Abstract
The high-voltage direct current (HVDC) grid has been recognized as an effective solution for renewable energy integration. Currently, two main development trends for HVDC grids are being studied: a DC breaker based HVDC grid and fault-blocking converter based HVDC grid. Although the former has a perfect performance for fault clearance, its development is still highly constrained by the cost and maturity of DC breakers. The latter can extinguish DC faults by the fault-blocking converters. Without using DC breakers, there is no bottleneck in its technical feasibility. Nevertheless, in fault scenarios, such types of HVDC grids will be blocked at length for air-deionization, which is its main drawback. The aim of this paper is to minimize its power interruption time, by optimizing protection coordination strategies. To cover the most complex cases, the overhead line applications, in which the reclosure actions are required to be implemented, are considered. In this paper, the protection requirements of HVDC grids are first discussed, then the benefits of fault-blocking modular multilevel converters (MMCs) and their fault features are analyzed. Based on this, a control function is designed to reduce the air-deionization time. To minimize the influence of the DC faults, a separation methodology for restarting the system is proposed. The effectiveness of the proposed protection coordination schemes is validated by PSCAD/EMTDC simulations.
THE high-voltage direct current (HVDC) grid is effective for the reliable integration of large-scale renewable energy. It can be connected directly to weak power grids in renewable energy concentration areas and is far easier for realizing the optimal allocation of different energy resources [
Nevertheless, it has been recognized that the conventional half-bridge modular multilevel converter (MMC) is vulnerable to DC faults [
Currently, available configurations proposed for the HVDC grid can be classified into two approaches. One is to use a high-voltage DC circuit breaker (DCCB) to isolate the faulty DC lines [
In terms of the fault-blocking converter based HVDC grid, the current primary concentration is focusing on the converter level. For example, several topologies are proposed with the capability of blocking fault currents, and further studies are being carried out to optimize the performance of the entire system [
Regarding the protection philosophies for the entire HVDC grid, most studies primarily concentrated on the quick identification of DC line faults [
However, in terms of DC faults, the primary bottleneck is the long-period blocking activity, which will be deteriorated, especially taking into account the reclosure requirement for overhead line applications. Currently, there is little literature to discuss this aspect further.
The primary objective of this paper is to minimize the blocking duration of the fault-blocking converter based HVDC grids. In Section II, the protection requirements of an HVDC grid are discussed, then the system configuration and the basic characteristics of the key components are briefly introduced. In Section III, the fault feature of a fault-blocking converter based HVDC grid is analyzed and the conventional protection scheme is presented. In Section IV, the optimized solution is proposed, which includes a control function to reduce the air deionization time and a coordination method to manage the fault reclosure issue. In Section V, the proposed strategies are verified by simulations. Finally, the conclusions are drawn in Section VI.
Typically, the protection requirements of an HVDC grid can be classified into three protective levels (PLs).
1) Normal operation of critical equipment (PL1): the critical equipment of HVDC grids is normally composed of power electronic devices such as the converters and DCCBs, whose overcurrent withstanding capabilities are strictly limited. The ideal protection objective of an HVDC grid is to ensure that all converters should not be blocked before the fault is isolated. However, due to the high fault current rising rate in the HVDC grid, the protection threshold of the converter is normally reached in several milliseconds. To achieve the objective, it requires very fast fault detection, location, and isolation speed. The protection action usually has to be done within several milliseconds, which leads to the highest requirement for the protection system.
2) Stable operation of an HVDC grid (PL2): due to the limited performance of existing protection systems and devices, it is inevitable that some of the converters are already blocked before the fault is isolated in some scenarios. However, this result can be acceptable as long as the quantity of the blocked converters will not cause the outage of the entire HVDC grid. The blocked converters can also be de-blocked and resume operation once the fault is cleared. Compared with PL1, this level has lower requirements on the capability of the key equipment and the protection time can also be prolonged to ten milliseconds.
3) Stable operation of an alternation current (AC) system (PL3): an HVDC grid is normally embedded into an AC system. Under extreme conditions, all DC converters are blocked or unable to transmit power. This may cause a significant impact on the AC system. The outage of an HVDC grid is allowed but at least cannot cause the instability of the AC system. In other words, the AC system stability becomes the design criteria. This demand has the lowest requirement for protection speed, but often causes the worst consequences. Normally, such a PL could be used for a strong AC system with an embedded small-scale HVDC grid. However, as the influencing extent strongly depends on the outage time, to extend the feasible application scope of such a solution, it is an essential issue to reduce the blocking time of the converters.

