Abstract
Once an asymmetrical fault occurs on the AC side of the receiving-end of a high-voltage direct current (HVDC) transmission system, the current reference will be affected by the control regulation on the DC inverter side and the commutation voltage asymmetry. In this case, the advance firing angle will fluctuate periodically, causing security threats to the system. If the fault cannot be cleared in time, the effect may be even more serious. However, the traditional proportional-integral (PI) controller cannot effectively suppress the periodic components in the input error signal, which is an important cause of continuous commutation failure. Thus, the system requires more time to recover from the fault. Motivated by this, a self-adaptive auto-disturbance rejection PI controller is proposed in this study. The controller has the advantages of fast response speed and strong anti-interference ability of the auto-disturbance rejection controller. On one hand, it can automatically adjust PI, and the parameters can maintain the system’s adaptive ability. On the other hand, the discretization process satisfies the computer simulation requirements. By applying the proposed controller to a system under constant current control and extinction angle control, the dynamic response speed can be improved and the robust performance of the system can be ensured when dealing with a wide range of perturbations. Finally, simulation results show that the proposed algorithm can effectively suppress the continuous commutation failure of DC transmission systems.
UNDER the national development strategy of “power transmission from West to East, mutual supply between North and South and nationwide interconnection”, high-voltage direct current (HVDC) transmission featured by cross-regional ability, large capacity, and asynchronous grid interconnection, is playing an important role in the grid development of China [
The occurrence of CF is related to many factors such as the AC bus voltage, commutation reactance, DC current, converter transformer ratio, and advance trigger angle. Among these, the main reason for CF is that the AC bus voltage drops owing to a ground fault. Generally, the first CF is inevitable. For short-term failure, recovery is normally possible after the fault clearance [
Reference [
Reference [
Existing research has mainly focused on forecasting and topology improvements rather than the analysis of continuous CF and the corresponding control strategy [
Reference [
There are several methods for suppressing continuous CFs at present such as suppression methods based on full-control devices [
An HVDC transmission system exhibits nonlinearity and multivariable strong coupling when disturbed, whereas a traditional PI control framework provides a typical linear control. Therefore, it requires to redesign the controller to improve the performance during transient process.
Auto-disturbance rejection control (ADRC) is a novel control technology that does not depend on a mathematically accurate model of the controlled plant, and manages to automatically detect and compensate for internal and external disturbances. It can achieve good control results even when the control object encounters uncertain disturbances or changes in parameters. This kind of control, owing to its higher adaptability and robustness, is partly applied in the switch and excitation of thermal power units.
Reference [
Reference [
We propose a self-adaptive auto-disturbance rejection proportional integral controller (SAADR-PI) to improve the constant current and constant extinction angle control on the rectifier and inverter sides, respectively.
The remainder of this paper is organized as follows. Section II discusses the mechanisms of single CF and continuous CF, and it is pointed out that the main factors leading to continuous CF are harmonic components in the trigger angle. In Section III, based on the deficiency of the linear PI controller, an SAADR-PI control strategy is proposed to enhance the accuracy of the tracking command value during the transient process. In Section IV, the performance of the proposed strategy is validated through several simulations in RTDS. The results verify the effectiveness of the mechanism analysis of continuous CF and the control strategy proposed in this paper. Finally, Section V concludes this paper.
The Graetz bridge is the most basic structure that constitutes an HVDC converter. As indicated in

