Abstract
Conventional transmission line distance protection approaches are subject to malfunction under reverse fault-induced current transformer (CT) saturation for the typically employed breaker-and-a-half configuration. This paper addresses this issue by proposing a new distance protection approach that combines the blocking and unblocking criteria of distance protection based on the values of incomplete differential current, operation voltage, and current harmonic content. The proposed approach is verified by theoretical analysis, dynamic simulation testing, and field operation to ensure that the obtained distance protection is reliable and refrains from operating unnecessarily under reverse fault-induced CT saturation in the breaker-and-a-half configuration. Meanwhile, the proposed approach is demonstrated can operate reliably when forward faults occur or various reverse faults are converted to forward faults.
THE operation range and sensitivity of distance protection are not directly affected by the operation mode of an electric power transmission system. Therefore, distance protection can satisfy the requirements of modern power systems for rapid fault clearing and hence can be widely used in high-voltage transmission lines [
According to the IEC 60255-121 standard [
However, according to the IEEE Std C37.110 [
The problems associated with distance protection under CT saturation have been addressed in a number of studies. For example, the optimal selection of CTs at key locations in the transmission system has been verified to be effective for reducing or avoiding the effect of CT saturation on distance protection [
Herein, the mechanism of distance protection malfunction during reverse fault-induced CT saturation is analyzed for the breaker-and-a-half configuration as an example. Accordingly, a new distance protection approach is proposed that combines the blocking and unblocking criteria of distance protection based on the criteria of incomplete differential current, operation voltage, and current harmonic content. The proposed approach is validated by theoretical analysis, dynamic simulation testing, and field operation to ensure that the obtained distance protection is reliable and can be implemented appropriately during reverse fault-induced CT saturation in the ring or breaker-and-a-half configuration. Meanwhile, the proposed approach is demonstrated can operate reliably when forward faults occur or various reverse faults are converted to forward faults owing to the subsidence of CT saturation.
The mho characteristic is one of the most typically used characteristics in distance protection [
(1) |
where is the operation voltage, and is the setting value of distance protection, and are the respective voltage and current obtained by the protection device, respectively; and is the polarization voltage, and is the positive-sequence voltage component at the protection device.
According to an example of a substation system shown in

Fig. 1 An example of a substation system with breaker-and-a-half configuration.
According to the characteristics of CT transmission, and can be expressed as [
(2) |
(3) |
where and are the secondary currents from CT1 and CT2, respectively; and . A and are the changes in the amplitude and angular difference generated during transmission, respectively. The definition of is similar. A virtual CT that outputs the secondary total current can be constructed, and according to (2) and (3), the transmission characteristic of CT can be expressed as:
(4) |
where is the primary current flowing through the line; and is the total current flowing to the protection device. For simplicity, the CT1 and CT2 ratios are assumed to be 1. Therefore, during a normal CT transmission.
The equivalent system obtained when a fault occurs at point F of line L2 in

Fig. 2 Equivalent system with reverse fault at point F in Fig. 1.
The parameters in
(5) |
(6) |
where is the resistance between the protection device and the short-circuit point; is the positive-sequence component of ; and , which is related to the fault type and system parameter. For example, with a single-phase earth fault, ; with a phase-phase fault, ; and with a three-phase fault, .
Substituting (5) and (6) into (1) yields
(7) |
The operation characteristic corresponding to (7) is a circle with end points of and as the diameter. During the normal transmission of CT1 and CT2, . This condition is illustrated in

Fig. 3 Mho action circle with positive-sequence voltage polarization. (a) Transmission of both CT1 and CT2 is normal. (b) CT2 is saturated.
The system illustrated in

Fig. 4 CT2 saturation with reverse fault under operation condition 1.
Fault currents flowing through the branch CT may differ significantly, thereby resulting in the saturation of one of the CTs. For the fault illustrated in

Fig. 5 Schematic diagrams for illustrating additional short-circuit states of substation system with breaker-and-a-half configuration shown in Fig. 1. (a) Forward short-circuit fault. (b) Reverse short-circuit fault.
Additional short-circuit states are illustrated in
To summarize, distance protection is at the risk of malfunction in the case of reverse-fault-induced CT saturation in the breaker-and-a-half configuration and will malfunction under particular operation modes. In addition, the fault location and extent of CT saturation are the factors affecting the distance protection malfunction.
The fault current direction characteristics of the short-circuit states illustrated in
(8) |
(9) |
where is the incomplete differential current; is the incomplete restraint current; is the differential restraint coefficient, which is generally set as 1.1; and is the restraint current threshold, which is set to avoid the effect of system disturbances on the criterion and causes the criterion to exhibit great sensitivity for the near-end metallic fault and not subject to false blocking during the far-end reverse line fault.
The values of and are obtained using the short data window algorithm [

