Abstract
Dynamic reactive power compensation equipment typically requires a fast response to output the necessary reactive power. The term “dynamic response time of reactive power” is often used but has never been clearly defined. This paper summarizes the reactive power calculations under different definitions and algorithms and considers these calculations in terms of signal processing to simulate and analyze the step response. This paper subsequently focuses on the widely used instantaneous reactive power algorithm and finally concludes that the dynamic reactive power response time closely depends on the reactive power calculation method itself. The single-phase instantaneous reactive power algorithm has the fastest response time. The reactive power response time of dynamic reactive devices in power systems is a minimum of a quarter of one cycle time for the well-known and widely used single-phase reactive power algorithms.
THE recent increase in the proportion of renewable energy resources within power systems has increased the significance of the role of power electronic devices. The reactive power characteristics of power electronic equipment are essential in power quality and stability issues and most devices considered as reactive power sources require a fast response. The “dynamic response time of reactive power” is often used to assess the ability of fast reactive power regulation [
Fast reactive power response is critical in high-voltage direct current (HVDC) transmission systems, which are rapidly developing in concurrence with renewable energy utilization. For conventional line-commutated current-sourced converter (LCC) based HVDC transmission systems, the fast reactive power compensation provided by a static synchronous compensator (STATCOM) can reduce the commutation failure probability of LCC thyristor valves [
The conventional reactive power concept has been defined to represent of the quantity of electric power resulting from the phase angle difference between the current and voltage. The power calculation is based on a steady sinusoidal AC system, i.e., the root mean square (RMS) concept. If the reactive power calculation method is considered in terms of signal processing, it can be concluded that the calculated response time for reactive power based on traditional reactive power theory would be one cycle time (T), thus ms for 50 Hz or ms for 60 Hz. Hence, the same results would be obtained as the Budeanu’s reactive power definition, which describes the reactive power under non-sinusoidal conditions.
The concept of IRP was firstly proposed in 1983 to deal with arbitrary voltage and current waveforms without any restriction on the three-phase three- or four-wire systems [
Even when considered as only a control algorithm, the three-phase instantaneous theory is not applicable to single- or individual-phase cases as the calculations require Clarke’s transform among the three phases and algebraic operations for diverse phase quantities. Thus, this theory has been confined to the field of three-phase low-voltage power electronics and has little advantage in the field of power transmission and distribution. Fast single-phase reactive power control is a typical and important requirement of the electromagnetic transient processes in power systems. In general, the fast single-phase reactive power algorithm is more applicable to power systems.
The response time according to three-phase IRP theory is zero, but this is insignificant as the calculated IRP q does not have the common meaning of traditional reactive power [
The reactive power calculation time of the conventional numerical integration method is equal to that of one cycle for single-phase power. It is noted that a long delay in response time is a major drawback of this method. Reference [
A definition for single-phase instantaneous active and reactive power based on the Hilbert transform for operation in the transient state is proposed in [
Some improved reactive power definitions and algorithms for single phase, also referred to as IRP, have been presented and applied in engineering since the 1990s [
Another quick reactive power calculation algorithm addressed in this paper is the synchronous reference frame dq (SRF-dq) algorithm [
The transient response time of single-phase reactive power has not been fully investigated and clarified under different reactive theories or definitions. The problem becomes more complicated when a required response time is given by grid regulations. The required response time of reactive power was roughly defined by the State Grid Corporation of China in 2013, when an increasing number of wind farms were integrated into the grid [
In this paper, the calculation of reactive power response time will be analyzed for single-phase power. Section II will summarize the calculation of reactive power, including the Hilbert transform algorithm, digital phase shift method, IRP algorithm, and SRF-dq algorithm. Section III will compare the differences of reactive power calculated using four different reactive power methods with different current changes, and provide further analysis. Section IV will study the influence of the reactive power algorithms on the response time in the control equipment. Finally, conclusions are given in Section V.
The electric power quantities, including reactive power under sinusoidal, non-sinusoidal, balanced, and unbalanced conditions, are defined in IEEE 1459 [
(1) |
where Q is the reactive power; U is the root mean square (RMS) value of voltage; I is the RMS value of current; is the cycle time; k is the positive integral number; is the moment when the measurement starts; u is the voltage; and is the phase angle between the voltage and the current.
The concept of reactive power for metering is defined in IEC 62053-24 [
(2) |
where U1 is the RMS value of the fundamental frequency component of the voltage; I1 is RMS value of the fundamental frequency component of the current; and is the phase angle between the fundamental frequency voltage and current.
In engineering applications, reactive power measurement instruments use the following phase shift equation to calculate reactive power [
(3) |
Both the IEEE and IEC reactive power calculations are integral algorithms over one or multiple cycles, derived from the traditional definition of reactive power under sinusoidal conditions. It is clear that the response time of reactive power using these algorithms will be one cycle or more due to the integration cycle when the voltage or current variables change. However, in electric energy metering applications, the response time of reactive power is insignificant.
In reactive power control apparatus such as STATCOM and SVC, the ability to output fast reactive power is critical. Thus, the reactive power itself must be measured quickly in order to maintain the fast control of the system. With the development of digital processing technologies, calculations of the reactive power devices often use the following specific algorithms to achieve fast reactive power calculations:
The Hilbert transform algorithm mainly solves reactive power calculations when the voltage or current has harmonic components. The theoretical basis is Budeanu’s definition of reactive power.
(4) |
where Un is the RMS value of the
For all harmonics, the Hilbert transform shifts the harmonic components by 90° and calculates the reactive power according to Budeanu’s expression.
In engineering applications, the Hilbert transform is widely used for reactive power calculations, the schematic diagram is shown in

