Abstract
In this paper, a fast fault detection scheme for voltage source converter based high-voltage direct current (VSC-HVDC) transmission systems is proposed. Based on Bergeron model equations, the remote terminal voltage of an adopted transmission system is calculated in terms of the local measured current and voltage signals. Subsequently, the computed voltage of the remote terminal is compared with the corresponding actual measured-communicated value. Provided that the considered transmission system is functioning well, the difference between the computed and measured voltages is almost zero. However, a considerable virtual voltage arises for fault conditions. When the voltage difference exceeds a predetermined threshold, a fault condition can be detected. Although a reliable communication link is required, the delay for detecting the fault is not caused by the communication time. For evaluation purpose, a detailed simulation is developed using PSCAD/EMTDC with various fault locations, including the cases near the inside or outside of the protected transmission system. The results corroborate a fast detection scheme depending on a moderate sampling/processing frequency level. A high security level is verified even with the worst external faults, or with the misaligned measured samples at the terminals. This corroborates the suitability of the proposed scheme for protecting multi-terminal HVDC systems.
HIGH-VOLTAGE direct current (HVDC) transmission systems are considered to be a promising scheme for connecting unsynchronized power systems or transmitting bulk power over long distances [
Regarding protection issues, VSC- and CSC-based schemes are different. Unlike most VSC types, CSC units can control the current into the DC side under DC fault conditions. Hence, DC fault cases with the VSC schemes should be detected quickly [
Different schemes have been proposed to provide fault detection with the capability of localizing faulty lines in multi-terminal DC systems [
To realize a selective fault detection approach, some schemes have been proposed depending on the differential protection concept based on communication channels between line terminals [
Other methods require high sampling frequencies, such as those depending on wavelet analysis [
The proposed scheme is based on the Bergeron model of the transmission system. This model has been utilized successfully in different applications for protection, particularly with HVDC systems [
Another current differential protection principle has been presented in [
This paper presents a fast detection approach for DC faults in VSC-HVDC transmission systems. It has been validated that there is no requirement for high sampling or processing frequency, where 10 kHz is adopted. Moreover, the proposed approach is the unit type, which does not operate for external faults even if it is immediately beyond the line terminals. Consequently, the proposed approach can be applied to multi-terminal systems with the capability of discriminating the faulty line only. Moreover, the proposed approach is suitable for systems with or without boundary inductors. Although it is based on a communication system, the data transfer time does not represent a delay for detecting the fault. This is primarily because the proposed approach is designed such that the data transfer time does not represent a delay, particularly with underground cable systems.
The proposed approach has been derived considering the representation of the transmission system with the Bergeron line model. The voltage of one terminal of the transmission system is calculated as a function of the monitored current and voltage signals at the other terminal. The calculated voltage is equal to the measured value provided that the transmission system is functioning well. If a fault exists in the transmission system, the calculated voltage would be virtual, which differs from the actual measured value. This is because the calculations are based on a well-functioning line equivalent circuit. Based on this criterion, the proposed fault detection approach is designed.
For the selected line or cable segment, the two terminals are designated by J and K. Taking terminal K as an example, the voltage difference would be:
(1) |
where is the voltage difference of terminal K; is the calculated voltage of terminal K obtained through the Bergeron model equation as a function of the monitored signals at terminal J; and is the measured voltage of terminal K, which represents the actual value. Furthermore, implies that the line or the cable is functioning well. With the occurrence of fault, would be a certain value depending on the fault condition.
Both terminals of the transmission system are considered with two voltage differences, one for each terminal, and . The proposed fault detection approach depends on the monitoring of both values to verify the condition of the transmission system.
The Bergeron model for calculating the voltage of terminal K in terms of the voltage and current at terminal J is given as:
(2) |
where Zc is the characteristic impedance of the transmission line or cable; r is the resistance per unit length; l is the length of the transmission line or cable; is the traveling duration for the traveling wave to propagate along the entire length; VJ is the measured voltage at terminal J; and iJK is the measured current at terminal J flowing toward the other end.
Considering the other terminal (terminal J), (3) is used to calculate the voltage of terminal J in terms of the measured signals at terminal K.
(3) |
As mentioned previously, the Bergeron model represents the core of many algorithms developed for transmission systems. The Bergeron model is based on the traveling wave equivalent circuit. The transmission system is represented by two sections of ideal circuits. The losses are considered by including the resistance as a lumped parameter element with four parts, as shown in