Fig. 6 Operation condition 2: double-circuit lines on the same tower with BRK3 open.
The operation voltage variation is defined as:
(10) |
where is the impedance of the entire transmission line; and and are the voltage and current variations at the protection device, respectively. This can be defined in cases of forward and reverse faults as follows.
For the forward fault,
(11) |
where is the equivalent positive-sequence impedance of the power system behind the protection device. Substituting (11) into (10), we can obtain
(12) |
The voltage variation at fault point F is defined as:
(13) |
where is the positive-sequence impedance from the short-circuit point F to the protection device. The forward fault is illustrated by the potential diagram of the voltage variation, as shown in

Fig. 7 Distribution diagram for reverse fault voltage variation. (a) Forward fault. (b) Reverse fault.
For a reverse fault,
(14) |
where is the equivalent positive-sequence impedance of the protection forward direction. Substituting (14) into (10), we can obtain
(15) |
The voltage variation at fault point F is expressed as:
(16) |
The reverse fault is illustrated by the potential diagram of the voltage variation, as shown in
Based on the above analysis, different relationships involving and are employed to set unblocking and blocking criteria of the operation voltage during positive and reverse faults, which are expressed as (17) and (18), respectively.
(17) |
(18) |
where is the voltage threshold value; and k is the restraint coefficient, which is generally set as 1.1, and ensures that the blocking criterion is reliable. Similar to (8), the threshold value is also set to reduce the effect of disturbance in the system on the criterion. The values of and are obtained using the short data window algorithm [
Under operation condition 1, the total current obtained by the protection is zero during a reverse bus fault. At this time, , and the blocking criterion of (18) is invalid. During the forward fault, is significantly greater than ; hence, the value of cannot impair the judgment of the unblocking criterion. Under this operation condition, the incomplete differential blocking criterion operates correctly and exhibits greater sensitivity than the operation voltage blocking criterion.
Under operation condition 2, the incomplete differential criterion is invalid during a fault at the remote end of the line. However, the operation voltage unblocking criterion operates correctly and exhibits greater sensitivity than the incomplete differential unblocking criterion.
The above analysis demonstrates the necessity of utilizing both the incomplete differential and operation voltage criteria to address special conditions where a single set of criteria is not applicable.
The action conditions of the incomplete differential and operation voltage criteria at various fault points under different system conditions are shown in
The following conclusions can be obtained from
1) Under operation condition 1, the operation voltage blocking criterion is always activated regardless of the fault type, whereas the operation voltage unblocking criterion is never activated, and the incomplete differential action criteria are activated normally.
2) Under operation condition 2, the incomplete differential blocking criterion is activated in the fault at P3, whereas the incomplete differential unblocking criterion is not activated, and the operation voltage criteria are activated normally.
3) Under general operation conditions, both the incomplete differential and operation voltage criteria are activated normally.
Accordingly, valid distance protection blocking actions are assured by applying an “and” logic to the criteria of the incomplete differential blocking and the operation voltage blocking, whereas valid distance protection unblocking actions are assured by applying an “or” logic to the criteria of the incomplete differential unblocking and operation voltage unblocking. Hence, the criteria provide a strict account of the fault direction under all operation conditions. The criteria are activated according to the characteristics of the linear transmission area of the CT prior to its saturation. Consequently, a logical interlock between the blocking and unblocking criteria is used to avoid the effect of current distortion on criteria decisions after CT saturation, as shown in

Fig. 8 Logic diagram for applying distance protection blocking and unblocking criteria.
When a reverse fault is converted to a forward fault, the distance protection blocking criteria act first and maintain the action, resulting in a failure to unblock distance protection after conversion to the forward fault. This problem is addressed in the present study by establishing unblocking criteria based on the current harmonic content.
The high second harmonic content of the output current is the key feature of CT saturation [
(19) |
where , , and are the secondary harmonic contents of the total current, side circuit breaker current, and middle circuit breaker current, respectively; , , and are the total current, side circuit breaker current, and middle circuit breaker current, respectively; and is the harmonic content ratio coefficient, which is set as 0.15 based on the literature [
During a reverse fault, distance protection is blocked, and the output current is monitored according to the criteria in (19) simultaneously. If CT saturation is relieved and the reverse fault is converted to a forward fault, the harmonic contents will be less than the threshold values, and distance protection will be unblocked. During forward-fault-induced CT saturation, the action characteristics of distance protection are affected by distortions in the current, and the protection trip time will be extended or the protection range will be reduced [