Fig. 1 HVDC inverter-side Graetz bridge topology.
Figure A1 in Appendix A shows the voltage and current waveforms of the Graetz bridge in the rectifier and inverter modes. Taking the commutation of inverter-side T1 to T3 as an example, Fig. A1 shows that T1, T2, and T3 are simultaneously conducted during the commutation overlap time , and T2 and T3 are simultaneously conducted during . If the commutation process is not complete or the commutation process is complete but the valve blocking capability is not restored, the valve forward voltage becomes positive, and the valve that is expected to be turned off will be conducted once again. This is called CF [
CF can be divided into single and continuous CF. A single CF implies that only one CF occurs in DC transmission. The first CF after an AC system fault on the inverter side occurs very quickly, and the DC system operates under hysteresis control. The operation begins only if the AC fault is detected. As the operation time is limited, even if preventive control measures are taken, it is difficult to avoid the first CF in DC transmission.
Continuous CF in DC transmission implies that there are one or more CFs in the DC system after the first CF. After the first CF, the DC system control block has sufficient time to adjust and recover from the fault. Therefore, the occurrence of continuous CF is related to the functioning of the DC system control block [
The control block of the DC system adopts a hierarchical control, namely, the system control level, pole control level, and valve control level. The lower the level is, the faster the response of the control will be. The response speed of the valve control is measured in milliseconds. Most research and improvements are aimed at the structure of the pole control level.
This study aims at the control framework in the CIGRE benchmark model [
The measurement is often replaced by a first-order inertia section, where the inertia time constant T reflects the response speed of the measuring device, and the gain G converts the actual values of DC voltage and current into a per-unit value. Figure A2 shows that the rectifier side adopts a constant current controller, and that the inverter side combines a constant current controller and constant extinction angle controller. In addition, the inverter side is equipped with a DC-current bias control, which enables smooth switching from constant extinction angle control to constant current control.
In general, is set as 1 p.u.. After a fault occurs, quickly falls and enables constant extinction angle control. To avoid the first CF, the output of constant extinction angle control will increase the advance trigger angle . The speed of the trigger angle increases depending on the traditional linear PI controller parameters. Considering the CIGRE HVDC benchmark model parameters, it takes 110 ms for to increase to 90° [
After the first CF occurs, one or multiple CFs may occur again during the recovery process owing to the drastic change in the output angle command under DC control. DC transmission may develop from a single CF to a continuous CF. Reference [
Figure A3 in Appendix A shows the simulation results of the CIGRE benchmark model on the RTDS platform. The single-phase ground fault on the AC side occurs at 2 s, and the fluctuation of the electrical quantity can be observed during the two consecutive CFs. The figure shows that the delay trigger angle, extinction angle, and DC current all have second-order harmonic components. In the practical application of AC/DC hybrid power grid engineering, 100 Hz protection is also an important part of DC system protection [
According to the above analysis of continuous CF, the strategy to suppress this problem should start with the following two aspects: first, to solve the second-order harmonic component in the collected electrical quantity; and second, to enhance the tracking accuracy of the trigger angle command and reduce the delay effect. To this end, the following control strategy is proposed to deal with continuous CF.
After the DC system detects a fault, the control strategy starts. After DC low-pass filtering, a second-order band-stop filter with a center frequency of 100 Hz is added to filter out the second-order harmonic component of the DC current signal for reducing the second-order harmonic component of the advance trigger angle command .
Given that the linear PI controllers cannot achieve good performance for nonlinear systems such as HVDC, a novel controller is designed based on the idea of the ADRC theory to replace the original PI controller and improve the tracking accuracy of the trigger angle command under internal and external disturbances. The steps will be introduced in detail as below.
The dynamic equation of the line commutated converter(LCC) HVDC transmission system can be expressed as:
(1) |
where and are the rectifier-side and inverter-side total impedances, respectively; is the DC capacitor; is the DC resistance; is the voltage of the DC capacitor; and , , and are the commutation reactance, AC bus voltage, and DC current on the rectifier side, respectively. Correspondingly, , , and represent those on the inverter side. is the rectifier-side delay firing angle; and is the inverter-side advance firing angle. Considering the trigger delay of the control section, we obtain:
(2) |
where is the constant time of delay firing angle ; is the constant time of advance firing angle ; and are the reference delay firing angle and the reference advance firing angle, respectively; and and are the control laws of the rectifier-side delay firing angle and the inverter-side advance firing angle, respectively.
For the control targets of the rectifier side and the inverter side, the constant current control is the tracking current command, and (3) is guaranteed:
(3) |
The inverter-side constant extinction angle should guarantee the following output:
(4) |
where is the reference inverter-side extinction angle.
By deriving (1) on both sides, we obtain:
(5) |
Then, by substituting (2) into (1), the standard form of input/output is derived as:
(6) |
where is the disturbance variable in the rectifier-side state function. The function and parameter in (6) are as follows:
(7) |
(8) |
(9) |
By combining (2), the standard form of input or output is expressed as:
(10) |
where is the disturbance variable on the inverter-side state function; and bi is given as:
(11) |
Similarly, a first-order ADRC can be used as a control.
The ADRC consists of three parts: tracking differentiator (TD), extended state observer (ESO), and nonlinear state error feedback (NLSEF). The ADRC compensates for the disturbance to the system by accurately estimating the total disturbance. Simplifying the system equivalent to a series integral structure by estimation and compensation, the control law of the controlled plant can be easily designed. The advantages include independence of the precise mathematical model of the controlled object, strong anti-disturbance ability, and good adaptability. A typical block diagram of an ADRC controller is shown in