Fig. 1 Equivalent circuit of Bergeron model.
It is noteworthy that all the calculations herein are executed by employing the aerial mode parameters of the transmission system (1-mode). The aerial mode topology has been utilized as it provides a decoupled circuit without the mutual coupling effect between positive and negative poles [
(4) |
where Vp and Vn are the positive voltage and negative voltage, respectively; S is the transformation matrix for calculating the modal components; and V1 and V0 are the 1-mode and 0-mode voltage components, respectively. It is the same equation for calculating the modal currents. All processing for calculating the voltage difference value are performed based on the 1-mode components, which are more stable than the 0-mode components [
The paper focuses on the strategy of the proposed approach considering one terminal of the transmission system. For terminal K, its voltage can be calculated according to (2). Subsequently, the required voltage and current samples monitored at terminal J are as follows:
1) and represent the latest monitored samples at the processing instant t.
2) , , , and represent the previously monitored samples before the moment of processing, i.e., at instants and , respectively.
Owing to the need for the previously monitored samples, storage data windows have been assigned to save the captured voltage and current samples at terminal J with a window size of .

Fig. 2 Calculation process of VK. (a) Storage data windows for voltage and current signals at terminal J. (b) Corresponding time instants for the employed samples of VJ and iJK and the calculated sample of VK.
At each time step, the new monitored sample is assigned in the most recent location in the window, and the previously stored samples are shifted back by one sample. Through the calculation process of the voltage of terminal K, the preceding samples of VJ and iJK at instants and can be fetched from these data windows.
After obtaining the calculated voltage, its value was compared with the actual measured value. Therefore, the voltage difference is determined. The processing or relaying unit used to calculate is located near terminal J. The calculated voltage sample is obtained as a function of the local measured signals and . The measured voltage sample is transmitted via the communication channel because it is monitored at the other remote end, which is shown in

Fig. 3 Proposed approach. (a) Calculation of voltage difference . (b) Required relaying units at terminals J and K for calculating and , respectively.
Although both and correspond to a previous instant, i.e., , the later is obtained in terms of the voltage and current samples at instant t, i.e., and . This implies that any recent disturbance at instant t would be reflected on the calculated voltage sample , which consequently affects the voltage difference value . Although the voltage difference is calculated in terms of the samples that correspond to the previous instant , a delay would occur when monitoring the system condition .
It is noteworthy that GPS receivers are recommended so as to capture the signals at the line terminals simultaneously. Hence, the time stamping of the monitored samples at the terminals would be with reference to a common clock [
The aforementioned discussion is with respect to the voltage difference . The other voltage difference value can be calculated similarly using a devoted processing unit located at terminal K, which is shown in
To verify whether the communication system would result in delay, the relative speed between the communication system and the traveling waves has been analyzed. Both the underground cables and overhead lines are tested. Regarding the recommended communication system, the fiber optic based systems are the most typically used, which require approximately 0.5 ms per 100 km length for data transfer [

Fig. 4 Employed configurations of transmission systems. (a) Overhead line. (b) Underground cable.
Meanwhile, if an overhead line is utilized, a slight delay will occur, which is estimated by the difference between the communication time and the traveling time. For example, it would be 0.16 ms per 100 km ( ms) according to the overhead line. This time represents a waiting duration until the required samples to be processed are received, which is acceptable for detecting faults in HVDC systems.
To validate the proposed scheme, a bipolar VSC-HVDC system (±400 kV) is simulated using the PSCAD/EMTDC program shown in