Fig. 1 Two kinds of configurations for HVDC grids. (a) Configuration based on HB-MMC and DCCB. (b) Configuration based on FB-MMC and fast DC mechanical switch.
1) Configuration based on half-bridge based MMC (HB-MMC) and DCCB: according to the aforementioned three PLs, both PL1 and PL2 need to isolate the fault within 10 ms, and the fast DCCB is the most feasible solution to realize this. In such a case, HB-MMCs can be used to reduce the overall equipment cost. The corresponding system configuration is shown in
Current feasible DCCB technologies include the mechanical type and the hybrid DCCB type which combines mechanical and semiconductor switches. This paper uses the hybrid DCCB as an example for demonstration, as shown in

Fig. 2 Typical topology of hybrid DCCB.
2) Configuration based on full-bridge based MMC (FB-MMC) and fast DC mechanical switch: as mentioned above, PL3 has no technical requirement for cutting off large fault current in a short time. This can avoid the use of DCCBs which are normally expensive and not mature enough. However, the HB-MMC itself cannot cut off the fault current and must rely on tripping the AC breaker. To avoid such a long fault clearance and restart time, another preferred choice which is consistent with PL3 is the configuration adopting fault-blocking converters. The system can realize the isolation of the AC and DC systems by blocking all the converters or transferring their control modes. Then, the fault line can be isolated by DC fast mechanical switches. The corresponding system configuration is shown in
The key components related with fault clearance performance are the fault-blocking converters (CS1-CS4) and DC fast mechanical switches (QS1-QS12), which are briefly introduced below.
Several topologies such as FB-MMC, hybrid MMC, alternate arm converter (AAC) have been proven able to realize the fault-blocking functionality [
The blocking idea is straightforward. After blocking the converters, the fault current injected by the converters will be stopped immediately.
For the latter idea, the converter will reduce its DC voltage to zero instead of blocking the converter, to avoid further development of fault current. During this period, thanks to its negative voltage output capability, the AC voltage waveform can still be maintained and the converter can still provide reactive power for the AC grid.
For demonstration, the typical FB-MMC is used in this paper and its topology is shown in

Fig. 3 Topology of FB-MMC.
The typical topology of a DC fast mechanical switch is shown in

Fig. 4 Typical topology of DC fast mechanical switch.
The passive-type mechanical switch utilizes the instability and negative resistance characteristics of the arc to generate a self-excited oscillating current. A parallel conversion circuit (composed of a capacitor and a reactor) is connected across the device to cause the current to oscillate, thereby generating a zero-crossing point and forcing the zero-crossing current.
The topology of the switch is similar to those used in the neutral zone of conventional HVDC. However, the type used for an HVDC grid can withstand higher DC voltage during normal operation. Currently, the product reaching up to 200 kV has been applied in the Zhoushan five-terminal voltage source converter based HVDC (VSC-HVDC) project in China and a higher voltage rating is being further developed.
For a quantitative description, this subsection gives a general technical economy comparison between HB-MMC with DCCB (Scheme 1) and FB-MMC with DC fast mechanical switches (Scheme 2).
The comparison is based on the four-terminal system and the detailed parameters are shown in
It can be seen that the extra cost of Scheme 1 is almost double that of Scheme 2. Furthermore, as other hybrid topologies for fault-blocking converters can further reduce the quantity of extra semiconductors, the cost of Scheme 2 can be further optimized.
However, it is obvious that the fault clearance performance of Scheme 1 is better than that of Scheme 2. It is also the target of this paper to promote the technical performance of Scheme 2.
During a DC pole-to-pole fault, the fault current is contributed by two sources. One is the energy released from overhead line, the other is the discharging current from converter stations, as shown in

Fig. 5 Fault features for fault-blocking converter based HVDC grid. (a) Fault current sources. (b) Fault current waveforms.
The former will lead to a high-frequency oscillation current, which will be injected into the fault location. The converters can act as parallel branches to share this current with the fault location. This point can be seen as an advantage of active control compared with blocking the converters, as blocking will make the converters unable to share, thereby leading to much higher oscillation current into the fault location and hampering the air deionization, as shown in
The fault currents contributed by converter stations are primarily caused by the discharge of internal capacitors. After the fault is detected, the converter reduces its DC output voltage to zero. The change of equivalent DC circuit configuration from the perspective of one converter station is illustrated in