Fig. 2 Auto-disturbance rejection algorithm control block diagram.
In
Taking the second-order system as an example, the specific algorithm has three parts:
1) Setting as the input signal at sampling instant k, the transition process can be arranged and the input can be extracted as (12).
(12) |
where , are the arranged transition processes at sampling instant k and , respectively, which are differentiable smooth signals; and represent and , respectively; h is the integration step length; and h0 is the parameter that determines the filtering effect when the input signal is contaminated by noise. The function is expressed as:
(13) |
(14) |
(15) |
where r and h are the adjustment parameters.
2) The observation of system states and extended states (total disturbances) by input u and output y can be expressed as:
(16) |
where , , , , and are the adjustment parameters; and b0 is the estimated value of b. The function can be expressed as:
(17) |
where is a constant related to the tracking effect, which is inversely proportional to the tracking effect, whereas the filtering effect is degraded when decreases; and is a constant that affects the filtering effect and is proportional to the filtering effect, whereas its increase causes a tracking delay. When the signal error is large, the function produces a small feedback gain. This satisfies the requirements of system stability and rapidity.
3) Finally, the state error feedback control law is designed as:
(18) |
where e1 and e2 are the errors between the arranged transition process v1 and system output estimate z and the differential of this error, respectively. The nonlinear control of the series integral plant is realized by selecting the nonlinear parameters , , , and parameters kP and kD reasonably.
The SAADR-PI controller inherits the advantages of fast response speed and strong anti-interference ability of the ADRC controller. Moreover, it can automatically adjust the PI parameters through the function to maintain the adaptive ability of the system. By applying it to the current and turn-off angle control strategy, the dynamic response speed and the robust performance of the system can both be improved.
This paper applies an SAADR-PI controller to the rectifier-side constant current and the inverter-side constant extinction angle control strategy to replace the traditional linear PI controller. The DC system closed-loop control block diagram is shown in

Fig. 3 Improved closed-loop control block diagram of HVDC transmission system.
The parameters of the tracking differentiator are adjusted according to the requirements of the transition process. The larger the speed factor r is, the faster the tracking speed will be [
The parameter in the function determines the degree of nonlinearity. The following principles are based on engineering application experience. In a proportional link, is set to achieve the goal of “large gain for small error, small gain for large error”. The differential link requires that the differential gain is small (large) when the differential error is small (large), so we set . Thus, the differential effect will be smaller when it is close to the steady state, which will help improve the performance of the control system [
The CIGRE HVDC benchmark model is built using the RTDS simulation software to verify the control method for suppressing continuous CF [
The main parameters of the test model are listed in Table BI in Appendix B, and the parameter settings in the control strategy are shown in Table BII.
A ground fault is applied on the inverter-side commutation bus, and the adjustable grounding inductance value Lf is used to simulate the different distances of the AC system faults from the commutation bus. The smaller the grounding inductance value is, the closer the AC system fault is to the commutation bus, and the more serious the fault will be [
1) Control method 1: only the original CIGRE HVDC benchmark model control block is used.
2) Control method 2: based on the control of the CIGRE HVDC benchmark model, the virtual resistance current-limiting method proposed in [
3) Control method 3: the proposed SAADR-PI controller is used.
Control methods 1 and 2 are compared with control method 3 proposed in this paper in order to verify the effect of the proposed algorithm in suppressing continuous CF. This paper focuses on the response of physical quantities such as the extinction angle, DC current, DC voltage, and DC transmission power after failure. Among these, the extinction angle response curve is used to judge whether the DC power transmission fails to commutate. The DC current, DC voltage, and transmission power response curve are used to observe the dynamic process during the fault. To facilitate the comparison, the response curves of the above physical quantities using the three control methods are placed in the same coordinate system. In

