Abstract
Islanding refers to a condition where distributed generators (DGs) inject power solely to the local load after electrical separation from power grid. Several islanding detection methods (IDMs) categorized into remote, active, and passive groups have been reported to detect this undesirable state. In active techniques, a disturbance is injected into the DG's controller to drift a local yardstick out of the permissible range. Although this disturbance leads to more effective detections even in well-balanced island, it raises the total harmonic distortion (THD) of the output current under the normal operation conditions. This paper analyzes the power quality aspect of the modified sliding mode controller as a new active IDM for grid-connected photovoltaic system (GCPVS) with a string inverter. Its performance is compared with the voltage positive feedback (VPF) method, a well-known active IDM. This evaluation is carried out for a 1 kWp GCPVS in MATLAB/Simulink platform by measuring the output current harmonics and THD as well as the efficiency under various penetration and disturbance levels. The output results demonstrate that since the proposed disturbance changes the amplitude of the output current, it does not generate harmonics/subharmonics. Thereby, it has a negligible adverse effect on power quality. It is finally concluded that the performance of the sliding mode-based IDM is reliable from the standpoints of islanding detection and power quality.
Keywords
Islanding detection method (IDM); power quality; sliding mode controller; total harmonic distortion (THD); voltage positive feedback (VPF).
THE penetration of renewable energy technologies increases substantially in distributed networks. In this regard, more than 80 GWp of the grid-connected photovoltaic systems (GCPVSs) have been installed worldwide in 2017, which represents a 30% growth compared to that in 2015 [
Islanding is a condition in which a part of the utility including distributed generator (DG) is separated from the network, while it continues to inject power solely into the local load. This state has to be identified effectively to assure the safety of repair crew and prevent the failure of sensitive equipment [
As shown in

Fig. 1 Interconnection of DG and local load to electric network.
The power quality analysis of DG output power owning to the applied active IDMs has been carried out in [
It can be concluded from the literature that the rate of THDI ascent depends on the level of GCPVS output power. The current control loop is also known as the primary source of harmonics because of the disturbance injection in the frequency or angle of output current.
This paper investigates the effect of modified sliding mode controller as a new VPF-based active IDM on the output power quality of GCPVS. Since the disturbance is involved into the inverter’s voltage control loop, the proposed algorithm will only change the output current amplitude rather than the frequency or angle. Consequently, its effect on the power quality of the distribution network is hardly noticeable as the same of the conventional VPF.
The rest of the paper is organized as follows. The modified sliding mode controller is introduced in Section II. In Section III, the sample of 1 kWp GCPVS case study in MATLAB/Simulink platform, including PV array and single-phase string inverter with bipolar pulse width modulation (PWM) is elaborated. Section III also presents the evaluation of the modified sliding mode controller in a few islanding scenarios and a systematic approach to define the margins of the disturbance gain. The effects of the provided disturbance on harmonics, THDI, and efficiency as well as a comparative assessment with the classic VPF are presented in Section IV. The conclusion remarks are finally discussed in Section V.
VPF is an active IDM which tries to unstabilize PCC voltage after the occurrence of islanding. This aim is achieved through a VPF injection to the inverter’s d-axis reference current which tunes the active power output. When the PCC voltage rises after islanding, it increases the reference current, the active power output, and consequently the PCC voltage. This voltage keeps growing in magnitude until it exceeds the over-voltage relay setting (1.1 p.u.). In the case of PCC voltage drop, the output power and voltage are diminished until the under-voltage (UV) relay setting (0.88 p.u.) is exceeded [
The VPF concept is employed in the sliding mode controller to represent a new active IDM [
(1) |

Fig. 2 Sliding mode MPPT technique. (a) Characteristics locus of VPV and IPV . (b) Schematic diagram.
where b should be determined using the least square error method and some pairs of VMPP and IMPP in several irradiance levels; and ref is an adaptive parameter that determines MPP in any climate condition. This factor should be defined in the inverter’s voltage control loop using conventional MPP tracking (MPPT) techniques such as perturb and observe (P&O). In the sliding mode controller, the value of the switching surface parameter determines the boost converter operation condition. When , the converter switch is opened and inductor will be discharged. This increases the PV array voltage and reduces its current. On the contrary, the converter switch closes in state, the inductor will be charged, the PV current is increaded, and the voltage is decreased. Therefore, the operation point would be regulated in such a way that the GCPVS operates around , i.e., MPP [
In simple words, the basic idea of the proposed IDM is to insert a PCC voltage feedback in ref of the sliding mode controller as follows:
(2) |
where Kpf controls the disturbance size; and is the PCC voltage deviation. When the grid is lost, the active power mismatch leads to a VPCC variation and the applied feedback drifts ref away from its MPP setting. The output power is thereby reduced and will cause a voltage drop () regarding the following equation:
(3) |
where R is the resistive part of the local load at PCC modeled by IEEE Standard 929-2000 [

