Journal of Modern Power Systems and Clean Energy

ISSN 2196-5625 CN 32-1884/TK

网刊加载中。。。

使用Chrome浏览器效果最佳,继续浏览,你可能不会看到最佳的展示效果,

确定继续浏览么?

复制成功,请在其他浏览器进行阅读

Transmission Line Distance Protection Under Current Transformer Saturation  PDF

  • Yuping Zheng 1,2
  • Tonghua Wu 1,2
  • Feng Hong 4
  • Gang Yao 4
  • Jimin Chai 1,3
  • Zhinong Wei 1
1. College of Energy and Electrical Engineering, Hohai University, Nanjing 210098,China; 2. State Key Laboratory of Smart Grid Protection and Control, NARI Group Corporation, Nanjing 211106, China; 3. Changzhou Institute of Technology, Changzhou 213032, China; 4. State Key Laboratory of Smart Grid Protection and Control, NARI Group Corporation, Nanjing 211106, China

Updated:2021-01-19

DOI:10.35833/MPCE.2019.000095

  • Full Text
  • Figs & Tabs
  • References
  • Authors
  • About
OUTLINE

Abstract

Conventional transmission line distance protection approaches are subject to malfunction under reverse fault-induced current transformer (CT) saturation for the typically employed breaker-and-a-half configuration. This paper addresses this issue by proposing a new distance protection approach that combines the blocking and unblocking criteria of distance protection based on the values of incomplete differential current, operation voltage, and current harmonic content. The proposed approach is verified by theoretical analysis, dynamic simulation testing, and field operation to ensure that the obtained distance protection is reliable and refrains from operating unnecessarily under reverse fault-induced CT saturation in the breaker-and-a-half configuration. Meanwhile, the proposed approach is demonstrated can operate reliably when forward faults occur or various reverse faults are converted to forward faults.

I. Introduction

THE operation range and sensitivity of distance protection are not directly affected by the operation mode of an electric power transmission system. Therefore, distance protection can satisfy the requirements of modern power systems for rapid fault clearing and hence can be widely used in high-voltage transmission lines [

1], [2]. However, the transmission characteristics of current transformers (CTs) are important factors that affect the dependability of distance protection, particularly under secondary current distortion during CT saturation [3].

According to the IEC 60255-121 standard [

3], the effect of CT saturation on distance protection can be classified into two categories: dependability loss and security loss. A dependability loss corresponds to a saturation-induced decrease in the current amplitude and a phase shift, which reduces the actuation range and increases the actuation time of distance protection. A security loss corresponds to a distance protection malfunction that arises from a saturation-induced reverse current. Generally, in the case of a single CT connected to protection, distance protection will lose dependability with reduced possibility of malfunction owing to a decrease in the secondary current after CT saturation. Similar conclusions have been drawn in the literature [4], [5].

However, according to the IEEE Std C37.110 [

6], in a ring or breaker-and-a-half configuration, the current used for line protection is the sum of the currents of two CTs. When the bus fails, a large ride-through current may flow through the CT. If the CT is saturated, the total current may present a large reverse current, and the distance protection will be at the risk of malfunction.

The problems associated with distance protection under CT saturation have been addressed in a number of studies. For example, the optimal selection of CTs at key locations in the transmission system has been verified to be effective for reducing or avoiding the effect of CT saturation on distance protection [

6]. However, this complicates the implementation and application range of distance protection. Hence, these problems cannot be resolved completely by depending solely on the optimal selection of CT locations. Other studies have proposed the use of new types of CTs such as Rogowski coils or electromagnetic CTs to limit the effect of CT saturation on distance protection [7], [8]. However, these new types of CTs cannot be applied in a sufficiently extensive manner to address these problems owing to issues regarding stability and economic considerations. Furthermore, studies focusing on the malfunction of distance protection during CT saturation are rather limited, and most previous studies investigate the malfunction of differential protection during CT saturation, including some approaches such as the identification approach of saturated waveforms [9]-[13] and the compensation approach for saturation current [14]-[17]. In addition, an approach employing directional elements has been proposed to avoid malfunction [18]. However, the operation conditions under which this method is applicable are limited, and malfunctions can still occur in special cases. Moreover, distance protection malfunctions in high-voltage transmission lines significantly affect the power grid, particularly in the ring or breaker-and-a-half configuration, and the risk of malfunction during reverse fault-induced CT saturation events is high. Accordingly, it is essential to analyze the causes of malfunctions in distance protection during CT saturation for developing reliable preventative approaches.

