Evaluation Method and Probabilistic Index of Voltage Sag Severity Considering Point-on-wave  PDF

  • Guopei Wu 1
  • Qing Zhong 2
  • Qizhang He 2
  • Zhong Xu 1
Guangzhou Power Supply Bureau Cooperation, Guangzhou, China; School of Electric Power, South China University of Technology, Guangzhou, China

Updated:2021-05-19

DOI:10.35833/MPCE.2019.000470

  • Full Text
  • Figs & Tabs
  • References
  • Authors
  • About
OUTLINE

Abstract

The impact of voltage sag on sensitive devices is related to the time when the sag occurs. However, the point-on-wave of a sag is uncertain. Therefore, this paper presents a novel approach to evaluate the voltage sag severity considering a random point-on-wave. First, the uncertainty of equipment malfunction is revealed. Second, under a given residual voltage, the relationship between the point-on-wave and the duration that the device can withstand is described with a fitting curve. Third, a voltage sag probabilistic index is proposed to describe the severity. The evaluation procedure is also presented. Finally, three types of releasers are tested and analyzed to determine the effectiveness of the proposed method. The evaluation method can help instruct electrical engineers establish more well-grounded sag mitigation proposals.

I. Introduction

VOLTAGE sag is defined as a decrease of between 0.1 and 0.9 p.u. in root mean square (RMS) voltage or current at the power frequency for a duration of 0.5 cycle to 1 min [

1]. Voltage sag often leads to equipment malfunction, substantial economic losses, and even casualties, causing increasing concern [2], [3]. In order to assure optimal operation of production lines, it is critical to evaluate the voltage sag severity of a supply system so that specific mitigation proposals can be designed. The severity of voltage sag is determined by characteristics such as residual voltage, duration, and point-on-wave [4]-[6]. Moreover, the performance during a voltage sag varies as the sag characteristics change, which poses a problem for sag mitigation. The equipment may also have different sensitivities to voltage sag. Thus, it is crucial to establish an evaluation method of voltage sag severity.

The voltage sag severity is co-determined by factors including the sag type, residual voltage amplitude, duration, reclosing time, and sensitivity of the electrical equipment. Existing studies on voltage sag severity indices mainly focus on residual voltage and duration. Other voltage sag characteristics are seldom mentioned in most of the literature. A few studies consider the existing standards and define a voltage severity index by comparing the residual voltage or duration value with a reference value, considering equipment sensitivity. In [

7], the relationship among multiple voltage sag magnitudes and cumulative durations is demonstrated by establishing a voltage duration curve. The researcher put forward a voltage sag severity index by superposing the sensitivity of multiple voltage sag duration intervals. In [8], the IEEE Std 1564-2014 Guide for voltage sag indices is used to assess voltage sag severity. In [9], voltage sags are identified by using a stochastic approach based on simulation results. An index is proposed considering sag frequency, residual voltage, and duration, which is used to identify the weak areas of the network that are exposed to disruptive voltage sags. Some studies have proposed a comprehensive index considering the power system and consumer equipment [10]-[12]. However, the behavior of certain equipment is affected by the point-on-wave in addition to the residual voltage sag magnitude and duration [13]. The assessment will be more precise if more influential sag characteristics are considered. Moreover, the equipment performs differently under various voltage sags, which leads to uncertainty in equipment malfunction [14]. To account for this uncertainty, various methods have been used to evaluate equipment sensitivity to voltage sag, including probabilistic methods [15], [16] and fuzzy logic [17]. Probabilistic methods possess the advantages of less computation and straightforward results and are exploited to evaluate voltage sag severity.

This paper first analyzes the uncertainty of equipment malfunction under voltage sag. The relationship between the point-on-wave and duration is revealed and fitted as a function based on an abundance of test data. With the fitting function, a probabilistic index for voltage sag severity is proposed to evaluate the effect of voltage sag on sensitive devices. Three kinds of ABB releasers are tested and analyzed to verify the effectiveness of the evaluation method. The method contributes to assessing voltage sag severity considering the point-on-wave and can be applied to design reasonable sag mitigation schemes.