Fig. 9 RTDS simulation model.
Two protection devices, denoted as A and B, are employed in the simulations at the M side of line L1. Device A is developed based on the proposed method, and device B is developed using the conventional distance protection strategy. Device A measures the respective output currents of CT1 and CT2, whereas device B measures the total current. Both devices comprise two-stage distance protections based on the mho relay, which is defined in (1). The value of of distance relay zone I is 22.11 Ω, whereas it is set to be 33.16 Ω for the distance relay zone II, and the time delay is set to be 0.5 s.
Dynamic simulations are conducted to verify the performance of the protection devices with forward and reverse metallic faults and different operation modes. The simulation results are listed in
The fault recording results of device A in a fault at F1 are shown in

Fig. 10 Criterion features during forward and reverse faults. (a) Forward fault. (b) Reverse fault.
The dynamic simulation results obtained in transfer faults are listed in
Dynamic simulations are conducted for reverse single-phase metallic ground faults and a fault through transition resistance at F4 under different saturation degrees of CT1 and CT2. The respective actions of protection devices A and B are listed in
The fault recording results of device A in a fault at F4 when CT1 is saturated are shown in

Fig. 11 Criterion feature in case of reverse fault and CT saturation.
In operation condition 1 for various operation modes, the single-phase grounding fault at F3 occurs again.
The dynamic simulation results of a single-phase grounding fault at F3 obtained under operation condition 1 combined with various modes at the two terminals are listed in
Over 10000 protection devices based on the proposed approach have been used in power grids of various voltage levels in China, and all of the field protection devices are operating as intended.
This paper addresses the tendency of conventional transmission line distance protection approaches to malfunction under reverse fault-induced CT saturation by proposing a new distance protection approach. The approach combines the criteria of distance protection blocking and unblocking based on the criteria of incomplete differential current, operation voltage, and current harmonic content. The mechanism of distance protection malfunction during reverse fault-induced CT saturation is analyzed for the breaker-and-a-half configuration as an example. The results of dynamic simulation testing and field operation verify that the proposed approach guarantees reliable distance protection and the intended operation during forward faults and reverse fault-induced CT saturation that lasts longer than 2 ms. In general, the proposed approach does not affect the accuracy and speed of distance protection. Moreover, the application of current harmonic content criteria enables the implementation of distance protection after a reverse fault is converted to a forward fault. Consequently, the reliability of distance protection is improved, and a higher practical engineering value is obtained. Ring or breaker-and-a-half configurations are typically used in domestic and foreign high-voltage power grids; hence, the promotion and application of the proposed approach will improve the reliability of power transmission line protection and enhance the safe operation of power grids.
References
Z. Li, X. Lin, H. Weng et al., “Efforts on improving the performance of superimposed-based distance protection,” IEEE Transactions on Power Delivery, vol. 27, no. 1, pp. 186-194, Jan. 2012. [百度学术]
K. G. Firouzjah, “Distribution network expansion based on the optimized protective distance of surge arresters,” IEEE Transactions on Power Delivery, vol. 33, no. 4, pp. 1735-1743. Jan. 2018, [百度学术]
IEEE Guide for the Application of Current Transformers Used for Protective Relaying Purposes, IEEE Std C37.110TM-2007, 2007. [百度学术]
Measuring Relays and Protection Equipment–Part 121: Functional Requirements for Distance Protection, IEC 60255-121-2014, 2014. [百度学术]
K. Wannous and P. Toman, “The impact of current transformer saturation on the distance protection,” in Proceedings of 17th International Scientific Conference on Electronic Power Engineering (EPE), Prague, Czech Republic, May 2016, pp. 257-261. [百度学术]