Herein, the mechanism of distance protection malfunction during reverse fault-induced CT saturation is analyzed for the breaker-and-a-half configuration as an example. Accordingly, a new distance protection approach is proposed that combines the blocking and unblocking criteria of distance protection based on the criteria of incomplete differential current, operation voltage, and current harmonic content. The proposed approach is validated by theoretical analysis, dynamic simulation testing, and field operation to ensure that the obtained distance protection is reliable and can be implemented appropriately during reverse fault-induced CT saturation in the ring or breaker-and-a-half configuration. Meanwhile, the proposed approach is demonstrated can operate reliably when forward faults occur or various reverse faults are converted to forward faults owing to the subsidence of CT saturation.

II. Analysis of Distance Protection Malfunction

The mho characteristic is one of the most typically used characteristics in distance protection [

3]. In this study, we perform an analysis based on an example of mho distance protection [19] of positive-sequence voltage polarization. Based on the phase-comparison principle, the operation equation is expressed as:

90°<arg(U˙OP/U˙P)<270° (1)

where U˙OP=U˙m-I˙mZset is the operation voltage, and Zset is the setting value of distance protection, U˙m and I˙m are the respective voltage and current obtained by the protection device, respectively; and U˙P=U˙m1 is the polarization voltage, and U˙m1 is the positive-sequence voltage component at the protection device.

According to an example of a substation system shown in Fig. 1, the current I˙ml on the protected line L1 is the sum of the primary currents I˙m1 from CT1 and I˙m2 from CT2.

Fig. 1 An example of a substation system with breaker-and-a-half configuration.

According to the characteristics of CT transmission, I˙m1 and I˙m2 can be expressed as [

3]:

I˙m1'=k˙1I˙m1 (2)
I˙m2'=k˙2I˙m2 (3)

where I˙m1' and I˙m2' are the secondary currents from CT1 and CT2, respectively; and k˙1=Aeϕ. A and ϕ are the changes in the amplitude and angular difference generated during transmission, respectively. The definition of k˙2 is similar. A virtual CT that outputs the secondary total current can be constructed, and according to (2) and (3), the transmission characteristic of CT can be expressed as:

k˙=I˙sum'I˙l=I˙m1'+I˙m2'I˙m1+I˙m2=k˙1I˙m1+k˙2I˙m2I˙m1+I˙m2 (4)

where I˙l is the primary current flowing through the line; and I˙sum' is the total current flowing to the protection device. For simplicity, the CT1 and CT2 ratios are assumed to be 1. Therefore, k˙1=k˙2=1 during a normal CT transmission.

The equivalent system obtained when a fault occurs at point F of line L2 in Fig. 1 is shown in Fig. 2, where E˙S is the sending-end electromotive force; E˙R is the receiving-end electromotive force; I˙F is the fault current flowing from point F to point K; ZK is the equivalent impedance from point M to point K; and ZR is the equivalent impedance of the protection forward direction.

Fig. 2 Equivalent system with reverse fault at point F in Fig. 1.

The parameters in Fig. 2 are used to express the operation voltage U˙OP and polarization voltage U˙P as:

U˙OP=U˙m-I˙l'Zset=I˙lZm-k˙I˙lZset=I˙l(Zm-k˙Zset) (5)
U˙P=U˙m1=E˙R+I˙l1ZR=-I˙l(ZR-Zm)+I˙l1ZR=I˙l[Zm-ZR(1-I˙l1/I˙l)]=I˙l(Zm-k'ZR) (6)

where Zm is the resistance between the protection device and the short-circuit point; I˙l1 is the positive-sequence component of I˙l; and k'=1-I˙l1/I˙l, which is related to the fault type and system parameter. For example, with a single-phase earth fault, k'=0.75-0.87; with a phase-phase fault, k'=0.5; and with a three-phase fault, k'=0.

Substituting (5) and (6) into (1) yields

90°<argZm-k˙ZsetZm-k'ZR<270° (7)

The operation characteristic corresponding to (7) is a circle with end points of k˙Zset and k'ZR as the diameter. During the normal transmission of CT1 and CT2, k˙=1. This condition is illustrated in Fig. 3(a), where the action circle is removed from the origin toward quadrant I. The reverse fault measurement impedance -Zk generally falls in quadrant III, and hence the relay exhibits good directionality. By contrast, when CT1 is under normal transmission and CT2 is under severe saturation, k˙1=1, whereas the amplitude of k˙2 is reduced and becomes zero [

6]. This condition is illustrated in Fig. 3(b), where k˙=I˙m1'/I˙l owing to the opposite directions of I˙m1' and I˙l, and the action circle corresponding to (7) shifts to quadrant III. Therefore, distance protection may malfunction when a short-circuit fault occurs at the far-end point or the opposite bus.