Fig. 6 Equivalent circuit of converter discharging process.
Before the DC voltage control is activated, the development of fault current is very close to that of HB-MMC. However, after blocking of the HB-MMC, the fault current is still continuously fed from the AC systems and will only decay after the AC breaker is tripped. For FB-MMC, AC output remains effectively controlled (even if the DC voltage is reduced to zero), thus it will only present a current decaying process on the DC side.
Based on the equivalent circuit above and assuming that the Req in the circuit is normally small, the fault current contributed by the converter can be expressed as:
(1) |
where I0 and are the initial steady-state DC current and the DC current at the time instant T0, respectively; ; , ; .
To obtain the fault current distribution of the entire network, the calculation methods proposed for the HVDC grid in many studies are applicable and will not be presented in detail in this paper [
It can be observed that the decay of fault current will normally take a lot of time and delay the fault clearance, which is an important issue to be managed.
Taking a fault on line T12 as an example, the overall protection sequence based on fault-blocking converters is as follows (only a one-time restart is considered).
t1: fault occurs.
t1-t2 (several milliseconds): the fault needs to be detected quickly by the protection system, and converters need to be controlled to reduce the DC voltage.
t2-t3 (several hundred milliseconds): waiting for the delay of fault current and air deionization.
t3-t4 (tens of milliseconds): the DC voltages of the converters are gradually increased to restart the system. The system is restarted successfully if the DC voltage has been established and then the converter power can be gradually restored to normal operation.
t4-t5 (several hundred milliseconds): if the DC voltage has not been successfully re-established, the voltage control needs to be re-activated and wait for the decay of fault current.
t5-t6 (tens of milliseconds): faulty line is tripped by DC fast mechanical switches. Then the system can recover to another operation state.
The state signals of the main equipment during the entire process are shown in

Fig. 7 State signals of main equipment during entire process.
It is observed that the long fault clearance time is caused by the decay of discharging current of capacitors. The decaying time relates to the resistance and reactance in the current loop, which cannot be practically controlled.
To accelerate the decaying process, the most efficient way is to utilize the active control capability of the converters. Different from the HB-MMC, the FB-MMC is capable of generating negative voltage. The basic idea is that by involving an extra voltage source, a reverse current can be generated to compensate the fault current, the equivalent circuit of which is shown in

Fig. 8 Equivalent circuit after inserting negative voltage.
To generate negative voltage of the appropriate value, a controller comparing the DC terminal current with its reference value can be designed as follows:
(2) |
where uref is the reference order of the negative voltage generated by the converter; Kp and Ki are the proportional and integral coefficients of the proportional-integral (PI) controller, respectively; and iref is the reference order of the DC current idc.
It is complex to obtain the detailed response of a fault current under the input of a four-terminal voltage source. However, it can be foreseen that the fault current is primarily influenced by the converter stations close to the fault location, thus a proximate calculation can be done by neglecting the contribution of remote stations and long circuit loops. The equivalent circuit can be simplified as

Fig. 9 Equivalent circuit after simplification.
The fault current contributed by CS1 can be expressed as:
(3) |
where .
Similarly,
(4) |
where .
Then, the fault current can be expressed as:
(5) |
The above result is based on the assumption that the converter stations are adopting the same control function and gains. According to (4), it can be seen that the fault current can be effectively controlled without static error.
As mentioned previously, whether the fault is cleared can be judged by re-establishing the DC voltage at a pre-determined value. Moreover, as each converter can independently complete the task, it is able to select only a single converter to distinguish the fault and this is helpful in reducing the extent of the impact on the entire grid.
Taking the fault on line T12 as an example, the state signals of the equipment are shown in