Fig. 1 Schematic diagram of reactive power calculation based on Hilbert transform algorithm.
A digital phase shift Hilbert filter consists of two sets of digital filters, F1 and F2, which satisfy:
(5) |
where HF1 is the digital phase-shifted Hilbert filter F1; HF2 is the digital phase-shifted Hilbert filter F2; is the angular frequency; and is the target angular frequency range.
The digital phase shift method delays the sampling value of voltage or current by a 1/4 cycle and multiplies the sampling value of current or voltage to obtain reactive power.
(6) |
where N is the total number of sampling points per cycle; k is the number of sampling points; and u(k) and i(k) are the voltage and the current sampling points, respectively.
In three-phase three- or four-wire systems, IRP results from the following equations [
(7) |
(8) |
where Ua, Ub, Uc and ia, ib, ic are the voltages and the currents of phases a, b, and c, respectively; , and , are the and values of three-phase voltage and current after Clark’s transformation, respectively. The three-phase IRP can be obtained via the following expression:
(9) |
where q is the three-phase IRP.
For single-phase IRP calculations, a similar expression is proposed in [
(10) |
(11) |
(12) |
In discrete sampling and digital data processing, the above expressions can be written as:
(13) |
(14) |
(15) |
It is noted that this expression for IRP does not contain integral or sum operations over a single cycle, thus the response time would be less than one cycle.
In order to simplify the calculation and analysis of a synchronous machine or three-phase inverter, the Park transform is widely applied as it can rotate the reference frames of AC quantities and transform them into DC quantities [
(16) |
(17) |
The IRP is calculated as:
(18) |
Similarly, for single-phase, , obtained via phase shift are the same as from (11) and (12).
(19) |
(20) |
The key process of the calculation described above is to use the Park transformation to obtain the dq component of voltage and current in the dq coordinate system. The IRP can be subsequently obtained from (18).
When the current undergoes a step change, the reactive power calculated via different algorithms has various transitional processes. These reactive power algorithms can be regarded as filters whose time delay is expressed by the time response of the filters. In the simulation, the current abruptly increases from 0.9 p.u. to 1.0 p.u. at , while the voltage is sinusoidal, which is an ideal step input to the current.
The idealized mathematical expression for current step impact can be regarded as the characteristic of an ideal reactive power control device, which can instantaneously change the output current. Thus, the simulation is a mathematic model for the ideal fastest reactive power device, whose current output has zero time delay when a control order is received according to Fig. A1 in Appendix A.
However, the reactive power calculations can be understood in terms of signal processing of current and voltage data. Considering different algorithms as filters, the single-phase reactive power algorithms should have a step response to the step current input. The response time of reactive power calculation algorithms should be identified and included.
(21) |
where is the phase angle of voltage at the instant . The cases studied are listed in
In the studied cases, the voltage is unchanging sinusoidal, and the current undergoes a step change. Although the cases are simplified and idealized, it can be considered approximate to the typical function of the reactive power control apparatus in power systems. The reactive power control apparatus such as SVC or STATCOM equipment, may have high current output variation but still has little influence on the voltage owing to the significant short circuit capacity of power systems. The alternative case, where the voltage and current vary simultaneously, is also studied in this section.
The single-phase voltage and current and the reactive power calculation that result from various algorithms are shown in Figs.
(22) |