Fig. 3 Trajectory of PV array operation point in proposed method. (a) Normal operation between two irradiance levels. (b) Islanding condition.
Since the proposed disturbance is applied to the voltage control loop of inverter (MPPT) rather than the current controller, it disturbs the output current amplitude of a linear load, but not the frequency or angle. Hence, it does not generate harmonics or subharmonics, and is expected to have near-zero influence on the power quality of the distribution network.
This section contains the introduction of the case study system and justification of the modified sliding-mode controller under a few islanding scenarios. The selection criteria of the disturbance gain are detailed as well.
The schematic of the sample system with the application of the proposed method is shown in

Fig. 4 Schematic of case study system under evaluation.
The local load is modeled as an RLC circuit with around 50 Hz resonant frequency and 2.5 quality factor Qf to meet the islanding standard requirements (Table V) [
Moreover, the only setting of the proposed IDM is Kpf. Although the selection criteria of this parameter is described later, it is assumed to be 2.17 in the presented analysis.
It is worth mentioning that in Table IV, the input capacitance and inductance of the boost converter are denoted by Cin and Lin, while Cout and Rout represent the output capacitance and resistance, respectively. Furthermore, kI, kP, and kR are the integral, proportional, and resonant gains of the inverter’s current controller, respectively. They are implemented in the αβ reference frame. The filter, grid, and load settings are also denoted by f, g, and l, respectively. All these parameters are shown in
The modified sliding mode controller should lessen active power output, and consequently PCC voltage to reach the minimum standard setting (0.88 p.u.) for islanding classification. The islanding has been simulated for the case study system through opening the circuit breaker aside PCC in
The results including active power and PCC voltage have been illustrated in

Fig. 5 Performance of proposed IDM in the worst case study. (a) Active power. (b) PCC voltage.
After islanding, the PCC voltage of the isolated region can be changed from its pre-islanding setting (Vpr) to a new level after separation (Vpo) as in (4):
(4) |
The post-islanding voltage depends on the active power mismatch between PDG and PL or the level of DG active power variation through activating the embedded disturbance named as active power disturbance () [