II. Uncertainty of Equipment Malfunction

The point-on-wave refers to the phase angle where instantaneous voltage begins to experience voltage sag. The point-on-wave of voltage sag initiation is the primary characteristic of voltage sag. It exerts considerable influence on the sensitivity of certain equipment, especially the operation of equipment that relies on the influence of timing [

18]. When the point-on-wave is fixed, the dip immunity of equipment can be characterized by the voltage tolerance curve (VTC) [19], [20]. The VTC changes when the point-on-wave varies. A cluster of VTCs can be obtained based on experimental data. In general, the sensitivity of equipment can be described by three regions: operation, malfunction, and uncertainty, as shown in Fig. 1. Umax and Umin are the residual voltage magnitude thresholds, and Tmax and Tmin are the duration thresholds. The equipment performs well in the operation region and trips in the malfunction region. However, equipment performance is unclear in the region of uncertainty, because the VTCs may appear anywhere in the region [19].

Fig. 1 Diagram of VTCs.

The equipment malfunction probability, which reflects the voltage sag severity, is determined by voltage sag immunity. The voltage sag immunity of equipment can be described by the residual voltage magnitude thresholds and duration thresholds under a fixed point-on-wave. However, under-estimation or over-estimation may occur if the region of uncertainty is too small or too large, as shown by shaded areas in Fig. 2.

Fig. 2 Estimation of uncertainty region. (a) Under-estimation of uncertainty region. (b) Over-estimation of uncertainty region.

Moreover, the point-on-wave ranges from 0° to 360°, and the point-on-wave where the sag occurs is uncertain. These uncertainties make it difficult to evaluate voltage sag severity. Therefore, this paper puts forward an evaluation method and index considering the uncertainty of equipment voltage sag immunity and point-on-wave. The point-on-wave is difficult to acquire directly in most cases when the duration is recorded by monitoring devices. By means of fitting experimental test results, the relationship between the point-on-wave and duration under a fixed residual voltage can be obtained. Assuming that the point-on-wave is a random variable, the equipment malfunction probability can be described by the integral of the probability density function of the point-on-wave under a fixed residual voltage when the duration is known. The equipment malfunction probability contributes to assess the voltage sag severity.

III. Voltage Sag Severity Evaluation

A. Probabilistic Index of Voltage Sag Severity

Previous research [

21] has found that the relationship between the duration threshold and point-on-wave of initiation under a fixed residual voltage exhibits a periodic characteristic. The relationship between point-on-wave θ and duration threshold T can be expressed by a continuous function T=g(θ). When the point-on-wave varies between 0° and 360°, most duration threshold values will repeat twice. Therefore, two points-on-wave of initiation θ1 and θ2 can be calculated when the duration threshold is known under a fixed residual voltage. When the residual voltage and sag duration are given, if the point-on-wave is between θ1 and θ2, the device will malfunction. Thus, a probabilistic index IP is proposed to evaluate the voltage sag severity. IP is defined as the probability that the point-on-wave is between θ1 and θ2, as expressed in (1).

IP=θ1θ2f(θ)dθ×100% (1)

where f(θ) is the probability density function of the point-on-wave derived from statistical analysis on the grid side. θ1 and θ2 (θ1<θ2) can be obtained when the duration threshold and T=g(θ) are given. Thus, the IP can represent the probability of equipment malfunction under a fixed residual voltage and duration.

B. Evaluation Procedure of Voltage Sag Severity

The evaluation procedure of the voltage sag severity is illustrated in Fig. 3, which can be described as follows.

Fig. 3 Evaluation procedure of voltage sag severity.

1) Set up the voltage tolerance test platform and obtain test results for various points-on-wave of initiation under a fixed residual voltage.

2) Fit experiment data to approximate the relationship between the point-on-wave and duration threshold with a mathematical function T=g(θ) by means of the least squares method.

3) Calculate the IP according to (1), assuming that the point-on-wave is subjected to a certain probability distribution.

IV. Case Study

A. Voltage Tolerance Test

A voltage tolerance test platform is established in this paper. An Ametek MXII-45, which can generate three-phase symmetric and asymmetric voltage, is adopted as the sag generator.

Its rated capacity is 45 kVA, and its voltage output ranges from 0 V to 300 V. When the equipment trips, it is considered to be disturbed by the voltage sag. When the RMS value of input current decreases to 0.1 A and cannot recover in 1 min, the equipment fails in the test.

Three types of releasers C20, C32, and C50 are tested with the experimental platform for more than 4000 times, whose parameters are given in Table I. The voltage tolerance test data of these releasers are presented in Appendix A Tables AI-AIII, where M and D represent the magnitude and duration, respectively. The releaser is a component of a low-voltage breaker that can make the breaker trip if the input voltage drops below a certain value.