J. Mooney, “Distance element performance under conditions of CT saturation,” in Proceedings of 61st Annual Conference for Protective Relay Engineers, College Station, USA, Apr. 2008, pp. 1-9. [百度学术]
A. N. Sarwade, P. K. Katti, and J. G. Ghodekar, “Enhancement of digital distance protection scheme with novel transducer,” in Proceedings of International Conference on Intelligent Computing and Application, Advances in Intelligent Systems and Computing, Singapore: Springer Nature, 2018, pp. 287-297. [百度学术]
Q. Chen, H. Hou, D. You et al., “Research on improvements of using electronic current transformer on distance protection,” in Proceedings of 42nd International University Power Engineering Conference, Brighton, UK, Oct. 2007, pp. 267-272. [百度学术]
Y.-C. Kang, S.-H. Ok, and S.-H. Kang, “A CT saturation detection algorithm,” IEEE Transactions on Power Delivery, vol. 19, no. 1, pp. 78-85, Jan. 2004. [百度学术]
S.-H. Kang, M.-S. Kim, S.-R. Nam et al., “A CT saturation detection algorithm based on wavelet transformation,” in Proceedings of 12th IET International Conference on Developments in Power System Protection, Copenhagen, Denmark, Mar.-Apr. 2014, pp. 1-7. [百度学术]
J. Ma, X. Gao, Z. Wang et al., “A new adaptive method to identify TA saturation using grille fractal,” Canadian Journal of Electrical and Computer Engineering, vol. 36, no. 4, pp. 152-157, Aug. 2013. [百度学术]
S. Biswal and M. Biswal, “Algorithm for CT saturation detection with the presence of noise,” in Proceedings of 4th International Conference on Electrical Energy Systems (ICEES), Chennai, India, Feb. 2018, pp. 248-251. [百度学术]
A. Hooshyar, M. Sanaye-Pasand, and E. F. El-Saadany, “CT saturation detection based on waveshape properties of current difference functions,” IEEE Transactions on Power Delivery, vol. 28, no. 4, pp. 2254-2263, Oct. 2013. [百度学术]
T. Ji, Q. Wu, W. Tang et al., “A morphological scheme for the correction of CT saturation waveforms,” in Proceedings of 2011 IEEE PES General Meeting, Detroit, USA, Jul. 2011, pp. 1-7. [百度学术]
S. R. Mohantya, V. R. Pandi, B. K. Panigrahi et al., “Performance evaluation of distance relay with CT saturation,” Applied Soft Computing, vol. 11, no. 8, pp. 4789-4797, Dec. 2011. [百度学术]
E. M. Esmail, N. I. Elkalashy, T. A. Kawady et al., “Detection of partial saturation and waveform compensation of current transformers,” IEEE Transactions on Power Delivery, vol. 30, no. 3, pp. 1620-1622, Jun. 2015. [百度学术]
A. Bagheri, M. Allahbakhshi, D. Behi et al., “Utilizing Rogowski coil for saturation detection and compensation in iron core current transformer,” in Proceedings of 25th Iranian Conference on Electrical Engineering (ICEE), Tehran, Iran, May 2017, pp. 1066-1071. [百度学术]
B. Kasztenny and I. Voloh, “Application of distance and line current differential relays in breaker-and-a-half configurations,” in Proceedings of IEEE/PES Transmission and Distribution Conference and Exhibition, Dallas, USA, May 2006, pp. 1-8. [百度学术]
ABB. (2011, Feb.). Line distance protection REL650 technical manual. [Online]. Available: https://library.abb.com/share?cid=9AAC30301058 [百度学术]
Y. Yuan, Y. Lu, Z. Liu et al., “A fast filter algorithm of short data window based on phase analysis,” Automation of Electric Power Systems, vol. 28, no. 3, pp. 58-63, Feb. 2004. [百度学术]
Y. Sun, Z. Zhang, Y. Shi et al., “The short-window integral method for calculating fundamental component from fault transient signalsin power systems,” Automation of Electric Power Systems, vol. 24, no. 1, pp. 30-33, Jan. 2000. [百度学术]
W. Liu, Y. Pan, Y. Wang et al., “Effect of CT transient characteristics on transfer of inrush,” The Journal of Engineering, vol. 2019, no. 16, pp. 3062-3066, Apr. 2019. [百度学术]
N. Farshid, K. Zahra, F. Ebrahim et al., “Fast detection and compensation of current transformer saturation using extended Kalman filter,” IEEE Transactions on Power Delivery, vol. 34, no. 3, pp. 1087-1097, Jun. 2019. [百度学术]
A. Hooshyar and M. Sanaye-Pasand, “Accurate measurement of fault currents contaminated with decaying DC offset and CT saturation,” IEEE Transactions on Power Delivery, vol. 27, no. 2, pp. 773-783, Apr. 2012. [百度学术]