Fig. 6 PCC voltage under several active power mismatches.
The selection criteria of Kpf as the proposed disturbance gain is mandatory. The lower and upper bounds of this setting should be determined to assure the system stability in grid-connected mode and zero NDZ, respectively.
Disturbance gain should be limited to an upper edge to avoid unacceptable active power output reduction of the inverter under probable PCC voltage fluctuations that occur several times a day in the power system. A small signal analysis should be done to this end. By employing the modified sliding mode controller and neglecting the DC losses, the reference active power of the inverter in the voltage control loop Pref can be expressed as follows:
(5) |
The expressions of small signal analysis of (2) and (5) can be deduced as follows:
(6) |
(7) |
where is used to represent the small variation of current, voltage, and power around their steady-state sets. Since the variation of refP&O is near zero, the corresponding expression has been neglected in (7). When VPCC decreases, the right-hand side term of (7) is positive and the GCPVS moves toward the short-circuit point. Therefore, equals to the subtraction of the MPP current from ISC. Since in both steady and transient states, the switching surface signal is zero, i.e., and , the final equation can be extracted:
(8) |
This expression is deduced by supposing that is proportionally smaller in comparison with other terms.
The mentioned analysis cannot be applied in the case of since would be negative and the GCPVS moves toward the open-circuit point. The final levels of IPV and would be unknown in this situation, and ultimately, the first term in (8) could not be defined.
This expression, however, can be employed to determine the upper bound for a maximum acceptable PDG reduction and a given step voltage size for For instance, by assuming 0.03 p.u. and 10% as the PCC voltage variation and maximum permissible fluctuations for PDG, respectively, the computational results (only for case) as well as the simulation outcomes are provided in Table VI. Based on these findings, Kpf should be restricted to 3.04 to assure at most 10% PDG drop with 3% VPCC change.
The lower margin of Kpf can be defined respecting the successful detection in worst islanding scenario, i.e., zero active power mismatch or disturbance. As mentioned above, while the relative active power disturbance locates inside the range of [29.13%, 17.35%], Vpo would not leave the standard range. Accordingly, if the proposed IDM diminishes PDG by 29.13 in zero active power mismatch, the PCC voltage would be successfully drifted to the lower margin (0.88 p.u.), and the islanding is identified.
(9) |
This equation can be further simplified by replacing VPV using (2) and neglecting IPV against refP&O:
(10) |
The following polynomial term can be finally derived to determine the upper limit of Kpf with a given PCC voltage variation:
(11) |
The right-hand side term can be negative or positive regarding the level of (). However, since the signs of the first and second terms are different, this equation has at least one positive solution. For instance, in order to assure islanding classification of the case study system with zero NDZ with p.u. (460 mV) and , Kpf should be at least 1.53 while voltage samples are measured in p.u.
Therefore, the optimized Kpf range for the case study GCPVS is [1.53, 3.04]. This range is defined self-standing regardless of the DG, inverter, and grid characteristics.
The same criteria have been considered for the definition of the VPF disturbance size and limited to the range of [
The effect of VPF and the proposed modified sliding-mode controller on power quality is assessed in the next section for the prototype system. In the following simulations, the disturbance gain is selected to be 20 and 2.17 for VPF and modified sliding mode controller. These selections guarantee zero NDZ and stable performance of the studied GCPVS in normal operation conditions.
The performance and efficiency of the sliding-mode-based IDM in the standpoints of current harmonics THDI are studied. The efficiency has not been placed in the power quality factors in scientific sources [
The presence of harmonics in the electrical system deviates voltage or current from its original sinusoidal waveforms. This deviation can be measured by THD, defined as the ratio of the root-mean-square (RMS) voltage or current of the harmonics to the fundamental component. Based on IEEE Standard 1547-2008 and IEC Standard 61727-2002, THDI should be limited to 5%. Furthermore, harmonic components should be restricted to the values listed in Table II [
The analysis is initially performed at various active power production levels. The results, including THDI for classic VPF and modified sliding-mode IDM are presented in

Fig. 7 Effect of VPF and proposed schemes on THDI with different percentages of nominal power.
In addition, the harmonic spectra (for ) in 25% of STC output power are illustrated in

Fig. 8 Effect of classic VPF and proposed IDM on power quality (harmonic spectra).
The disturbance size and amount of generated power are critical variables in power quality analysis of the active IDMs. In this regard, the average THDI at a few disturbance and generation levels has been determined and depicted in