Table I General Information of Tested Releasers
TypeRated current (A)Operation voltage (V)Rated frequency (Hz)Actuator type
ACDCACDC
C20 20 72-253 12-72 50 60 Insulation group II, black, sealable
C32 32 12-440 12-440 50 60 Insulation group II, black, sealable
C50 50 12-440 50 60 Toggle

The test procedure is described as follows.

Step 1:   the initial residual voltage magnitude is set to be 0.9 p.u., and the initial point-on-wave is 0°.

Step 2:   the moment when the equipment failed to pass the test is recorded. If the equipment passes the test, the recorded value is 1 s.

Step 3:   the point-on-wave is changed from 0° to 315° with steps of 45° . Step 2 is repeated.

Step 4:   the residual voltage magnitude is changed from 0 to 0.9 p.u. with steps of 0.05 p.u.. Step 2 and Step 3 are repeated. To achieve greater detail, the step of the residual voltage magnitude change can be reduced.

More than 800 pieces of data are obtained. VTCs of the three types of releasers at different points-on-wave are shown in Fig. 4.

Fig. 4 VTCs of tested releasers at different points-on-wave. (a) VTCs of C20. (b) VTCs of C32. (c) VTCs of C50.

B. Calculation of IP

A C32 releaser is taken as an example, and its test result under 30% residual voltage is shown in Fig. 5. In order to simplify the mathematical expression, the data from 285° to 360° are shifted to 0°, and the corresponding starting angle is subtracted by 360°.

Fig. 5 Point-on-wave and duration threshold curve under 30% residual voltage.

Taking 225° as the dividing point, the left and right curves are linearly fitted by the least square method. The piecewise function T=g(θ) is defined as (2).

T=-0.0519θ+16.85    -75°θ<225°0.382θ-82.44         225°θ285° (2)

Assuming that the point-on-wave is subjected to a uniform distribution between -75° and 285°, the probability density function of the point-on-wave could be calculated as f(θ)=1/360. Therefore, IP should be calculated with (3).

IP=θ2-θ1360×100% (3)

For example, θ1 is 131.98° and θ2 is 268.17° when T = 10 ms under 30% residual voltage. The corresponding IP can be calculated and is equal to 37.83%. The IP with 30% residual voltage (uniform distribution) is shown in Fig. 6.

Fig. 6 IP with 30% residual voltage (uniform distribution).

Assuming that the point-on-wave is subjected to a normal distribution, both the median and standard deviations are 90. IP should be calculated as (4).

IP=θ1θ2190×2πe-(θ-90)22×8100dθ×100% (4)

IP with 30% residual voltage (normal distribution) is shown in Fig. 7. IP varies when the point-on-wave is subjected to different distributions. If the residual voltage and duration threshold are known and the probability distribution of the point-on-wave is given, IP can describe the probability of device malfunction. The larger the IP, the higher the probability of device malfunction.

Fig. 7 IP with 30% residual voltage (normal distribution).

In reality, only residual voltage data and duration data are recorded, whereas the information about the point-on-wave is typically unavailable. The sensitivity of equipment can be fully and precisely assessed when the point-on-wave is included in the analysis.

V. Conclusion

A probabilistic index calculation method of voltage sag severity is proposed to evaluate the effect of voltage sag on sensitive equipment. The relationship between the point-on-wave and duration threshold is determined by a mathematical function based on test results. The voltage sag IP is then calculated using the probabilistic density function of the point-on-wave. Three types of releasers are chosen to verify the effectiveness of the method. The evaluation results are beneficial for further analyzing the seriousness of voltage sag and putting forward schemes for voltage sag mitigation.

The evaluation method is based on voltage tolerance tests. Therefore, considerable field/laboratory tests should be performed to support the application of the method. Furthermore, more sag characteristics should be considered to accurately assess the voltage sag severity.