Fig. 5 Two-terminal HVDC system.
The system details are given in
To validate the proposed approach, a severe positive-pole-to-ground fault condition is applied at the middle of the transmission system at F1, as depicted in

Fig. 6 Transient response of virtual voltage differences with pole-to-ground fault at F1. (a) Voltage and voltage difference of 1-mode components at terminal J. (b) Voltage and voltage difference of 1-mode components at terminal K. (c) Responses to both positive- and negative-pole-to-ground faults.
The response is also performed considering the negative-pole fault condition at the same point (50 km away from terminal J). As shown in
To investigate the selectivity of the proposed approach, the voltage difference values are monitored with the faults, which are extremely close to the line ends, i.e., near the inside and outside of the line zone. As shown in

Fig. 7 Voltage difference response considering faults near terminals. (a) Voltage difference of terminal K with internal pole-to-ground fault at F2. (b) Voltage difference of terminal J with internal pole-to-ground fault at F2. (c) Voltage difference of terminal K with external pole-to-ground fault at F5. (d) Voltage difference of terminal J with external pole-to-ground fault at F5.
The voltage differences are verified for external severe faults near the outside of the line zone (i.e., F4 or F5).
From the obtained results shown in

Fig. 8 Voltage difference maximum value versus fault location with pole-to-pole and pole-to-ground faults. (a) versus fault location. (b) versus fault location.
Moreover, the voltage difference depends on the fault type. Its value is higher in the pole-to-pole fault condition compared with that in the pole-to-ground fault condition. This is because the degree of divergence associated with the calculated voltage signal is higher in the pole-to-pole fault condition.
The proposed approach is profiled precisely such that the faults within the adopted line or cable could be detected successfully, and that the maloperations with external faults near the outside of the line zone are avoided. The pickup setting of the proposed fault detection scheme is designed based on a threshold level for the voltage difference value.
The pickup setting is regulated to attain a good security level. If a low level of the pickup setting is selected, the fault detection scheme may over-reach the protected line zone. The pickup threshold is regulated such that only approximately 80% of the transmission line length is covered. This accounts for inaccuracies owing to the variations of parameters or unsynchronized signals at the terminals. The remaining 20% of the line or cable is protected through the other voltage difference value at the other terminal.

Fig. 9 Pickup settings for voltage differences and corresponding protected areas. (a) Pickup settings of and corresponding protected area. (b) Pickup settings of and corresponding protected area. (c) Jurisdiction areas of both relaying units.
To determine the pickup setting level, the following criterion is proposed:
(5) |
This criterion provides an approximate value for the voltage difference with the fault at approximately 80% of the transmission system length. As the profile of the voltage difference depends on the fault type, the pickup setting is adaptive.
Two pickup settings are proposed in (5). and are the pickup thresholds for the pole-to-pole and pole-to-ground faults, respectively. It is not appropriate to depend on one setting to guarantee a secure performance. Utilizing only may result in an unprotected area for pole-to-ground faults. Meanwhile, depending on the setting of pole-to-ground faults only may result in the length of the protected transmission system with pole-to-pole faults that are over-reached, thereby causing maloperations with external faults.
As two different pickup settings exist, a preliminary step should be performed to select the appropriate pickup setting. The voltage difference value is to be compared with the pickup setting if the fault is recognized as a pole-to-ground fault. The other pickup setting is considered for pole-to-pole fault cases. The pole-to-ground faults are discriminated by the imbalance between the positive and negative poles. Hence, the current or voltage imbalances are verified as a preparatory step before verifying the voltage difference value. As shown in