Fig. 2 Step response of different reactive power calculations as current undergoes a step change at .

Fig. 3 Step response of different reactive power calculations as current undergoes a step change at .

Fig. 4 Step response of different reactive power calculations as current undergoes a step change at .
The calculation results of single-phase voltage, current and the reactive power from the various methods are shown in Figs.
(23) |

Fig. 5 Step response of different reactive power calculations with .

Fig. 6 Step response of different reactive power calculations with .

Fig. 7 Step response of different reactive power calculations with .
In general, it can be stated that IRP and SRF-dq algorithms have shorter transition processes and a faster step response time of 5 ms, whereas the phase shift method has a response time of 20 ms and the Hilbert transform algorithm has a response time of nearly 30 ms. The response time for diverse reactive power calculation methods can be explained via the filter time delay. For example, using data sampled a quarter of cycle () before, the IRP and SRF-dq algorithms have a time delay of nearly 5 ms (T/4).
As mentioned above, (21) is mathematical expression for the current step output of an idealized reactive power device. While the current abruptly changes from 0.9 to 1.0 p.u. at , the idealized reactive power device can be regarded as the fastest; i.e., no other reactive power device can respond faster than the idealized one. Alternatively, among these normally used reactive power algorithms, IRP and SRF-dq algorithms are the fastest methods for single-phase reactive power calculations, with a response time of . Therefore, the conclusion can be reached that the response time of reactive power in a power system is a minimum of T/4, using single-phase reactive power algorithms.
If the voltage and the current change simultaneously, the conclusion remains valid, as expressed by (24) and shown in
(24) |

Fig. 8 Step response of different reactive power calculations if voltage and current change simultaneously while .
According to the above analysis, the step response time of reactive power of the single phase ranges from 5 to 30 ms, with different methods applied to a 50 Hz system. In particular, the response time of the IRP and SRF-dq algorithms is 5 ms. Thus, the IRP and SRF-dq algorithms are applied in most reactive control devices for fast performance.
However, in three-phase power systems, the response time of the three-phase IRP algorithm using (7)-(9) would be different. An example is shown in (25) and (26).
(25) |
(26) |
Note that the current of phase a has the same expression as in (22), the currents of the three phases change simultaneously and symmetrically, and the response time of three-phase IRP is approximately zero.
It is noted that the step response time using single-phase IRP indicated in

Fig. 9 Step response of three-phase IRP calculation while .
A further difference between these two reactive power algorithms occurs under asymmetric current. For example, the current of phase a undergoes a step change, whereas the currents of phases b and c remain constant as follows.
(27) |
(28) |
As shown in

Fig. 10 Step response of IRP of three-phase calculation while .
In fact, the single- and three-phase IRPs are two completely different algorithms [
The main function of reactive power compensation systems is to provide fast reactive power compensation, stablize system voltages, and damp power oscillation. Different systems have different response time requirements regarding reactive power and voltage control for reactive power compensation equipment. In a strong system, the response time requirement is relatively slow, but in a weak system, the response time of the reactive power compensation device is required to be fast enough to support the system voltage.
Taking the 500 kV 3000 MW Yongan-Funing LCC-HVDC transmission project of China as an example, the short-circuit ratio of the receiving Funing terminal system is approximately 3. The terminal system has the problem of a shortage of dynamic reactive power, and it is possible that commutation failure may occur after the recovery of an AC system fault, which affects the safe and stable operation of the HVDC transmission system. Therefore, three sets of 100 Mvar STATCOMs have been installed at Funing convert station to provide dynamic reactive power support.