Appendix

Appendix A

Table aI Voltage Tolerance Test Data of C20 Releaser
θ=0°θ=45°θ=90°θ=135°θ=180°θ=225°θ=270°θ=315°
M (%)D (ms)M (%)D (ms)M (%)D (ms)M (%)D (ms)M (%)D (ms)M (%)D (ms)M (%)D (ms)M (%)D (ms)
70 1000 68 1000 68 1000 66 1000 66 1000 68 1000 68 1000 66 1000
68 100 67 100 67 100 65 100 66 100 67 100 67 100 66 100
60 64 60 66 60 62 60 62 60 57 60 61 60 46 60 42
55 38 55 37 55 33 55 31 55 28 55 32 55 41 55 41
50 36 50 32 50 29 50 26 50 23 50 25 50 33 50 35
45 22 45 17 45 14 45 12 45 9 45 20 45 23 45 21
40 19 40 17 40 13 40 11 40 8 40 7 40 23 40 20
35 18 35 15 35 13 35 10 35 8 35 7 35 22 35 20
30 18 30 15 30 13 30 10 30 8 30 6 30 21 30 20
25 18 25 14 25 12 25 10 25 8 25 6 25 20 25 20
20 18 20 14 20 12 20 10 20 7 20 6 20 19 20 20
15 17 15 13 15 12 15 9 15 6 15 5 15 17 15 18
10 16 10 13 10 12 10 9 10 6 10 4 10 16 10 18
0 16 0 13 0 11 0 8 0 5 0 4 0 4 0 17
Table aII Voltage Tolerance Test Data of C32 Releaser
θ=0°θ=45°θ=90°θ=135°θ=180°θ=225°θ=270°θ=315°
M (%)D (ms)M (%)D (ms)M (%)D (ms)M (%)D (ms)M (%)D (ms)M (%)D (ms)M (%)D (ms)M (%)D (ms)
63 1000 63 1000 65 1000 65 1000 64 1000 64 1000 63 1000 63 1000
62 100 62 100 63 100 64 100 63 100 64 100 63 100 63 100
50 28 50 29 50 26 50 25 50 23 50 25 50 27 50 28
45 20 45 17 45 14 45 12 45 9 45 12 45 24 45 21
40 19 40 16 40 13 40 11 40 8 40 7 40 22 40 21
30 18 30 15 30 12 30 10 30 7 30 6 30 21 30 20
20 17 20 14 20 12 20 10 20 7 20 5 20 18 20 19
10 17 10 14 10 12 10 9 10 7 10 5 10 16 10 19
0 16 0 14 0 14 0 9 0 7 0 5 0 15 0 18
Table aIII Voltage Tolerance Test Data of C50 Releaser
θ=0°θ=45°θ=90°θ=135°θ=180°θ=225°θ=270°θ=315°
M (%)D (ms)M (%)D (ms)M (%)D (ms)M (%)D (ms)M (%)D (ms)M (%)D (ms)M (%)D (ms)M (%)D (ms)
55 1000 55 1000 57 1000 57 1000 55 1000 55 1000 58 1000 57 1000
55 100 55 100 56 100 57 100 53 100 55 100 58 100 57 100
50 57 50 57 50 45 50 44 50 43 50 45 50 44 50 44
45 38 45 32 45 23 45 29 45 26 45 26 45 26 45 26
40 35 40 23 40 21 40 21 40 22 40 24 40 25 40 25
35 32 35 22 35 19 35 16 35 16 35 21 35 24 35 24
30 20 30 18 30 14 30 12 30 9 30 8 30 23 30 23
25 20 25 17 25 14 25 11 25 9 25 7 25 22 25 21
20 18 20 16 20 13 20 11 20 8 20 7 20 21 20 20
15 18 15 16 15 13 15 11 15 8 15 7 15 21 15 20
10 17 10 15 10 12 10 10 10 8 10 7 10 20 10 20
5 17 5 16 5 12 5 10 5 8 5 7 5 19 5 20
0 16 0 14 0 12 0 8 0 6 0 6 0 16 0 18

References

1

IEEE Recommended Practice for Monitoring Electric Power Quality, IEEE Std. 1159-2019, 2019. [百度学术

2

J. V. Chan, J. V. Milanovic, and A. Delahunty, “Risk-based assessment of financial losses due to voltage sag,” IEEE Transactions on Power Delivery, vol. 26, no. 2, pp. 492-500, Apr. 2011. [百度学术

3

J. V. Milanovi and Y. Zhang, “Global minimization of financial losses due to voltage sags with FACTS based devices,” IEEE Transactions on Power Delivery, vol. 25, no. 1, pp. 298-306, Jan. 2010. [百度学术

4

Y. Xu, Y. Wu, M. Zhang et al., “Sensitivity of programmable logic controllers to voltage sags,” IEEE Transactions on Power Delivery, vol. 34, no. 1, pp. 2-10, Jan. 2019. [百度学术

5

Y. Xu, W. Lu, K. Wang et al., “Sensitivity of low-voltage variable-frequency devices to voltage sags,” IEEE Access, vol. 7, pp. 2068-2079, Jul. 2019. [百度学术