Fig. 9 Average THDI for different disturbance sizes. (a) Modified sliding mode. (b) Classic VPF.
The commercial and power plant GCPVSs can be formed by string inverters, where multi-inverters are connected to the same PCC. The effect of multi-identical GCPVSs connection on the THDI has been assessed in this part. Table VII shows the average THDI of multi-DGs connection in 25% of nominal power. The outcomes imply on the acceptable power quality of the presented algorithm with multi-GCPVSs.
The average MPPT efficiency, i.e., the ratio of DC link power to the PV array power as well as the inverter efficiency, i.e., the ratio of AC output active power to the PV array power, for the sample GCPVS equipped with the proposed algorithm at various irradiance levels have been measured. What can be inferred from the provided data in Table VIII is that the presented disturbance has little influence on the DG’s efficiency, since MPP can be accomplished at a small bound around ref as the same as other MPPT algorithms. Hence, besides effective islanding detection, a high efficiency is guaranteed in normal operational mode. In addition, since the disturbance of VPF algorithm has been employed in the current controller of the inverter, it does not change the MPPT operation and efficiency.
Table VIII
Effect of Suggested Disturbance on MPPT and Inverter Efficiencies
In this paper, the influence of the classic VPF and modified sliding-mode IDM on the GCPVS’s power quality and efficiency has been evaluated. The study has been done for a 1 kWp PV system with string inverter. The simulation results show that, while the THD of output current in the proposed IDM is smaller than the simple VPF, both methods render acceptable power quality in a wide range of system operation. This proper performance has been achieved due to the variation of the current magnitude rather than the angle or frequency. This magnitude variation is realized in VPF and the proposed method in the current and voltage control loops (MPPT), respectively. The simulations also confirm that the acceptable THDI and harmonics are guaranteed in multi-GCPVSs connection situation even at low power generation levels as the worst scenario.
Since the new technique tries to deviate the system from its MPP condition, the effect of embedded disturbance on the efficiency is also performed. In this regard, the simulations are carried out and a negligible reduction in MPPT and inverter efficiencies (less than 0.04%) has been demonstrated in the proposed method. This occurs since MPP can be gained at a small bound around ref.
It has been finally concluded that the modified sliding-mode controller has the advantages of the conventional VPF scheme in islanding detection as well as a higher power quality in the production of energy.
REFERENCES
A. Jäger-Waldau, “PV status report 2017,” Publications Office of the European Union, Luxembourg, 2018. [百度学术]
M. Sandhu and T. Thakur, “Harmonic minimization in a modified cascaded multilevel inverter for islanded microgrid using two switching techniques,” International Journal of Grid and Distributed Computing, vol. 10, no. 12, pp. 11-20, Dec.2017. [百度学术]
S. Natarajan and R. S. R. Babu, “Reduction of total harmonic distortion in cascaded H-bridge inverter by pattern search technique,” International Journal of Electrical and Computer Engineering (IJECE), vol. 7, no. 6, p. 3292, Dec.2017. [百度学术]
A. Luo, Q. Xu, F. Ma et al., “Overview of power quality analysis and control technology for the smart grid,” Journal of Modern Power Systems and Clean Energy, vol. 4, no. 1, pp. 1-9, Jan.2016. [百度学术]
A. Khamis, H. Shareef, E. Bizkevelci et al., “A review of islanding detection techniques for renewable distributed generation systems,” Renewable and Sustainable EnergyReviews, vol. 28, pp. 483-493, Dec.2013. [百度学术]
W. Xu, G. Zhang, C. Li et al., “A power line signaling based technique for anti-islanding protection of distributed generators–part I: scheme and analysis,” IEEE Transactions on Power Delivery, vol. 22, no. 3, pp. 1758-1766, Jul.2007. [百度学术]
G. Bayrak, “A remote islanding detection and control strategy for photovoltaic-based distributed generation systems,” Energy Conversion and Management, vol. 96, pp. 228-241, May 2015. [百度学术]
G. Bayrak and E. Kabalci, “Implementation of a new remote islanding detection method for wind-solar hybrid power plants,” Renewable and Sustainable Energy Reviews, vol. 58, pp. 1-15, May 2016. [百度学术]
J. C. M. Vieira, D. S. Correa, W. Freitas et al., “Performance curves of voltage relays for islanding detection of distributed generators,” IEEE Transactions on Power Systems, vol. 20, no. 3, pp. 1660-1662, Aug.2005. [百度学术]
J. C. M. Vieira, W. Freitas, W. Xu et al., “Performance of frequency relays for distributed generation protection,” IEEE Transactions on Power Delivery, vol. 21, no. 3, pp. 1120-1127, Jul.2006. [百度学术]