Fig. 11 Single-line diagram.
A significant number of tests on the performance of STATCOM devices have been conducted in the Funing project. The step test for reactive response time is typically used to determine the reactive power requirement from 0 to 100 Mvar. The result is shown in

Fig. 12 Test result of reactive power step from 0 to 100 Mvar.
The response time of reactive power is about 6 ms, satisfying the specification requirements, and the reactive power calculation algorithm used for STATCOMs in this project is the single-phase IRP.
Furthermore, this section will demonstrate the influence of the reactive power algorithm itself on the response time of a dynamic reactive power control equipment.
The typical control diagram of STATCOM reactive power control equipment can be described with equivalent transfer functions, while the reactive power algorithm is removed for research.
In

Fig. 13 Control block of reactive power control equipment.
In this section, two cases with relatively fast and slow response characteristics of an equivalent transfer function are studied. The instantaneous current i and calculated reactive power are recorded for the transient processes.
As shown in

Fig. 14 Step response of reactive power control equipment for case 1 (, ).
As shown in

Fig. 15 Step response of reactive power control equipment for case 2 (, ).
From the above cases, it is verified that IRP and SRF-dq algorithms are the fastest of the four algorithms, and that the step response of the reactive power calculation using IRP and SRF-dq algorithms is more than 5 ms due to their inner time delay, which is discussed in Section III. It can be further seen that if the control characteristic is very fast, as in case 1, the response time of reactive power control equipment is mainly decided by the reactive power algorithm itself. If the control characteristic is relatively slow, as in case 2, the difference in the response time from various reactive power algorithms is slightly shortened.
In general, for fast dynamic reactive power compensation applications, the reactive power algorithm itself has a significant influence on reactive power regulation. This implies that when evaluating reactive power response characteristics, for example, in Fig. A1 in Appendix A, the reactive power calculation method should be stated. Considering both the response speed and overshoot control, the IRP and SRF-dq methods are suggested for dynamic reactive power compensation applications.
This paper summarized the definitions of reactive power and the corresponding calculation methods. The reactive power response time, which is very important for dynamic reactive power compensation, is analyzed. The following conclusions are drawn.
1) Reactive power response time is normally used without an accurate definition, and its value is highly dependent on the reactive power calculation method. Among the frequently used single-phase reactive power calculation methods, the IRP and SRF-dq algorithms have the fastest response time. The phase shift method and Hilbert transform algorithm are relatively slower. The response time of the IRP and SRF-dq algorithms is T/4.
2) The single-phase IRP method is different to the three-phase IRP algorithm in reactive power calculation. The response time of single-phase IRP is meaningful and practical under transient conditions.
3) Among the most well-known and widely used methods for calculating single-phase reactive power, the IRP and SRF-dq algorithms are currently the fastest. If a step change to the current is regarded as the fastest ideal control output, the response time of an ideal control device using the IRP and SRF-dq algorithms is a minimum of T/4.