Fig. 10 Verification of signal imbalance for both selecting appropriate pickup setting and identifying faulty pole. (a) Selection of appropriate pickup setting before verifying voltage difference value. (b) Identification of faulty pole after confirming a pole-to-ground fault type.
It can be concluded that will be compared with if an imbalance occurs between the positive and negative voltages/currents. Meanwhile, verification with reference to must be performed if the imbalance conditions are not satisfied. It is noteworthy that the proposed approach should be tested if the power delivered through the poles are not balanced prior to the fault. This aspect will be discussed in the following section.
After confirming that the fault is a pole-to-ground fault, the faulty pole can be determined as either a positive-pole or negative-pole fault. This is performed by verifying the relative values of the positive and negative currents. If the ratio () is higher than two, the fault condition is recognized as a positive-pole-to-ground case, where the positive-pole current is significantly higher than the negative-pole current under this condition. Meanwhile, this ratio is reduced if the fault is a negative-pole fault, where the negative current is increased. This is clarified in
In conclusion, the imbalance between the positive and negative signals is verified in two separate steps. First, the currents or voltages are verified according to the conditions in
The proposed approach should be tested if an imbalance operation occurs before the fault. This can be performed by controlling the delivered power through poles prior to the fault. Three test cases have been examined: positive-pole-to-ground, negative-pole-to-ground, and pole-to-pole faults. In the worst condition, these tests are performed with an extremely high imbalance before the fault occurrence. The ratio of the positive-pole current to the negative-pole current is approximately two prior to the fault.
The tested fault cases are at the middle of the transmission system length, whereas the fault instant is at 0.6 s. The results obtained for the three cases are presented in Figs.

Fig. 11 Response under positive-pole-to-ground fault with a significant imbalance prior to fault. (a) Signal imbalance and voltage difference value. (b) Logical values of conditions.

Fig. 12 Response under negative-pole-to-ground fault with a significant imbalance prior to fault. (a) Signal imbalance and voltage difference value. (b) Logical values of conditions.
1) As shown in
2) Once the fault occurrs, the imbalance between the positive and negative currents/voltages becomes highly significant. Hence, the appropriate pickup setting can be accurately selected, i.e., .
3) As shown in
4) After confirming the fault by verifying the voltage difference value (), the faulty pole is identified by verifying the ratio of the pole currents (). Currents are preferred over voltages owing to their faster response.
5) The obtained results have proved that no problems are encountered by adopting the current imbalance in verifications, even when an imbalance operation occurs prior to the fault.
The negative-pole-to-ground fault condition has been tested as well. The results obtained are presented in
In addition, a test case for the pole-to-pole fault has been performed with the same imbalance condition prior to the fault. The obtained results are presented in

Fig. 13 Response to pole-to-pole fault with a significant imbalance prior to fault. (a) Signal imbalance and voltage difference value. (b) Logical values of conditions.
Finally, it can be concluded that the imbalance operation does not affect the performance of the proposed approach. This is because the voltage difference value maintains at zero in well-functioning conditions. In addition, with the adopted processing and conditions in
Using the simulated system, the fault detection time can be recorded with the tested pole-to-ground and pole-to-pole fault cases at various locations. The results obtained for the fault detection time are illustrated in
× means that the fault detection scheme does not operate.
For each fault case, the detection time is measured with reference to the arrival moment of the fault-generated waves at the terminals. The table presents the time consumed by the generated traveling wave from the fault point to reach the terminal along with the detection time. These results are clarified as follows:
1) The proposed fault detection approach does not maloperate with severe external faults, even if they are located extremely close to the outside of the cable ends.
2) The fault detection process is rapid, as it only takes a sub-millisecond after the arrival of the incident-traveling wave from the fault point at the transmission system terminals. The fault detection times remain at the same level for faults in different locations because the detection time is measured with reference to the arrival moment of the fault-generated waves at the terminals. Changing the fault location affects primarily the wave arrival delay time. However, the detection time does not change significantly.
3) Based on , the faults in Zone I can be detected. Similarly, faults in Zone II can be discriminated successfully based on .
4) Those faults located at one of the terminals of the adopted cable at either 0 or 100 km are detected within a short detection time of 0.1 ms, equal to the sampling time step employed. Hence, by utilizing a shorter time step with a higher sampling frequency, the detection of such faults could be facilitated within a time duration of less than 0.1 ms.
The delay times of the traveling waves are determined based on detecting the first change in the currents or voltages by referring to the instance at which the fault occurs. To determine accurate values for these times, the sampling frequency at which the signals are monitored is increased with a reduced time step of 20 .
The results obtained imply that the proposed fault detection approach can be considered as a unit protection approach. After detecting the fault, the faulty zone should be isolated. Hence, a direct current circuit breaker (DCCB) must be set at each terminal of the adopted transmission section. Various technologies are associated with the selected DCCB. Solid-state-based types provide a fast clearing process, but the high conduction loss is a limitation [
The triggering signals for these CBs would be provided by the relaying units at the line ends. As shown in