Fig. 3 Mho action circle with positive-sequence voltage polarization. (a) Transmission of both CT1 and CT2 is normal. (b) CT2 is saturated.

The system illustrated in Fig. 1 presents a special operation condition, denoted as operation condition 1, when BRK4 is disconnected with a reverse fault at point F so that the same current flows through CT1 and CT2, and I˙l is zero. The condition where CT2 is severely saturated is illustrated in Fig. 4, where the total current I˙sum' from the CT output presents a consistent positive-direction characteristic with respect to I˙m1'. Subsequently, k˙ is in quadrant III, and the amplitude approaches infinity. Herein, the action circle corresponding to (7) extends infinitely to quadrant III, and the possibility of a reverse-fault-induced malfunction arises.

Fig. 4 CT2 saturation with reverse fault under operation condition 1.

Fault currents flowing through the branch CT may differ significantly, thereby resulting in the saturation of one of the CTs. For the fault illustrated in Fig. 1 and analyzed above, the fault currents from bus M and line L1 flowing through CT2 are easily saturated. Moreover, the directional characteristics of the total current are affected by CT2 saturation. Namely, the total current moves gradually in the forward direction as the extent of CT2 saturation increases, thereby increasing the probability of distance protection malfunction. Furthermore, a similar situation occurs with the fault at point Fb, as shown in Fig. 5(b). Hence, both the fault position and CT saturation extent are the factors that affect the distance protection malfunction.

Fig. 5 Schematic diagrams for illustrating additional short-circuit states of substation system with breaker-and-a-half configuration shown in Fig. 1. (a) Forward short-circuit fault. (b) Reverse short-circuit fault.

Additional short-circuit states are illustrated in Fig. 5(a) and (b), which represent a fault at the near-end point Fa along the forward direction of the line and a fault at point Fb on the reverse bus, respectively. Figure 5(a) shows that, when the fault occurs at point Fa, variations ΔI˙m1 and ΔI˙m2 of the current flowing through CT1 and CT2 are reversed, i.e., they are in the same direction. Figure 5(b) shows that when the fault occurs at point Fb, ΔI˙m1 is forward and ΔI˙m2 is reverse, i.e., the two are in opposite directions. These two short-circuit states are analyzed in much greater detail in the following section. However, the fault at point Fb shown in Fig. 5(b) is similar to the fault illustrated in Fig. 1 and that analyzed previously.

To summarize, distance protection is at the risk of malfunction in the case of reverse-fault-induced CT saturation in the breaker-and-a-half configuration and will malfunction under particular operation modes. In addition, the fault location and extent of CT saturation are the factors affecting the distance protection malfunction.

III. Identification Method for CT Saturation for Distance Protection

A. Incomplete Differential Criteria

The fault current direction characteristics of the short-circuit states illustrated in Fig. 5(a) and (b) enable the formulation of incomplete differential criteria for conducting distance protection. Among the distance protection criteria, the blocking criterion and the unblocking criterion are expressed as (8) and (9), respectively.

ΔIcdkresΔIzdΔIzd>Iset,zd (8)
ΔIcd>kresΔIzdΔIzd>Iset,zd (9)

where ΔIcd=ΔI˙m1+ΔI˙m2 is the incomplete differential current; ΔIzd=ΔI˙m1-ΔI˙m2 is the incomplete restraint current; kres is the differential restraint coefficient, which is generally set as 1.1; and Iset,zd is the restraint current threshold, which is set to avoid the effect of system disturbances on the criterion and causes the criterion to exhibit great sensitivity for the near-end metallic fault and not subject to false blocking during the far-end reverse line fault.

The values of ΔI˙m1 and ΔI˙m2 are obtained using the short data window algorithm [

20], [21]. The criteria can identify the fault direction during CT saturation [3] and can implement distance protection for a forward fault while blocking distance protection for a reverse fault. In the far-end reverse line fault (Fig. 5(b)), the blocking criterion is not subject to false blocking. In addition, the amplitudes of ΔI˙m1 and ΔI˙m2 are high for the near-end metallic fault, and the directional characteristics are conspicuous. Hence, the criteria exhibit greater sensitivity. However, a small fault current arising under fault conditions such as a far-end fault or near-end fault with transition resistance may induce CT saturation under residual CT magnetism. Under these conditions, the directional characteristics of ΔI˙m1 and ΔI˙m2 are not conspicuous and hence the criteria may be invalid. This can be analyzed based on the system illustrated in Fig. 6, where the two transmission lines from bus M are installed on the same tower. When BRK3 is open, which is defined as operation condition 2, a short-circuit fault occurs at the end of the line or on the bus N, and ΔI˙m2 may be extremely small. At this point, ΔIcdΔIzd, and the blocking criterion operates to halt the implementation of distance protection. These problems are addressed by the proposed operation voltage criteria.