Y. Shang, S. Shi, and X. Dong, “Islanding detection based on asymmetric tripping of feeder circuit breaker in ungrounded power distribution system,” Journal of Modern Power Systems and Clean Energy, vol. 3, no. 4, pp. 526-532, Oct.2015. [百度学术]
E. Kamyab and J. Sadeh, “Islanding detection method for photovoltaic distributed generation based on voltage drifting,” IET Generation, Transmission & Distribution, vol. 7, no. 6, pp. 584-592, Jun.2013. [百度学术]
M. Bakhshi, R. Noroozian, and G. B. Gharehpetian, “Islanding detection scheme based on adaptive identifier signal estimation method,” ISA Transactions, vol. 71, pp. 328-340, Nov.2017. [百度学术]
M. Mishra, M. Sahani, and P. K. Rout, “An islanding detection algorithm for distributed generation based on Hilbert-Huang transform and extreme learning machine,” Sustainable Energy, Grids and Networks, vol. 9, pp. 13-26, Mar.2017. [百度学术]
P. P. Das and S. Chattopadhyay, “A voltage-independent islanding detection method and low-voltage ride through of a two-stage PV inverter,” IEEE Transactions on Industry Applications, vol. 54, no. 3, pp. 2773-2783, May 2018. [百度学术]
L. A. C. Lopes and H. Sun, “Performance assessment of active frequency drifting islanding detection methods,” IEEE Transactions on Energy Conversion, vol. 21, no. 1, pp. 171-180, Mar.2006. [百度学术]
A. Yafaoui, B. Wu, and S. Kouro, “Improved active frequency drift anti-islanding detection method for grid connected photovoltaic systems,” IEEE Transactions on Power Electronics, vol. 27, no. 5, pp. 2367-2375, May 2012. [百度学术]
D. Reigosa, F. Briz, C. B. Charro et al., “Active islanding detection using high-frequency signal injection,” IEEE Transactions on Industry Applications, vol. 48, no. 5, pp. 1588-1597, Sep.2012. [百度学术]
T. Bei, “Accurate active islanding detection method for grid-tied inverters in distributed generation,” IET Renewable Power Generation, vol. 11, no. 13, pp. 1633-1639, Nov.2017. [百度学术]
H. F. Xiao, Z. Fang, D. Xu et al., “Anti-islanding protection relay for medium voltage feeder with multiple distributed generators,” IEEE Transactions on Industrial Electronics, vol. 64, no. 10, pp. 7874-7885, Oct.2017. [百度学术]
P. Du, Z. Ye, E. E. Aponte et al., “Positive-feedback-based active anti-islanding schemes for inverter-based distributed generators: basic principle, design guideline and performance analysis,” IEEE Transactions on Power Electronics, vol. 25, no. 12, pp. 2941-2948, Dec.2010. [百度学术]
S. K. Kim, J. H. Jeon, H. K. Choi et al., “Voltage shift acceleration control for anti-islanding of distributed generation inverters,” IEEE Transactions on Power Delivery, vol. 26, no. 4, pp. 2223-2234, Oct.2011. [百度学术]
F. J. Lin, J. H. Chiu, Y. R. Chang et al., “Active islanding detection method using d-axis disturbance signal injection with intelligent control,” IET Generation, Transmission & Distribution, vol. 7, no. 5, pp. 537-550, May 2013. [百度学术]
A. Samui and S. R. Samantaray, “An active islanding detection scheme for inverter-based DG with frequency dependent ZIP-exponential static load model,” International Journal of Electrical Power & Energy Systems, vol. 78, pp. 41-50, Jun.2016. [百度学术]
R. Bakhshi and J. Sadeh, “Voltage positive feedback based active method for islanding detection of photovoltaic system with string inverter using sliding mode controller,” Solar Energy, vol. 137, pp. 564-577, Nov.2016. [百度学术]
IEEE Standard for Interconnecting Distributed Resources with Electric Power Systems, IEEE Standard 1547-2008, 2008. [百度学术]
Characteristics of the Utility Interface for Photovoltaic (PV) Systems, IEC 61727, 2002. [百度学术]
G. A. Rampinelli, F. P. Gasparin, A. J. Bühler et al., “Assessment and mathematical modeling of energy quality parameters of grid connected photovoltaic inverters,” Renewable and Sustainable Energy Reviews, vol. 52, pp. 133-141, Dec.2015. [百度学术]
M. Hamzeh and H. Mokhtari, “Power quality comparison of active islanding detection methods in a single phase PV grid connected inverter,” In Proceedings of IEEE International Symposium on Industrial Electronics (ISIE 2009), Seoul Olympic Parktel, Korea, Jul.2009, pp. 1-6. [百度学术]
Y. Levron and D. Shmilovitz, “Maximum power point tracking employing sliding mode control,” IEEE Transactions on Circuits and Systems I: Regular Papers, vol. 60, no. 3, pp. 724-732, Mar.2013. [百度学术]
IEEE Recommended Practice for Utility Interface of Photovoltaic (PV) Systems, IEEE Standard 929-2000, 2000. [百度学术]
Q CELLS Official Website. (2018, Aug.). QPRO-G2 data. [Online]. Available: www.q-cells.com [百度学术]
K. Ding, X. Bian, H. Liu et al., “A MATLAB-Simulink-based PV module model and its application under conditions of nonuniform irradiance,” IEEE Transactions on Energy Conversion, vol. 27, no. 4, pp. 864-872, Dec.2012. [百度学术]
R. C. Dugan, M. F. McGranaghan, S. Santoso et al., Electrical Power Systems Quality, 3rd ed. New York: McGraw-Hill, 2003. [百度学术]