Fig. 4 DC system response curve under different asymmetric fault types. (a) Single-phase ground fault with grounding inductance H. (b) Two-phase phase-to-phase short circuit with fault inductance H. (c) Two-phase grounding short circuit with grounding inductance H.
When there is a single ground fault at 4 s on the inverter-side converter bus, the grounding inductance H, and the fault lasts for 0.5 s. Under the fault condition, the simulation results of the respective electric quantities using the three control methods are shown in
With regard to the first CF, the fault time on the inverter-side AC bus is very short, and the DC system control block has limited action. After the fault, it is difficult to avoid the first CF. However, an appropriate control method such as control method 2 can effectively avoid the second CF. VDCL is activated by the virtual resistor in advance, but the first CF cannot be avoided. Control method 3 effectively avoids the first CF and continuous CF.
Since the controller does not change the original control frame, the inverter side still adopts constant extinction control during the fault. The DC voltage is always approximately 0.9 p.u. during the AC voltage drop, and the power level is also 0.9 p.u.. Moreover, it recovers to the rated operation point within 0.1 s after the fault is cleared. This shows the effective tracking capability of the SAADR-PI controller and meets the requirements of actual engineering operations.
Similarly, by applying a phase-to-phase short circuit and a two-phase grounding fault to an AC system, the fault inductance is set to be 1.12 H and 0.95 H, respectively, and the system simulation waveforms are shown in
As the probability of CF is closely related to the initial fault time, it is necessary to examine the impact of different initial fault times on the performance of the control strategy under the same fault [
The white marks in Figs. C1-C3 show that no CF occurs in the original CIGRE benchmark model. The green marks indicate that no CF occurs under the proposed control strategy. The yellow marks indicate that only the first CF occurs under the proposed control strategy. And the red marks indicate that a continuous CF occurs more than twice. It can be seen from the figure that continuous CF is most likely to occur between 4.006 s and 4.016 s because the valve is about to be commutated or is under the process of commutation. Therefore, the control strategy responds too late. For the rest of the time when the fault is quite severe, the voltage drop on the AC side makes it impossible to support the completion of the commutation, which will also result in the occurance of continuous CF.
This study analyzes the characteristics of electric quantity changes after asymmetrical faults such as phase-to-ground on an inverter-side AC bus. Then, a method is proposed to suppress continuous CF based on ADRC. The conclusions are as follows.
1) After a fault occurs, abundant second-order harmonic components appear in the DC current and extinction angles of the DC system, causing the trigger angle to exhibit significant periodic fluctuations. This is the main cause of continuous CF in the system.
2) A control strategy for a discrete computer simulation is designed based on the ADRC theory. By improving the response rate and enhancing the robustness under external disturbances, the system can effectively suppress continuous CF and shorten the recovery time after system failure. The simulation results verifiy the effectiveness of the proposed algorithm.
Appendix

Fig. A1 Voltage and current waveforms of converter in rectifier and inverter modes.

Fig. A2 Diagram of CIGRE HVDC control block.

Fig. A3 Electrical quantities waveform under continuous CF. (a) . (b) . (c) .

Fig. A4 Topology of CIGRE HVDC benchmark model. Appendix B
The parameters of CIGRE HVDC benchmark model and SAADR-PI controller are given in Tables BI and BII, respectviely.

Fig. C1 Statistics of simulation results of single-line-to-ground faults under different ground reactance and fault times.

Fig. C2 Statistics of simulation results of line-to-line faults under different ground reactance and fault times.