Fig. 6 Operation condition 2: double-circuit lines on the same tower with BRK3 open.

B. Operation Voltage Criteria

The operation voltage variation ΔU˙op is defined as:

ΔU˙op=ΔU˙m-ΔI˙mZL (10)

where ZL is the impedance of the entire transmission line; and ΔU˙m and ΔI˙m are the voltage and current variations at the protection device, respectively. This can be defined in cases of forward and reverse faults as follows.

For the forward fault,

ΔU˙m=-ΔI˙mZS (11)

where ZS is the equivalent positive-sequence impedance of the power system behind the protection device. Substituting (11) into (10), we can obtain

ΔU˙op=-ΔI˙m(ZS+Zset) (12)

The voltage variation at fault point F is defined as:

ΔU˙f=ΔI˙m(ZS+ZF) (13)

where ZF is the positive-sequence impedance from the short-circuit point F to the protection device. The forward fault is illustrated by the potential diagram of the voltage variation, as shown in Fig. 7(a). Accordingly, the condition ΔU˙op>ΔU˙m must hold along the entire transmission line during a short circuit in the forward direction.

Fig. 7 Distribution diagram for reverse fault voltage variation. (a) Forward fault. (b) Reverse fault.

For a reverse fault,

ΔU˙m=ΔI˙mZR (14)

where ZR is the equivalent positive-sequence impedance of the protection forward direction. Substituting (14) into (10), we can obtain

ΔU˙op=ΔI˙m(ZR-ZL) (15)

The voltage variation at fault point F is expressed as:

ΔU˙f=-ΔI˙m(ZR+ZF) (16)

The reverse fault is illustrated by the potential diagram of the voltage variation, as shown in Fig. 7(b). Accordingly, the condition ΔU˙op<ΔU˙m must be met during a reverse short circuit.

Based on the above analysis, different relationships involving ΔU˙op and ΔU˙m are employed to set unblocking and blocking criteria of the operation voltage during positive and reverse faults, which are expressed as (17) and (18), respectively.

ΔU˙op>kΔU˙mΔU˙m>Uset,dif (17)
ΔU˙op<kΔU˙mΔU˙m>Uset,dif (18)

where Uset,dif is the voltage threshold value; and k is the restraint coefficient, which is generally set as 1.1, and ensures that the blocking criterion is reliable. Similar to (8), the threshold value Uset,dif is also set to reduce the effect of disturbance in the system on the criterion. The values of ΔU˙m and ΔI˙m are obtained using the short data window algorithm [

20], [21]. Under normal operation conditions, the criteria can identify the fault direction during CT saturation [3] and then implement distance protection for a forward fault while blocking distance protection for a reverse fault. Details regarding the application of the operation voltage criteria under the two operation conditions are provided as follows.

Under operation condition 1, the total current obtained by the protection is zero during a reverse bus fault. At this time, ΔU˙op=ΔU˙m, and the blocking criterion of (18) is invalid. During the forward fault, ΔU˙op is significantly greater than ΔU˙m; hence, the value of k cannot impair the judgment of the unblocking criterion. Under this operation condition, the incomplete differential blocking criterion operates correctly and exhibits greater sensitivity than the operation voltage blocking criterion.

Under operation condition 2, the incomplete differential criterion is invalid during a fault at the remote end of the line. However, the operation voltage unblocking criterion operates correctly and exhibits greater sensitivity than the incomplete differential unblocking criterion.

The above analysis demonstrates the necessity of utilizing both the incomplete differential and operation voltage criteria to address special conditions where a single set of criteria is not applicable.

C. Logic Coordination Between Incomplete Differential and Operation Voltage Criteria

The action conditions of the incomplete differential and operation voltage criteria at various fault points under different system conditions are shown in Table I, where P1, P2, and P3 denote the fault points at the near-end line, far-end line, and opposite bus, respectively.