In conclusion, when determining the reactive power response time of dynamic reactive power compensation equipment, it is necessary to identify the reactive power calculation method. It is meaningless to specify the reactive power response time without the specific calculation method.
REFERENCES
S. C. Ferreira, R. B. Gonzatti, R. R. Pereira et al., “Finite control set model predictive control for dynamic reactive power compensation with hybrid active power filters,” IEEE Transactions on Industrial Electronics, vol. 65, no. 3, pp. 2608-2617, Mar. 2018. [百度学术]
S. Dong and Y. C. Chen, “Adjusting synchronverter dynamic response speed via damping correction loop,” IEEE Transactions on Energy Conversion, vol. 32, no. 2, pp. 608-619, Jun. 2017. [百度学术]
Y. Li, J. Zhao, Z. Liu et al., “Assessment method of dynamic reactive power valuation for transient voltage stability,” in Proceedings of 2013 IEEE International Conference of IEEE Region 10 (TENCON 2013), Xi’an, China, Oct. 2013, pp. 1-4. [百度学术]
H. Akagi, Y. Kanazawa, and A. Nabae, “Instantaneous reactive power compensators comprising switching devices without energy storage components,” IEEE Transactions on Industry Applications, vol. IA-20, no. 3, pp. 625-630, May 1984. [百度学术]
K. Mohamed, Z. S. Ahmed, F. Mohammed-Karim et al., “The impact study of a STATCOM on commutation failures in an HVDC inverter feeding a weak AC system,” Journal of Electrical Engineering, vol. 63, no. 2, pp. 95-102, Mar. 2012. [百度学术]
M. Zhao, X. Yuan, J. Hu et al., “Voltage dynamics of current control time-scale in a VSC-connected weak grid,” IEEE Transactions on Power Systems, vol. 31 no. 4, pp. 2925-2937, Jul. 2016. [百度学术]
X. NI, C. Zhao, C. Guo et al., “The effects of VSC-HVDC on the system strength of LCC-HVDC in dual-infeed hybrid HVDC System,” Proceedings of the CSEE, vol. 35, no. 16, pp. 4052-4061, Aug. 2015. [百度学术]
D. Xie, Z. Xu, L. Yang et al., “A comprehensive LVRT control strategy for DFIG wind turbines with enhanced reactive power support,” IEEE Transactions on Power Systems, vol. 28, no. 3, pp. 3302-3310, Aug. 2013. [百度学术]
A. Garcia-Cerrada, P. Garcia-Gonzalez, R. Collantes et al., “Comparison of thyristor-controlled reactors and voltage-source inverters for compensation of flicker caused by arc furnaces,” IEEE Transactions on Power Delivery, vol. 15, no. 4, pp. 1225-1231, Oct. 2000. [百度学术]
H. Akagi, S. Ogasawara, and H. Kim, “The theory of instantaneous power in three-phase four-wire systems: comprehensive approach,” in Proceedings of 1999 IEEE Industry Applications Conference 34th IAS Annual Meeting, Phoenix, USA, Oct. 1999, pp. 431-439. [百度学术]
L. S. Czarnecki, “Constraints of instantaneous reactive power p-q theory,” IET Power Electronics, vol. 7, no. 9, pp. 2201-2208, Sept. 2014. [百度学术]
H. Akagi, E. H. Watanabe, and M. Aredes, Instantaneous Power Theory and Applications to Power Conditioning, 1st ed., Hoboken: John Wiley & Sons, 2006, pp. 41-104. [百度学术]
J. L. Willems, “A new interpretation of the Akagi-Nabae power components for nonsinusoidal three-phase situations,” IEEE Transactions on Instrumentation & Measurement, vol. 41, no. 4, pp. 523-527, Aug. 1992. [百度学术]
A. Nabae and T. Tanaka, “A new definition of instantaneous active-reactive current and power based on instantaneous space vectors on polar coordinates in three-phase circuits,” IEEE Transactions on Power Delivery, vol. 11, no. 3, pp. 1238-1243, Jul. 1996. [百度学术]
P. Salmerón and R. S. Herrera, “Instantaneous reactive power theory–a general approach to poly-phase systems,” Electric Power Systems Research, vol. 79, no. 9, pp. 1263-1270, Sept. 2009. [百度学术]
L. S. Czarnecki, “Instantaneous reactive power p-q theory and power properties of three-phase systems,” IEEE Transactions on Power Delivery, vol. 21, no. 1, pp. 362-367, Jan. 2006. [百度学术]
