proceedings of 21st Electrical Power Distribution Networks Conference, Karaj-Alborz, Iran, May 2016, pp. 70-74. [Baidu Scholar]
X. Han, Q. Wu, M. Li et al., “Mathematical morphology-based single phase-to-ground fault feeder selector for a resonant grounded distribution system,” IEEJ Transactions on Electrical and Electronic Engineering, vol. 13, pp. 517-518. May 2018. [Baidu Scholar]
Z. Guo, J. Yao, and Z. Tan, “Hilbert-Huang transform-based transient busbar protection algorithm,” IET Generation, Transmission & Distribution, vol. 9, no. 4, pp. 2032-2039, Oct. 2015. [Baidu Scholar]
Y. Xue, X. Chen, H. Song et al., “Resonance analysis and faulty feeder identification of high-impedance faults in resonant grounding system,” IEEE Transactions on Power Delivery, vol. 32, no. 3, pp. 1545-1555, Jan, 2017. [Baidu Scholar]
M. Guo, S. Liu, and G. Yang, “A novel approach to detect fault lines in distribution network using similarity recognition based on time-frequency spectrum,” Proceeding of the CSEE, vol. 33, no. 19, pp. 183-190, Oct. 2013. [Baidu Scholar]
I. Kiaei and S. Lotfifard, “Fault section identification in smart distribution systems using multi-source data based on fuzzy Petri nets,” IEEE Transactions on Smart Grid, vol. 11, no. 1, pp. 74-83, Jan. 2020. [Baidu Scholar]
X. Wang, J. Gao, M. Chen et al., “Faulty line detection method based on optimized bistable system for distribution network,” IEEE Transactions on Industrial Informatics, vol. 14, no. 4, pp. 1370-1380, Apr. 2018. [Baidu Scholar]
W. Zhang, G. Song, M. Wu et al., “Application of parameter identification in secondary single-phase grounding fault detection of 10 kV small current grounding system,” Distribution & Utilization, vol. 4, pp. 72-78, Jun. 2017. [Baidu Scholar]
B. Jiang, X. Dong, and S. Shi, “Application of approximate entropy to cross-country fault detection in distribution network,” Power System Protection and Control, vol. 43, no. 17, pp. 15-21, Sept. 2015. [Baidu Scholar]
A. Codino, F. M. Gatta, and R. Calone, “Detection of cross-country faults in medium voltage distribution ring lines,” in Proceedings of 2017 AEIT International Annual Conference, Cagliari, Italy, Sept. 2017, pp. 1-6. [Baidu Scholar]
R. Burgess and A. Ahfock, “Minimizing the risk of cross-country faults in systems using arc suppression coils,” IET Generation, Transmission & Distribution, vol. 5, no.7, pp. 703-711, Jul. 2011. [Baidu Scholar]
J. Wang, “The fault detection of the simultaneous SLG in two distribution feeders,” Heilongjiang Power Technology, vol. 13, no. 5, pp. 281-282, May 1999. [Baidu Scholar]
X. Dong, B Su, and S. Shi, “Cross-country disturbance information and its application in relay protection,” Automation of Electric Power Systems, vol. 28, no. 2, pp. 21-25, Jan. 2004. [Baidu Scholar]
Y. Xue, Y. Xie, and F. Wen, “A review on cascading failures in power systems,” Automation of Electric Power Systems, vol. 37, no. 19, pp. 1-9, Oct. 2013. [Baidu Scholar]
Z. He, X. Chen, and G. Luo, “Wavelet entropy measure definition and its application for transmission line fault detection and identification (part i: definition and methodology),” in Proceedings of 2006 International Conference on Power System Technology, Chongqing, China, Oct. 2006, pp. 22-26. [Baidu Scholar]
N. Peng, K. Ye, R. Liang et al., “Single-phase-to-earth fault feeder detection in power distribution network based on amplitude ratio of zero-mode transients,” IEEE Access, vol. 7, pp. 117678-117691, Aug. 2019. [Baidu Scholar]
R. Liang, N. Peng, Z. Yang et al., “A novel single-phase-to-earth fault location method for distribution network based on zero-sequence components distribution characteristics,” International Journal of Electrical Power and Energy Systems, vol. 102, pp. 11-22, Nov. 2018. [Baidu Scholar]
M. G, S. Liu, and G. Yang, “A new approach to detect fault lines in distribution network using similarity recognition based on time-frequency spectrum,” Proceeding of the CSEE, vol. 33, no. 19, pp. 183-190, Oct. 2013. [Baidu Scholar]