TABLE I Action Condition of Incomplete Differential and Operation Voltage Criteria
ConditionFault pointIncomplete differential blocking criterionIncomplete differential unblocking criterionOperation voltage blocking criterionOperation voltage unblocking criterion
Condition 1 P1 Action No action Action No action
P2 No action Action Action No action
P3 No action Action Action No action
Condition 2 P1 Action No action Action No action
P2 No action Action No action Action
P3 Action No action No action Action
General P1 Action No action Action No action
P2 No action Action No action Action
P3 No action Action No action Action

The following conclusions can be obtained from Table I.

1) Under operation condition 1, the operation voltage blocking criterion is always activated regardless of the fault type, whereas the operation voltage unblocking criterion is never activated, and the incomplete differential action criteria are activated normally.

2) Under operation condition 2, the incomplete differential blocking criterion is activated in the fault at P3, whereas the incomplete differential unblocking criterion is not activated, and the operation voltage criteria are activated normally.

3) Under general operation conditions, both the incomplete differential and operation voltage criteria are activated normally.

Accordingly, valid distance protection blocking actions are assured by applying an “and” logic to the criteria of the incomplete differential blocking and the operation voltage blocking, whereas valid distance protection unblocking actions are assured by applying an “or” logic to the criteria of the incomplete differential unblocking and operation voltage unblocking. Hence, the criteria provide a strict account of the fault direction under all operation conditions. The criteria are activated according to the characteristics of the linear transmission area of the CT prior to its saturation. Consequently, a logical interlock between the blocking and unblocking criteria is used to avoid the effect of current distortion on criteria decisions after CT saturation, as shown in Fig. 8, and the continuity of the criteria can be maintained during CT saturation.

Fig. 8 Logic diagram for applying distance protection blocking and unblocking criteria.

D. Criteria for Current Harmonic Content Unblocking

When a reverse fault is converted to a forward fault, the distance protection blocking criteria act first and maintain the action, resulting in a failure to unblock distance protection after conversion to the forward fault. This problem is addressed in the present study by establishing unblocking criteria based on the current harmonic content.

The high second harmonic content of the output current is the key feature of CT saturation [

19], [22], [23]. Accordingly, CT saturation can be assumed to be relieved when the second harmonic content of the output current is less than a threshold value, enabling distance protection to be unblocked. The proposed current harmonic content unblocking criteria are expressed as:

Im,h2<kHImIm1,h2<kHIm1Im2,h2<kHIm2 (19)

where Im,h2, Im1,h2, and Im2,h2 are the secondary harmonic contents of the total current, side circuit breaker current, and middle circuit breaker current, respectively; Im, Im1, and Im2 are the total current, side circuit breaker current, and middle circuit breaker current, respectively; and kH is the harmonic content ratio coefficient, which is set as 0.15 based on the literature [

22]-[24] and a large number of simulation tests.

During a reverse fault, distance protection is blocked, and the output current is monitored according to the criteria in (19) simultaneously. If CT saturation is relieved and the reverse fault is converted to a forward fault, the harmonic contents will be less than the threshold values, and distance protection will be unblocked. During forward-fault-induced CT saturation, the action characteristics of distance protection are affected by distortions in the current, and the protection trip time will be extended or the protection range will be reduced [

4]. Meanwhile, the action characteristics cannot be restored until CT saturation has subsided to a certain extent or completely relieved. Therefore, the full-cycle Fourier algorithm is used to implement a criterion that has a short time delay, and the criterion can be unblocked in time with limited effect on the action characteristics of the distance protection.

IV. Simulation Analysis

A. Simulation System Parameter

Figure 9 presents the dual-circuit simulation model built in the Real Time Digital Simulator (RTDS) and employed for analysis. It is a typical model operating at 500 kV, where the same tower adopts the breaker-and-a-half configuration at one side and the dual-bus configuration at the other side. Internal fault points F1-F3 and external fault points F4 and F5 are established in the model to simulate various fault types. The system impedance and line parameters are listed in Table II.

Fig. 9 RTDS simulation model.

TABLE II System Impedance and Line Parameters of RTDS Simulation Model
ParameterValue
Positive-sequence resistance (Ω/km) 0.028
Positive-sequence inductive reactance (Ω/km) 0.275
Positive-sequence capacitive reactance in parallel (Ω·km) 0.225
Zero-sequence resistance (Ω/km) 0.094
Zero-sequence inductive reactance (Ω/km) 0.674
Positive-sequence capacitive reactance in parallel (Ω·km) 0.313
Line length (km) 100
System equivalent impedance at bus M (Ω) 10∠85°
System equivalent impedance at bus N (Ω) 20∠85°

Two protection devices, denoted as A and B, are employed in the simulations at the M side of line L1. Device A is developed based on the proposed method, and device B is developed using the conventional distance protection strategy. Device A measures the respective output currents of CT1 and CT2, whereas device B measures the total current. Both devices comprise two-stage distance protections based on the mho relay, which is defined in (1). The value of Zset of distance relay zone I is 22.11 Ω, whereas it is set to be 33.16 Ω for the distance relay zone II, and the time delay is set to be 0.5 s.