R. A. Mastromauro, M. Liserre, T. Kerekes et al., “A single-phase voltage-controlled grid-connected photovoltaic system with power quality conditioner functionality,” IEEE Transactions on Industrial Electronics, vol. 56, no. 11, pp. 4436-4444, Aug. 2009. [百度学术]
A. Luo, Y. Chen, Z. Shuai et al., “An improved reactive current detection and power control method for single-phase photovoltaic grid-connected DG system,” IEEE Transactions on Energy Conversion, vol. 28, no. 4, pp. 823-831, Sept. 2013. [百度学术]
T. Tanaka, E. Hiraki, K. Ueda et al., “A novel detection method of active and reactive currents in single-phase circuits using the correlation and cross-correlation coefficients and its applications,” IEEE Transactions on Power Delivery, vol. 22, no. 4, pp. 2450-2456, Oct. 2007. [百度学术]
M. Saitou and T. Shimizu, “Generalized theory of instantaneous active and reactive powers in single-phase circuits based on Hilbert transform,” in Proceedings of 2002 IEEE 33rd Annual IEEE Power Electronics Specialists Conference, Cairns, Australia, Jun. 2002, pp. 1419-1424. [百度学术]
H. Pang, Z. Wang, and J. Chen, “A measuring method of the single-phase AC frequency, phase, and reactive power based on the Hilbert filtering,” IEEE Transactions on Instrumentation and Measurement, vol. 56, no. 3, pp. 918-923, May 2007. [百度学术]
Y. Gao, W. Zhao, and S. Huang, “Reactive power definitions in single-phase circuits based on instantaneous reactive power theory,” Electrical Measurement & Instrumentation, vol. 53, no. 20, pp. 1-8, Oct. 2016. [百度学术]
J. Liu, B. Liu, and Z. Wang, “Hybrid type series active power filter used in single-phase circuit based on instantaneous reactive power theory,” Proceedings of the CSEE, vol. 17, no. 1, pp. 37-41, Jan. 1997. [百度学术]
J. Yang, Z. Wang, and G. Qiu, “Detecting method for harmonics and reactive currents in single-phase circuits,” Transactions of China Electrotechnical Society, vol. 11, no. 3, pp. 42-46, Feb. 1996. [百度学术]
S. A. Khajehoddin, M. Karimi-Ghartemani, A. Bakhshai et al., “A power control method with simple structure and fast dynamic response for single-phase grid-connected DG systems,” IEEE Transactions on Power Electronics, vol. 28, no. 1, pp. 221-233, May 2012. [百度学术]
R. L. Bojoi, L. R. Limongi, D. Roiu et al., “Enhanced power quality control strategy for single-phase inverters in distributed generation systems,” IEEE Transactions on Power Electronics, vol. 26, no. 3, pp. 798-806, Jan. 2011. [百度学术]
Specification for Technical Performance and Test of Reactive Power Compensation Equipment in Wind Farm, Q/GDW Standard 11064, 2013. [百度学术]
G. Fan, Z. Pei, Y. Xiao et al., “Research on response speed and it’s test method of reactive power compensation equipment in wind farm,” Smart Grid, vol. 3, no. 2, pp. 139-144, Feb. 2015. [百度学术]
K. Yamashita, H. Renner, S. M. Villanueva et al., “Modelling of inverter-based generation for power system dynamic studies,” CIGRE Joint Working Group Technical Brochure, C4/C6.35/CIRED, May 2018. [百度学术]
IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces, IEEE Standard 1547, 2018. [百度学术]
IEEE Standard Definitions for the Measurement of Electric Power Quantities Under Sinusoidal, Nonsinusoidal, Balanced, or Unbalanced Conditions - Redline, IEEE Standard 1459, 2010. [百度学术]
Electricity Metering Equipment (a.c.) - Particular Requirements - Part 24: Static Meters for Reactive Energy at Fundamental Frequency (Classes 0.5 S, 1 S and 1), IEC Standard 62053-24, 2014. [百度学术]
J. Liu, J. Yang, and Z. Wang, “A new approach for singe-phase harmonic current detecting and its application in a hybrid active power filter,” in Proceedings of 25th Annual Conference of the IEEE Industrial Electronics Society, San Jose, USA, Nov. - Dec. 1999, pp. 849-854. [百度学术]