Fig. 10 Circuit during fault isolation and recovery and optimized protection sequence. (a) Circuit during fault isolation and recovery. (b) State signals of main equipment.
t1: the fault occurs.
t2: four converter stations are actively controlled.
t3: fault current is controlled within a certain level and DC fast mechanical switches QS1 and QS5 are opened. Simultaneously, CS1, CS3, and CS4 are deblocked and recover normal operation.
t4 -t5: CS2 attempts to re-establish the DC voltage. If no protection action occurs, the fault is identified to be temporary. Then, QS1 and QS5 can be closed to reconnect CS2 with the other stations. Otherwise, CS2 will be actively controlled again.
t6: after the fault current decays, the DC fast mechanical switch QS2 is opened.
t6 -t7: CS2 controls its DC voltage to its rated level.
t7: QS5 is reclosed to connect CS2 with the other stations.
It can be seen from
To verify the proposed protection strategies, the four-terminal meshed HVDC grid model with FB-MMCs and DC fast mechanical switches is established in PSCAD/EMTDC.
In the model, the AC systems are equivalent ideal voltage sources with an impedance shown in
The DC voltage of entire HVDC grid is controlled by CS4 whereas all the other converter stations (CS1-CS3) operate in active power control mode whose values are set as +1.0, -1.0, and +0.5 p.u., respectively (positive means operating as a rectifier).
As shown in

Fig. 11 Waveforms of a conventional protection scheme under a permanent fault.
The protection system detects the fault in 3 ms after the fault occurrence and immediately reduces the DC voltage.
After that, the DC current starts to slowly decay and after almost 300 ms, it is close to zero and the air deionization is deemed to be completed.
It is observed that during this period, the converters can still generate 0.4 p.u. reactive power to the AC system. Additionally, the high-frequency oscillation current appears in all bridge arms of each converter station, sharing the discharging current of overhead lines with the fault point, which accelerates the decay of high-frequency current.
At 1.3 s, the converter stations try to recover the DC voltage gradually but fails at 1.32 s, as high impulse current presents again. The converters implement the active voltage control once more after another 300 ms, and the switches QS1 and QS2 are opened as the fault is identified as permanent. Then, the converter stations can be quickly recovered to normal operation. It is observed that nearly 600 ms of power interruption occurs due to the fault. This is not acceptable for an HVDC grid and may cause the instability of the corresponding AC system.
Waveforms based on the optimized solution are given in

Fig. 12 Waveforms of optimized protection scheme under a permanent fault. (a) Switching sequences of QS1, QS2, and QS5. (b) Fault current. (c) Waveforms of CS1. (d) Waveforms of CS2. (e) Waveforms of CS3. (f) Waveforms of CS4.
With QS1 and QS5 opened, the CS2 can perform the fault distinguishing activity independently. However, after the failure of restart, the fault is deemed as permanent, then the QS2 is opened at t6. The CS1, CS3, and CS4 can be quickly recovered to normal operation after the fault is isolated by the switches QS1 and QS5 at s, assuming that mechanical switches can be opened in 20 ms.
During t6 and t7, a certain time is reserved between the open of QS2 and the close of QS5. The period is used for the re-establishment of DC voltage of CS2, thus it can connect with the other stations without significant disturbance.
During the entire process, the power interruption of CS1, CS3, and CS4 only lasts within 100 ms. The CS2 can also recover to normal power transmission within 400 ms after the fault. When CS2 is absent from the grid, the power balance is maintained by CS4, absorbing the power injected by both CS1 and CS3. After CS2 is reconnected and participates in the power balance, the power level of CS4 recovers to a normal state.
To demonstrate the effectiveness of the current controller further, the main parameters of the case are substituted in (4) to obtain a quantitative calculation result of the fault current, which is then compared with the simulation results.
The calculated results are shown in (6), where Kp = 50, Ki = 1000, Rf1 = Rf2 = 4.43 Ω, L1Σ = L2Σ = 0.3 H. It should be noted that the resistance is mainly contributed by the overhead line, while the reactance is contributed by both the overhead line and converter reactors.
(6) |
Based on (5), the calculation and simulation results are constructed in