B. Simulation Result

Dynamic simulations are conducted to verify the performance of the protection devices with forward and reverse metallic faults and different operation modes. The simulation results are listed in Table III. The results indicate that both devices A and B provide consistent operation characteristics of distance protection under general operation conditions as well as forward and reverse faults. Hence, the proposed approach does not affect the original operation characteristics of distance protection.

TABLE III Performance of Protection Device Under Different Operation Modes and Faults
ModeFault pointDevice ADevice B
Both strong F1 Distance relay zone I (12 ms) Distance relay zone I (12 ms)
Both strong F2 Distance relay zone I (21 ms) Distance relay zone I (21 ms)
Both strong F4 No action No action
ES strong, ER weak F1 Distance relay zone I (10 ms) Distance relay zone I (10 ms)
ES strong, ER weak F3 Distance relay zone II (521 ms) Distance relay zone II (521 ms)
ES strong, ER weak F5 No action No action

The fault recording results of device A in a fault at F1 are shown in Fig. 10(a) to illustrate the criterion features obtained during a forward fault. After the fault occurs, the criteria of the incomplete differential unblocking and operation voltage unblocking are satisfied rapidly, and distance protection is unblocked. Similarly, the fault recording results of device A in a fault at F5 are shown in Fig. 10(b) to illustrate the criterion features obtained during a reverse fault. After the fault occurs, the criteria of the incomplete differential blocking and operation voltage blocking are satisfied rapidly, and distance protection is blocked.

Fig. 10 Criterion features during forward and reverse faults. (a) Forward fault. (b) Reverse fault.

The dynamic simulation results obtained in transfer faults are listed in Table IV. The results indicate that both devices A and B provide consistent operation characteristics of distance protection. Furthermore, the results verify the feasibility of the current harmonic content unblocking criteria, which exhibit action features similar to those of the conventional method.

TABLE IV Action of Protection Device in Transfer Fault
FaultConvert time (ms)Device ADevice B
F1 A-phase, F4 B-phase 10 Distance relay zone I (12 ms), A-phase trip Distance relay zone I (12 ms), A-phase trip
F1 A-phase, F4 A-phase 10 Distance relay zone I (12 ms), A-phase trip Distance relay zone I (12 ms), A-phase trip
F4 A-phase, F1 B-phase 10 Distance relay zone I (22 ms), B-phase trip Distance relay zone I (22 ms), B-phase trip
F4 A-phase, F1 A-phase 10 Distance relay zone I (22 ms), A-phase trip Distance relay zone I (22 ms), A-phase trip
F4 A-phase, CT1 saturation, F1 A-phase 10 Distance relay zone I (25 ms), A-phase trip Distance relay zone I (22 ms), A-phase trip

Dynamic simulations are conducted for reverse single-phase metallic ground faults and a fault through transition resistance at F4 under different saturation degrees of CT1 and CT2. The respective actions of protection devices A and B are listed in Table V. The results indicate that device A can reliably block distance protection under the reverse fault-induced CT saturation when the saturation time is greater than or equal to 2 ms. By contrast, device B is subject to malfunction. Moreover, the blocking criteria of device A still have a greater sensitivity compared with the single blocking criterion of device B in the case of involving a fault through transition resistance. Additionally, the criteria provide a smaller fault current as well as reliable distance protection blocking.

TABLE V Protection Action of Reverse Fault at F4
Fault typeSaturated CTSaturation time (ms)Device ADevice B
Metallic CT1 1.5 Action Action
CT1 2.0 No action Action
CT1 2.5 No action Action
CT1 5.0 No action Action
CT2 2.0 No action No action
CT2 5.0 No action No action
Through transition resistance CT1 1.5 Action Action
CT1 2.0 No action Action
CT1 2.5 No action Action
CT1 5.0 No action Action
CT2 2.0 No action No action

The fault recording results of device A in a fault at F4 when CT1 is saturated are shown in Fig. 11. Therefore, the criteria of the incomplete differential blocking and operation voltage blocking are satisfied rapidly in the CT linear transmission region after the fault, and the distance protection is blocked. Subsequently, the criteria of the operation voltage unblocking and incomplete differential unblocking are satisfied after entering the CT saturation region. However, the distance protection blocking criterion blocks the unblocking criterion, and the blocking status of the distance protection is maintained.