Fig. C3 Statistics of simulation results of two-line-to-ground faults under different ground reactance and fault times.
REFERENCES
X. Zhou, S. Chen, Z. Lu et al., “Technology features of the new generation power system in China,” Proceedings of the CSEE, vol. 38, no. 7, pp. 1893-1904, Jul. 2018. [百度学术]
T. An, C. Han, Y. Wu et al., “HVDC grid test models for different application scenarios and load flow studies,” Journal of Modern Power Systems and Clean Energy, vol. 5, no. 2, pp. 262-274, Jul. 2016. [百度学术]
Y. Xue, X. Zhang, and C. Yang, “Commutation failure elimination of LCC HVDC systems using thyristor-based controllable capacitors,” IEEE Transactions on Power Delivery, vol. 33, no. 3, pp. 1448-1458, Jun. 2018. [百度学术]
Y. Tang and C. Zheng, “Review on influencing factors of commutation failure in HVDC systems,” Proceedings of the CSEE, vol. 39, no. 2, pp. 499-513, Jan. 2019. [百度学术]
T. Zhu, W. Ning, and K. Ou, “Discussion on commutation failure in HVDC transmission system,” Power System Protection and Control, vol. 36, no. 23, pp. 116-120, Dec. 2008. [百度学术]
X. Li, S. Chen, T. Li et al., “Research on the periodic commutation failure by 1000 kV UHV transformer energizing for LinFeng HVDC Project,” Power System Technology, vol. 38, no. 10, pp. 2671-2679, Dec. 2014. [百度学术]
Z. Wei, Y. Yuan, X. Lei et al., “Direct-current predictive control strategy for inhibiting commutation failure in HVDC converter,” IEEE Transactions on Power Systems, vol. 29, no. 5, pp. 2409-2417, Sept. 2014. [百度学术]
H. Son and H. Kim, “An algorithm for effective mitigation of commutation failure in high-voltage direct-current systems,” IEEE Transactions on Power Delivery, vol. 31, no. 4, pp. 1437-1446, Aug. 2016. [百度学术]
L. Wang, G. Wang, H. Li et al., “Risk evaluation of commutation failure in multi-infeed HVDC systems under AC system fault conditions,” Automation of Electric Power Systems, vol. 35, no. 3, pp. 9-14, Mar. 2011. [百度学术]
C. Guo, C. Li, Y. Liu et al., “A DC current limitation control method based on virtual-resistance to mitigate the continuous commutation failure for conventional HVDC,” Proceedings of the CSEE, vol. 36, no. 18, pp. 4930-4937, Sept. 2016. [百度学术]
L. Liu, S. Lin, and Z. He, “A novel method based on virtual commutation area insufficient to mitigate the continuous commutation failure for HVDC,” Proceedings of the CSEE, vol. 38, no. 18, pp. 5361-5368, Jul. 2018. [百度学术]
R. Li, Y. Li, and X. Chen, “A control method for suppressing the continuous commutation failure of HVDC transmission,” Proceedings of the CSEE, vol. 38, no.17, pp. 5029-5042, Jul. 2018. [百度学术]
L. Jing, Bin Wang, X. Dong et al., “An overview of continuous commutation failure in HVDC transmission system,” Electric Power Automation Equipment, vol. 39, no. 9, Jan. 2019. [百度学术]
X. Ni, C. Zhao, C. Guo et al., “Enhanced line commutated converter with embedded fully controlled sub-modules to mitigate commutation failures in high voltage direct current systems,” IET Power Electronics, vol. 9, no. 2, pp. 198-206, Oct. 2016,. [百度学术]
G. Zhang, Z. Liu, S. Yao et al., “Suppression of low-frequency oscillation in traction network of high-speed railway based on auto-disturbance rejection control,” IEEE Transactions on Transportation Electrification, vol. 2, no. 2, pp. 244-255, Jun. 2016. [百度学术]
Y. Tao, S. Shen, D. Li et al., “Study on auto-disturbance-rejection control for HVDC system,” Automation of Electric Power Systems, vol. 26, no. 22, pp. 22-26, Nov. 2002. [百度学术]
Y. Yuan, Z. Wei, X. Lei et al., “Survey of commutation failures in DC transmission systems,” Electric Power Automation Equipment, vol. 33, no. 11, pp. 140-147, Jan. 2013., [百度学术]
X. Li, S. Chen, X. Lei et al., “Optimization of commutation failure prevention and automatic recovery for east China multi-infeed high-voltage direct current system,” Automation of Electric Power Systems, vol. 39, no. 6, pp. 134-140, Jun. 2005. [百度学术]
S. Mirsaeidi and X. Dong, “An enhanced strategy to inhibit commutation failure in line-commutated converters,” IEEE Transactions on Industrial Electronics, vol. 67, no. 1, pp. 340-349, Jan. 2020. [百度学术]
L. Zeng, Y. Li, Y. Zhang et al., “Research on mechanism and control strategy of continuous commutation failures in HVDC system caused by asymmetrical fault in inverter-side AC system,” Proceedings of the CSEE, vol. 39, no. 11. pp. 3159-3168, Jun. 2019. [百度学术]
C. Fu, H. Rao, and X. Li, “HVDC 50 Hz and 100 Hz protection of AC/DC hybrid transmission system,” Automation of Electric Power Systems, vol. 32, no. 12, pp. 57-60, Dec. 2008. [百度学术]
X. Xu, Y. Zou, and J. Guo, “Control system of cascade multilevel STATCOM based on auto-disturbance rejection controller,” Proceedings of the CSEE, vol. 27, no. 31, pp. 40-44, Nov. 2007. [百度学术]
H. Li, J. Shang, Y. Chen et al., “The applications of nonlinear PI controller based on the fal function in the DC-DC converter,” Transactions of China Electrotechnical Society, vol. 29, no. 1, pp. 326-331, Sept. 2014. [百度学术]
H. Huang, L. Wu, and J. Han. “A Study of active disturbance rejection control on unit coordinated control system in thermal power plant,” Proceedings of the CSEE, vol. 24, no. 10, pp. 170-175, Oct. 2004. [百度学术]
M. Szechtman, T. Wess, and C. V. Thio, “A benchmark model for HVDC system studies,” in Proceedings of International Conference on AC and DC Power Transmission, London, UK, Sept. 1991, pp. 374-378. [百度学术]
Y. Sun, L. Peng, F. Ma et al., “Design a fuzzy controller to minimize the effect of HVDC commutation failure on power system,” IEEE Transactions on Power Systems, vol. 23, no. 1, pp. 100-107, Feb. 2008. [百度学术]
C. Li, C. Liu, Z. Zhang et al., “Analysis of commutation failure in HVDC power transmission system considering prediction control of commutation failure and initial fault angle,” Automation of Electric Power Systems, vol. 42, no. 3, pp. 56-63, Mar. 2018. [百度学术]