Fig. 13 Comparison between calculation and simulation results.
Aimed at improving the DC fault performance for the HVDC grid based on fault-blocking converter, the optimized protection strategies with special consideration on the reclosure issue are proposed in this paper.
Based on the proposed current damping control strategy, the decay of fault current can be accelerated and controlled within 50 ms. Combined with the proposed fault reclosure methodology, most converters can be isolated from the fault and recovered to normal operation within 100 ms, leading to less impact on the HVDC grid and AC system.
References
N. Ahmed, A. Haider, D. V. Hertem et al., “Prospects and challenges of future HVDC supergrids with modular multilevel converters,” in Proceedings of the 14th European Conference on Applications, Birmingham, UK, Aug.-Sept. 2011, pp. 1-10. [百度学术]
D. V. Hertem, M. Ghandhari, and M. Delimar, “Technical limitations towards a supergrid–a European prospective,” in Proceedings of IEEE International Energy Conference and Exhibition, Manama, Bahrain, Dec. 2010, pp. 1-10. [百度学术]
A. Lesnicar and R. Marquardt, “An innovative modular multilevel converter topology suitable for a wide power range,” in Proceedings of IEEE Bologna Power Tech Conference, Bologna, Italy, Jun. 2003, pp. 3-6. [百度学术]
R. Allebrod, S. Hamerski, and R. Marquardt, “New transformerless, scalable modular multilevel converters for HVDC-transmission,” in Proceedings of IEEE Power Electronics Specialists Conference, Rhodes, Greece, Jun. 2008, pp. 174-179. [百度学术]
H. Huang, “Multilevel voltage-sourced converters for HVDC and FACTs applications,” in Proceedings of CIGRE SC B4 2009 Bergen Colloquium, Bergen, Norway, Apr. 2009, pp. 1-5. [百度学术]
J. Dorn, H. Huang, and D. Retzmann, “A new multilevel voltage-sourced converter topology for HVDC applications,” in Proceedings of CIGRE Session, Paris, France, Oct. 2008, pp. 1-8. [百度学术]
G. Song, J. Hou, B. Guo et al., “Pilot protection of hybrid MMC DC grid based on active detection,” Protection and Control of Modern Power Systems, vol. 5, no. 1, pp. 82-96, Feb. 2020. [百度学术]
Y. Wang and R. Marquardt, “Future HVDC-grids employing modular multilevel converters and hybrid DC-breakers,” in Proceedings of EPE 15th European Conference on Power Electronics and Applications, Lille, France, Sept. 2013, pp. 1- 8. [百度学术]
C. M. Franck, “HVDC circuit breakers: a review identifying future research needs,” IEEE Transactions on Power Delivery, vol. 26, no. 2, pp. 998-1007, Apr. 2011. [百度学术]
R. Derakhshanfar, T. U. Jonsson, U. Steiger et al., “Hybrid DC breaker–a solution for future HVDC system,” in Proceedings of CIGRE Session, Paris, France, Aug. 2014, pp. 1-12. [百度学术]
R. Marquardt, “Modular multilevel converter: an universal concept for HVDC-networks and extended dc-bus-applications,” in Proceedings of International Power Electronics Conference, Sapporo, Japan, Jun. 2010, pp. 502-507. [百度学术]
R. Marquardt, “Modular multilevel converter topologies with DC-short circuit current limitation,” in Proceedings of IEEE 8th International Conference on Power Electronics, May-Jun. 2011, Jeju, South Korea, pp. 1425-1431. [百度学术]
W. Grieshaber, J.-P. Dupraz, D.-L. Penache et al., “Development and test of a 120 kV direct current circuit breaker,” in Proceedings of CIGRE Session, Paris, France, Aug. 2014, pp. 1-10. [百度学术]
W. Zhou, X. Wei, S. Zhang et al., “Development and test of a 200 kV full-bridge based hybrid HVDC breaker,” in Proceedings of 17th European Conference on Power Electronics and Applications, Geneva, Switzerland, Sept. 2015, pp. 1-10. [百度学术]
P. Fairley. (2013, May). Germany takes the lead in HVDC–new developments in high-voltage DC electronics could herald an epic shift in energy delivery? [Online]. Available: https://spectrum.ieee.org/energy/re-newables/germany-takes-the-lead-in-hvdc/ [百度学术]
R. Oliveira and A. Yazdani, “A modular multilevel converter with DC fault handling capability and enhanced efficiency for HVDC system applications,” IEEE Transactions on Power Electronics, vol. 32, no. 1, pp. 11-22, Jan. 2017. [百度学术]