Fig. 11 Criterion feature in case of reverse fault and CT saturation.

In operation condition 1 for various operation modes, the single-phase grounding fault at F3 occurs again.

The dynamic simulation results of a single-phase grounding fault at F3 obtained under operation condition 1 combined with various modes at the two terminals are listed in Table VI. In addition, the actions of protection devices A and B obtained during simulations under operation condition 2 with a reverse single-phase grounding fault at F5 are listed in Table VII for different saturation degrees of CT1 and CT2. The simulation results obtained under the two operation conditions demonstrate that device A does not fail to implement distance protection in the forward fault condition, and that it refrains from implementing distance protection unnecessarily under the reverse fault and CT saturation conditions. Meanwhile, device B is subject to malfunction. Hence, these results verify that the combination of the incomplete differential and operation voltage criteria addresses the problems associated with single-criterion approaches under special operation conditions. In addition, the correct criterion action is ensured under all operation conditions.

TABLE VI Protection Action of Forward Fault at F3
ConditionDevice ADevice B
Both strong Distance relay zone II (511 ms) Distance relay zone II (512 ms)
Both weak Distance relay zone II (512 ms) Distance relay zone II (513 ms)
E˙S strong, E˙R weak Distance relay zone II (512 ms) Distance relay zone II (512 ms)
E˙S weak, E˙R strong Distance relay zone II (512 ms) Distance relay zone II (511 ms)
TABLE VII Protection Action of External Fault at F5
Saturated CTSaturation time (ms)Device ADevice B
CT1 2 No action No action
CT1 5 No action No action
CT2 2 No action Action
CT2 5 No action Action

Over 10000 protection devices based on the proposed approach have been used in power grids of various voltage levels in China, and all of the field protection devices are operating as intended.

V. Conclusion

This paper addresses the tendency of conventional transmission line distance protection approaches to malfunction under reverse fault-induced CT saturation by proposing a new distance protection approach. The approach combines the criteria of distance protection blocking and unblocking based on the criteria of incomplete differential current, operation voltage, and current harmonic content. The mechanism of distance protection malfunction during reverse fault-induced CT saturation is analyzed for the breaker-and-a-half configuration as an example. The results of dynamic simulation testing and field operation verify that the proposed approach guarantees reliable distance protection and the intended operation during forward faults and reverse fault-induced CT saturation that lasts longer than 2 ms. In general, the proposed approach does not affect the accuracy and speed of distance protection. Moreover, the application of current harmonic content criteria enables the implementation of distance protection after a reverse fault is converted to a forward fault. Consequently, the reliability of distance protection is improved, and a higher practical engineering value is obtained. Ring or breaker-and-a-half configurations are typically used in domestic and foreign high-voltage power grids; hence, the promotion and application of the proposed approach will improve the reliability of power transmission line protection and enhance the safe operation of power grids.

References

1

Z. Li, X. Lin, H. Weng et al., “Efforts on improving the performance of superimposed-based distance protection,” IEEE Transactions on Power Delivery, vol. 27, no. 1, pp. 186-194, Jan. 2012. [百度学术

2

K. G. Firouzjah, “Distribution network expansion based on the optimized protective distance of surge arresters,” IEEE Transactions on Power Delivery, vol. 33, no. 4, pp. 1735-1743. Jan. 2018, [百度学术

3

IEEE Guide for the Application of Current Transformers Used for Protective Relaying Purposes, IEEE Std C37.110TM-2007, 2007. [百度学术

4

Measuring Relays and Protection Equipment–Part 121: Functional Requirements for Distance Protection, IEC 60255-121-2014, 2014. [百度学术

5

K. Wannous and P. Toman, “The impact of current transformer saturation on the distance protection,” in Proceedings of 17th International Scientific Conference on Electronic Power Engineering (EPE), Prague, Czech Republic, May 2016, pp. 257-261. [百度学术

6

J. Mooney, “Distance element performance under conditions of CT saturation,” in Proceedings of 61st Annual Conference for Protective Relay Engineers, College Station, USA, Apr. 2008, pp. 1-9. [百度学术

7

A. N. Sarwade, P. K. Katti, and J. G. Ghodekar, “Enhancement of digital distance protection scheme with novel transducer,” in Proceedings of International Conference on Intelligent Computing and Application, Advances in Intelligent Systems and Computing, Singapore: Springer Nature, 2018, pp. 287-297. [百度学术