Fig. 14 Triggering strategy for DCCBs and behavior under remote fault condition. (a) Triggering strategy for DCCBs. (b) Performance under remote fault F3 with underground cable system to trigger CB at terminal J. (c) Performance under remote fault F3 with overhead line system to trigger CB at terminal J.
It is noted that for
If the fault is detected by only one relaying unit, as in the case of F3, the remote CB at terminal J will be triggered via the communication, as shown in
If the transmission system is an overhead line, as in
The applicability of the proposed protection system can be extended to multi-terminal systems, where each transmission element has its own separate zone. To investigate the security of the proposed detector, a three-terminal 200 kV symmetric-monopole system is simulated by the PSCAD program, as described in

Fig. 15 Proposed approach applied in a multi-terminal system. (a) Simulated three-terminal system. (b) Voltage differences for faulty and non-faulty lines.
The fault inception instant is at 0.6 s. The voltage differences considering both faulty and non-faulty lines are monitored, as shown in
This section investigates the response when synchronization errors are included within the signals measured at the terminals. This is investigated by considering the applied fault condition according to

Fig. 16 Effect of unsynchronized samples at terminals. (a) Voltage differences for faulty line with unsynchronized samples at terminals. (b) Voltage differences for non-faulty line with unsynchronized samples at terminals.
Meanwhile, the response of is also monitored to verify the security of the proposed approach if the samples are misaligned.
Boundary inductors are recommended to be used with VSC-HVDC systems to limit the increase rate of the current in fault cases. This is an important aspect, where the DCCB can be selected with reduced current breaking capability. The response of the proposed scheme is verified by considering the boundary inductors. The behavior is not affected, as the measurement devices are installed at the line side of the boundary inductors, as shown in
The same multi-terminal system shown in

Fig. 17 Effect of boundary inductors on proposed scheme. (a) Effect of boundary inductance value on voltage difference profile. (b) Response with boundary inductors in multi-terminal system under fault near a typical terminal.
The security of the proposed approach is tested and the abovementioned inductors are adopted. Considering the fault case shown in
The length of the employed transmission system in the previous analysis is 100 km. However, in future practical conditions, the transmission system may be slightly longer. Therefore, the proposed scheme is verified using a longer transmission system of 400 km. The voltage difference profile is investigated in different fault cases, including pole-to-pole and pole-to-ground cases at different locations (0, 100, 200, 300, and 400 km). The results obtained are presented in