R. Li, G. P. Adam, D. Holliday et al., “Hybrid cascaded modular multilevel converter with DC fault ride-through capability for the HVDC transmission system,” IEEE Transactions on Power Delivery, vol. 30, no. 4, pp. 1853-1862, Aug. 2015. [百度学术]
M. M. C. Merlin, T. C. Green, P. D. Mitcheson et al., “A new hybrid multi-level voltage-source converter with DC fault blocking capability,” in Proceedings of 9th IET International Conference on AC and DC Power Transmission, London, UK, Oct. 2010, pp. 1-10. [百度学术]
R. Feldman, E. Farr, A. Watson et al., “DC fault ride-through capability and STATCOM operation of a HVDC hybrid voltage source converter,” IET Generation, Transmission & Distribution, Jan. 2014, pp. 114-120. [百度学术]
M. M. C. Merlin, T. C. Green, P. D. Mitcheson et al., “The alternate arm converter: a new hybrid multilevel converter with DC-fault blocking capability,” IEEE Transactions on Power Delivery, vol. 29, no. 1, pp. 310-317, Feb. 2014. [百度学术]
R. Zeng, L. Xu, L. Yao et al., “Precharging and DC fault ride-through of hybrid MMC-based HVDC systems,” IEEE Transactions on Power Delivery, vol. 30, no. 3, pp. 1298-1306, Jun. 2015. [百度学术]
J. Descloux, P. Rault, S. Nguefeu et al., “HVDC meshed grid: control and protection of a multi-terminal HVDC system,” in Proceedings of CIGRE Session, Paris, France, Aug. 2012, pp. 1-10. [百度学术]
K. Nanayakkara, A. Rajapakse, and R. Wachal, “Traveling-wave-based line fault location in star-connected multiterminal HVDC systems,” in Proceedings of IEEE PES General Meeting, Vancouver, Canada, Jul. 2013, pp. 1-10. [百度学术]
S. Azizi, M. Sanaye-Pasand, M. Abedini et al., “A traveling-wave-based methodology for wide-area fault location in multiterminal DC systems,” IEEE Transactions on Power Delivery, vol. 29, no. 6, pp. 2552-2560, Dec. 2014. [百度学术]
X. Zhang, N. Tai, Y. Wang et al., “EMTR-based fault location for DC line in VSC-MTDC system using high-frequency currents,” IET Generation, Transmission & Distribution, vol. 11, no. 10, pp. 2499-2507, Jul. 2017. [百度学术]
J. Sneath, A. D. Rajapakse, Y. Wang et al., “Fault detection and interruption in an earthed HVDC grid using ROCOV and hybrid DC breakers,” IEEE Transactions on Power Delivery, vol. 31, no. 3, pp. 973-981, Jun. 2016. [百度学术]
P. T. Lewis, B. M. Grainger, H. A. A. Hassang et al., “Fault section identification protection algorithm for modular multilevel converter based high voltage DC with a hybrid transmission corridor,” IEEE Transactions on Industrial Electronics, vol. 63, no. 9, pp. 5652-5662, Sept. 2016. [百度学术]
S. Li, W. Chen, X. Yin et al., “Protection scheme for VSC-HVDC transmission lines based on transverse differential current,” IET Generation, Transmission & Distribution, vol. 11, no. 11, pp. 2805-2813, Sept. 2017. [百度学术]
S. Shao, A. J. Watson, J. C. Clare et al., “Robustness analysis and experimental validation of a fault detection and isolation method for the modular multilevel converter,” IEEE Transactions on Power Electronics, vol. 31, no. 5, pp. 3794-3805, May 2016. [百度学术]
J. Liu, N. Tai, and C. Fan, “Transient-voltage-based protection scheme for DC line faults in the multiterminal VSC-HVDC system,” IEEE Transactions on Power Delivery, vol. 32, no. 3, pp. 1483-1494, Jun. 2017. [百度学术]
B. Li, J. He, Y. Li et al., “A review of the protection for the multi-terminal VSC-HVDC grid,” Protection and Control of Modern Power Systems, vol. 4, no. 3, pp. 239-249, Nov. 2019. [百度学术]
W. Leterme, S. P. Azad, and D. V. Hertem, “A local backup protection algorithm for HVDC grids,” IEEE Transactions on Power Delivery, vol. 31, no. 4, pp. 1767-1775, Aug. 2016. [百度学术]
X. Pei, G. Tang, S. Zhang et al., “Analysis of transient characteristics of short-circuit current for bipolar VSC-based DC grid,” Journal of Global Energy Interconnection, vol. 1, no. 4, pp. 404-412, Jan. 2018. [百度学术]
C. Li, C. Zhao, J. Xu et al., “A pole-to-pole short circuit fault current calculation method for DC grids,” IEEE Transactions on Power Systems, vol. 32, no. 6, pp. 4943-4953, Nov. 2017. [百度学术]