8

Q. Chen, H. Hou, D. You et al., “Research on improvements of using electronic current transformer on distance protection,” in Proceedings of 42nd International University Power Engineering Conference, Brighton, UK, Oct. 2007, pp. 267-272. [百度学术

9

Y.-C. Kang, S.-H. Ok, and S.-H. Kang, “A CT saturation detection algorithm,” IEEE Transactions on Power Delivery, vol. 19, no. 1, pp. 78-85, Jan. 2004. [百度学术

10

S.-H. Kang, M.-S. Kim, S.-R. Nam et al., “A CT saturation detection algorithm based on wavelet transformation,” in Proceedings of 12th IET International Conference on Developments in Power System Protection, Copenhagen, Denmark, Mar.-Apr. 2014, pp. 1-7. [百度学术

11

J. Ma, X. Gao, Z. Wang et al., “A new adaptive method to identify TA saturation using grille fractal,” Canadian Journal of Electrical and Computer Engineering, vol. 36, no. 4, pp. 152-157, Aug. 2013. [百度学术

12

S. Biswal and M. Biswal, “Algorithm for CT saturation detection with the presence of noise,” in Proceedings of 4th International Conference on Electrical Energy Systems (ICEES), Chennai, India, Feb. 2018, pp. 248-251. [百度学术

13

A. Hooshyar, M. Sanaye-Pasand, and E. F. El-Saadany, “CT saturation detection based on waveshape properties of current difference functions,” IEEE Transactions on Power Delivery, vol. 28, no. 4, pp. 2254-2263, Oct. 2013. [百度学术

14

T. Ji, Q. Wu, W. Tang et al., “A morphological scheme for the correction of CT saturation waveforms,” in Proceedings of 2011 IEEE PES General Meeting, Detroit, USA, Jul. 2011, pp. 1-7. [百度学术

15

S. R. Mohantya, V. R. Pandi, B. K. Panigrahi et al., “Performance evaluation of distance relay with CT saturation,” Applied Soft Computing, vol. 11, no. 8, pp. 4789-4797, Dec. 2011. [百度学术

16

E. M. Esmail, N. I. Elkalashy, T. A. Kawady et al., “Detection of partial saturation and waveform compensation of current transformers,” IEEE Transactions on Power Delivery, vol. 30, no. 3, pp. 1620-1622, Jun. 2015. [百度学术

17

A. Bagheri, M. Allahbakhshi, D. Behi et al., “Utilizing Rogowski coil for saturation detection and compensation in iron core current transformer,” in Proceedings of 25th Iranian Conference on Electrical Engineering (ICEE), Tehran, Iran, May 2017, pp. 1066-1071. [百度学术

18

B. Kasztenny and I. Voloh, “Application of distance and line current differential relays in breaker-and-a-half configurations,” in Proceedings of IEEE/PES Transmission and Distribution Conference and Exhibition, Dallas, USA, May 2006, pp. 1-8. [百度学术

19

ABB. (2011, Feb.). Line distance protection REL650 technical manual. [Online]. Available: https://library.abb.com/share?cid=9AAC30301058 [百度学术

20

Y. Yuan, Y. Lu, Z. Liu et al., “A fast filter algorithm of short data window based on phase analysis,” Automation of Electric Power Systems, vol. 28, no. 3, pp. 58-63, Feb. 2004. [百度学术

21

Y. Sun, Z. Zhang, Y. Shi et al., “The short-window integral method for calculating fundamental component from fault transient signalsin power systems,” Automation of Electric Power Systems, vol. 24, no. 1, pp. 30-33, Jan. 2000. [百度学术

22

W. Liu, Y. Pan, Y. Wang et al., “Effect of CT transient characteristics on transfer of inrush,” The Journal of Engineering, vol. 2019, no. 16, pp. 3062-3066, Apr. 2019. [百度学术

23

N. Farshid, K. Zahra, F. Ebrahim et al., “Fast detection and compensation of current transformer saturation using extended Kalman filter,” IEEE Transactions on Power Delivery, vol. 34, no. 3, pp. 1087-1097, Jun. 2019. [百度学术

24

A. Hooshyar and M. Sanaye-Pasand, “Accurate measurement of fault currents contaminated with decaying DC offset and CT saturation,” IEEE Transactions on Power Delivery, vol. 27, no. 2, pp. 773-783, Apr. 2012. [百度学术