Fig. 18 Voltage difference profile for 400 km transmission system. (a) versus fault location under pole-to-pole and pole-to-ground faults. (b) versus fault location under pole-to-pole and pole-to-ground faults.
A fast fault detection scheme is proposed herein for VSC-HVDC transmission systems by computing the virtual difference in the terminal voltages of a protected line. A communication system is required for transferring data between the line terminals. However, the proposed detector does not have an intended delay owing to the communication system. The proposed approach successfully detects the fault and identifies the faulty pole in pole-to-ground fault cases. The high immunity of the proposed approach to maloperations has been verified in different worst-case scenarios such as severe and extremely close external faults, misaligned samples at terminals, and significant imbalance operation prior to fault occurrence. Furthermore, it has been discovered that the proposed scheme can be utilized successfully in multi-terminal systems. The results reveal the reliability, versatility, and accurate fault detection capability of the proposed approach for VSC-HVDC transmission systems.
REFERENCES
J. Lin, “Integrating the first HVDC-based offshore wind power into PJM system–a real project case study,” IEEE Transactions on Industrial Applications, vol. 53, no. 3, pp. 1970-1978, May-Jun. 2016. [百度学术]
Y. Fu, C. Wang, W. Tian et al., “Integration of large-scale offshore wind energy via VSC-HVDC in day-ahead scheduling,” IEEE Transactions on Sustainable Energy, vol. 7, no. 2, pp. 535-545, Apr. 2016. [百度学术]
G. Tang, Z. He, and H. Pang, “R&D and application of voltage sourced converter based high voltage direct current engineering technology in China,” Journal of Modern Power Systems and Clean Energy, vol. 2, no. 1, pp. 1-15, Jan. 2014. [百度学术]
P. Rodriguez and K. Rouzbehi, “Multi-terminal DC grids: challenges and prospects,” Journal of Modern Power Systems and Clean Energy, vol. 5, no. 4, pp. 515-523, Jul. 2017. [百度学术]
N. Flourentzou, V. G. Agelidis, and G. D. Demetriades, “VSC-based HVDC power transmission systems: an overview,” IEEE Transactions on Power Electronics, vol. 24, no. 3, pp. 592-602, Mar. 2009. [百度学术]
R. Sellick and M. Akerberg, “Comparison of HVDC light (VSC) and HVDC classic (LCC) site aspects, for a 500MW 400kV HVDC transmission scheme,” in Proceedings of 10th IET International Conference on AC and DC Power Transmission (ACDC 2012), Birmingham, UK, Dec. 2012, pp 1-6. [百度学术]
F. Schettler, H. Huang, and N. Christl, “HVDC transmission systems using voltage sourced converters design and applications,” in Proceedings of IEEE PES Summer Meeting, Seattle, USA, Jul. 2000, pp. 715-720. [百度学术]
J. Rafferty, L. Xu, and J. Morrow, “Analysis of voltage source converter-based high-voltage direct current under DC line-to-earth fault,” IET Power Electronics, vol. 8, no. 3, pp. 428-438, Mar. 2015. [百度学术]
J. Yang, J. E. Fletcher, and J. O’Reilly, “Short-circuit and ground fault analyses and location in VSC-Based DC network cables,” IEEE Transactions on Industrial Electronics, vol. 59, no. 10, pp. 3827-3837, Oct. 2012. [百度学术]
M. Farhadi and O. A. Mohammed, “Protection of multi-terminal and distributed DC systems: design challenges and techniques,” Electric Power Systems Research, vol. 143, pp. 715-727, Feb. 2017. [百度学术]
S. Le Blond, R. Bertho Jr., D. V. Coury et al., “Design of protection schemes for multi-terminal HVDC systems,” Renewable and Sustainable Energy Reviews, vol. 56, pp. 965-974, Apr. 2016. [百度学术]
D. Jovcic, D. V. Hertem, K. Linden et al., “Feasibility of DC transmission networks,” in Proceedings of 2nd IEEE PES International Conference and Exhibition on Innovative Smart Grid Technologies (ISGT), Manchester, UK, Dec. 2011, pp. 1-8. [百度学术]