6

N. A. Ismail, L. M. Kasim, N. F. Mokhtar et al., “Digital analysis and development of ride-through capability of AC contactor with respect to voltage sag characteristics,” in Proceedings of 2nd International Conference on Computer and Automation Engineering (ICCAE), Singapore, Singapore, Feb. 2010, pp. 177-181. [百度学术

7

X. Gong, Y. Yu, B. Wang et al., “A severity assessment method for multiple voltage sag,” in Proceedings of 2017 IEEE 3rd Information Technology and Mechatronics Engineering Conference (ITOEC), Chongqing, China, Oct. 2017, pp. 135-140. [百度学术

8

A. Santiago, A. R. Oscar, F. G. Luis et al., “Analysis of voltage sag severity case study in an industrial circuit,” IEEE Transactions on Industry Applications, vol. 53, no. 1, pp. 15-21, Jan. 2017. [百度学术

9

H. Liao, S. Abderlrahman, Y. Guo et al., “Identification of weak areas of power network based on exposure to voltage sags–Part I: development of sag severity index for single-event characterization,” IEEE Transactions on Power Delivery, vol. 30, no. 6, pp. 2392-2400, Jun. 2015. [百度学术

10

X. Zhou, F. H. Wang, J. Zhang et al., “A voltage sag severity index considering the power system and consumer equipment,” in Proceedings of 2014 IEEE PES General Meeting Conference & Exposition, National Harbor, USA, Jul. 2014, pp. 1-5. [百度学术

11

Y. Fan, S. Yu, C. Xin et al., “Voltage sag severity assessment based on multiobjective decision analytic hierarchy process,” in Proceedings of 2018 2nd IEEE Conference on Energy Internet and Energy System Integration, Beijing, China, Oct. 2018, pp.1-8. [百度学术

12

P. Ling, Z. Peng, and Y. Xiao, “Comprehensive evolution of node voltage sag severity considering the power grid side and the user side,” in Proceedings of 2018 China International Conference on Electricity Distribution, Tianjin, China, Sept. 2018, pp. 467-471. [百度学术

13

X. Xiao, H. He, and Y. Wang, “Analytical model of AC contactors for studying response mechanism to multi-dimensional voltage sag characteristics and its novel applications,” IET Generation, Transmission & Distribution, vol. 13, no. 17, pp. 3910-3920, Jul. 2019. [百度学术

14

Z. Yuan, H. Wang, Y. Huang et al., “Uncertainty assessment of sensitive equipment failure probability caused by voltage sags,” in Proceedings of Power & Energy Engineering Conference, Wuhan, China, Sept. 2010, pp. 1-7. [百度学术

15

X. Zhou, F. H. Wang, J. Zhang et al., “A voltage sag severity index considering the power system and consumer equipment,” in Proceedings of 2014 IEEE PES General Meeting Conference & Exposition, National Harbor, USA, Jul. 2014, pp. 1-9. [百度学术

16

J. C. Cebrian, N. Kagan, and J. V. Milanović, “Probabilistic estimation of distribution network performance with respect to voltage sags and interruptions considering network protection setting–Part I: the methodology,” IEEE Transactions on Power Delivery, vol. 33, no. 1, pp. 42-51, Jan. 2018. [百度学术

17

J. Y. Chan and J. V. Milanovic, “Methodology for assessment of financial losses due to voltage sags and short interruptions,” in Proceedings of 2007 9th International Conference on Electrical Power Quality and Utilization, Barcelona, Spain, Oct. 2007, pp. 1-7. [百度学术

18

M. S. Hasan, K. M. Muttaqi, and A. Bouzerdoum, “Characterization of voltage sag based on point-on-wave,” in Proceedings of International Conference on Electrical & Computer Engineering, Dhaka, Bangladesh, Dec. 2016, pp. 1-8. [百度学术

19

CIGRE/CIRED/UIE Joint Working Group C4.107. (2007, Apr.). Economic framework for power quality. [Online]. Available: https://www.escholar.manchester.ac.uk/uk-ac-man-scw:265983 [百度学术

20

CIGRE/CIRED/UIE Joint Working Group C4.110. (2010, Oct.). Voltage dip immunity of equipment and installations. [Online]. Available: https://www.mendeley.com/catalogue/42ee830b-2bf8-3b2e-bd50-2aa26a514b66/ [百度学术

21

S. Z. Djokie, J. V. Milanovic, and S. M. Rowland, “Advanced voltage sag characterisation II: point on wave,” IET Generation, Transmission & Distribution, vol. 1, no. 1, pp. 146-154, Jan. 2017. [百度学术