J. Sneath and A. D. Rajapakse, “Fault detection and interruption in an earthed HVDC grid using ROCOV and hybrid DC breakers,” IEEE Transactions on Power Delivery, vol. 31, no. 3, pp. 973-981, Jun. 2016. [百度学术]
R. Li, L. Xu, and L. Yao, “DC fault detection and location in meshed multiterminal HVDC systems based on DC reactor voltage change rate,” IEEE Transactions on Power Delivery, vol. 32, no. 3, pp. 1516-1526, Jun. 2017. [百度学术]
J. Descloux, P. Rault, S. Nguefeu et al., “HVDC meshed grid: control and protection of a multi-terminal HVDC system,” in Proceedings of CIGRE Conference, Paris, France, Aug. 2012, pp. 1-10. [百度学术]
A. E. B. Abu-Elanien, A. E. Elserougi, A. S. Abdel-Khalik et al., “A differential protection technique for multi-terminal HVDC,” Elsevier Electric Power Systems Research, vol. 130, pp. 78-88, Jan. 2016. [百度学术]
K. De Kerf, K. Srivastava, M. Reza et al., “Wavelet-based protection strategy for DC faults in multi-terminal VSC HVDC systems,” IET Generation, Transmission & Distribution, vol. 5, no. 4, pp. 496-503, May 2011. [百度学术]
L. Shang, G. Herold, J. Jaeger et al., “High-speed fault identification and protection for HVDC line using wavelet technique,” in Proceedings of IEEE PowerTech Conference, Porto, Portugal, Sept. 2001, pp. 1-5. [百度学术]
Y. M. Yeap and A. Ukil, “Wavelet based fault analysis in HVDC system,” in Proceedings of 40th Annual Conference of the IEEE Industrial Electronics Society (IECON), Dallas, USA, Nov. 2014, pp. 2472-2478. [百度学术]
J. Suonan, S. Gao, Z. Jiao et al., “A novel fault-location method for HVDC transmission lines,” IEEE Transactions on Power Delivery, vol. 25, no. 2, pp.1203-1209, Apr. 2010. [百度学术]
S. Gao, Q. Liu, and G. Song, “Current differential protection principle of HVDC transmission system,” IET Generation, Transmission & Distribution, vol. 11, no. 5, pp. 1286-1292, May 2017. [百度学术]
H. W. Dommel, “Digital computer solution of electromagnetic transients in single and multiphase networks,” IEEE Transactions on Power Apparatus and Systems, vol. 88, no. 4, pp. 388-399, Apr. 1969. [百度学术]
G. Song, J. Suonan, and Q. Xu, “Parallel transmission lines fault location algorithm based on differential component net,” IEEE Transactions on Power Delivery, vol. 20, no. 4, pp. 2396-2406, Nov. 2005. [百度学术]
A. Seuret, F. Michaut, J. P. Richard et al., “Networked control using GPS synchronization,” in Proceedings of American Control Conference, Minneapolis, USA, Jul. 2006, pp. 1-6. [百度学术]
J. Descloux, P. Rault, S. Nguefeu et al., “HVDC meshed grid: control and protection of a multi-terminal HVDC system,” in Proceedings of CIGRE Conference, Paris, France, Aug. 2012, pp. 1-10. [百度学术]
S. V. Achanta, R. Bradetich, and K. Fodero, “Speed and security considerations for protection channels,” in Proceedings of 69th Annual Conference for Protective Relay Engineers (CPRE), College Station, USA, Apr. 2016, pp. 1-9. [百度学术]
W. Xiang, Y. Hua, J. Wen et al.,“Research on fast solid state DC breaker based on a natural current zero-crossing point,” Journal of Modern Power Systems and Clean Energy, vol. 2, no. 1, pp. 30-38, Mar. 2014. [百度学术]
C. Meyer, S. Schröder, and R. W. D. Doncker, “Solid-state circuit breakers and current limiters for medium-voltage systems having distributed power systems,” IEEE Transactions on Power Electronics, vol. 19, no. 5, pp. 1333-1340, Oct. 2004. [百度学术]
M. Callavik, A. Blomberg, J. Häfner et al., “The hybrid HVDC breaker an innovation breakthrough enabling reliable HVDC grids,” ABB Grid Systems, Technical Report, Nov. 2012. [百度学术]
J.-M. Meyer and A. Rufer, “A DC hybrid circuit breaker with ultra-fast contact opening and integrated gate-commutated thyristors (IGCTs),” IEEE Transactions on Power Delivery, vol. 21, no. 2, pp. 646-651, May 2006. [百度学术]