High-voltage Ride Through Strategy for DFIG Considering Converter Blocking of HVDC System  PDF

  • Changping Zhou
  • Zhen Wang
  • Ping Ju
  • Deqiang Gan
College of Electrical Engineering, Zhejiang University, Hangzhou 310027, China

Updated:2020-05-28

DOI:10.35833/MPCE.2019.000321

  • Full Text
  • Figs & Tabs
  • References
  • Authors
  • About
OUTLINE

Abstract

This paper presents a P-Q coordination based high-voltage ride through (HVRT) control strategy for doubly fed induction generators (DFIGs) based on a combined Q-V control and P-V de-loading control. The active/reactive power injection effect of DFIG on transient overvoltage is firstly analyzed and the reactive power capacity evaluation of DFIG considering its de-loading operation is then conducted. In the proposed strategy, the reactive power limit of DFIG can be flexibly extended during the transient process in coordination with its active power adjustment. As a result, the transient overvoltage caused by DC bipolar block can be effectively suppressed. Moreover, key outer loop parameters such as Q-V control coefficient and de-loading coefficient can be determined based on the voltage level of point of common coupling (PCC) and the available power capacity of DFIG. Finally, case studies based on MATLAB/Simulink simulation are used to verify the effectiveness of the proposed control strategy.

I. Introduction

THE past ten years have witnessed the rapid development of wind power for the purpose of solving the worldwide traditional energy and environmental crises [

1]. Due to the inherent uncertainty and volatility of wind power resources, the necessary power electronic interfaces for integrating wind turbine generators (WTGs) have posed big challenges to power system operation and control such as additional reserve requirement and inertial reduction in weak connection [2].

In Northwestern China, many large-scale wind farms are located far away from the receiving-end grids, and thus forming a weak-grid integration [

3]. For long-distance transmission of wind power in China, high-voltage direct current (HVDC) transmission technology is widely used for grid connection. Since each HVDC converter can consume a large amount of reactive power (about 40%-60% of the transferred active power), additional reactive power compensators (RPCs) such as a group of capacitor banks are needed to provide enough reactive power required for the commutation. When any DC bipolar block occurs, the surplus reactive power due to delayed compensator removing, will cause transient overvoltage surge [4]. In this case, the WTG overvoltage protection will evoke further WTG shedding, and even system instability risk [5]. In [6], an overvoltage phenomenon is observed in offshore wind farms following the blocking of the connected HVDC converter. The mechanism of transient overvoltage caused by DC blocking and its influence factors are analyzed in [7] and further a short circuit ratio (SCR) based index is proposed to measure the transient overvoltage level.

Fortunately, many efforts have been devoted to relieve the above transient overvoltage problem on wind farm side, which can be approximately classified into three categories. The first one can be attributed into a type of external RPC control methods, in which additional RPCs or their combination on the stator side are equipped and RPC control schemes are designed accordingly, e.g., a combination scheme of static synchronous compensator and dynamic voltage restorer is proposed to achieve fault ride through of DFIG in [

8], [9]; a superconducting fault current limiter and a transient voltage controller are jointly used to improve the system transient voltage stability in [10], [11]. The second one is a type of rotor-side converter (RSC) supplementary circuit control methods, where protection circuits are added in the rotor or DC circuit to attenuate the rotor overcurrent or DC overvoltage, e.g., a series dynamic braking resistor based crowbar in rotor circuit is proposed to limit current surge in [12]; a DC series chopper circuit is proposed to maintain a constant DC voltage in [13]; a DC series storage protection circuit is proposed to store excess energy during voltage surge in [14]. The third one is a type of RSC/grid-side converter (GSC) control methods, e.g., a RSC demagnetizing current controller is proposed to suppress inner voltage saturation in [15], [16]; a GSC high-voltage ride through (HVRT) control strategy with adaptive adjustment of DC-link voltage reference is proposed in [17]; an automatic voltage control at point of common coupling (PCC) based on optimized RSC reactive current reference to maximize the reactive power support capability of DFIG is applied in [18], [19].

Taking into account active power regulation, the reactive power capacity of DFIG has not been fully explored in above solutions. In this paper, the effect of the active/reactive power injection of WTG on overvoltage is firstly studied and the reactive power limit of DFIG considering its de-loading operation is analyzed subsequently. Then, a P-Q coordination method is proposed for emergency reactive power control to suppress transient overvoltage, in which a Q-V control logic is developed for reactive power adjustment and a P-V de-loading control logic is presented for active power adjustment accordingly. As a result, the reactive power supporting potential can be enlarged flexibly. The main contributions of this paper are summarized as follows.

1) The reactive power operation region of DFIG considering its active power de-loading control is elaborately depicted.

2) A P-Q coordination based HVRT strategy is proposed to fulfill transient overvoltage suppression, in which the Q-V control is coordinated with the P-V de-loading control to achieve the maximum reactive power capacity.

The rest of this paper is organized as follows. Section II analyzes the sending-end transient overvoltage and the effect of the active/reactive power injection of DFIG on transient overvoltage as well as the reactive power limit evaluation of DFIG. Section III introduces the proposed P-Q coordination based HVRT control strategy and the determination of key parameters. Section IV provides the case studies. Finally, conclusions are drawn in Section V.

II. Transient Overvoltage Analysis

A. System Description

The system integrated with DFIG-based wind farm in Fig. 1 represents a typical case of bulk wind power transmission from generation centers to load centers by means of HVDC transmission, where PWM stands for pulse width modulation. An equivalent model consisting of the equivalent reactance Xe and voltage source V˙e is used to represent the sending-end alternating current (AC) grid. For simplicity, a single DFIG-based wind turbine is used to represent the aggregate behavior of the whole wind farm. The traditional double loop control structure is applied for DFIG converter control. Originally under normal operation condition, the conventional maximum power point tracking (MPPT) control is used for the RSC outer loop and the constant Q-V control is used for the GSC outer loop to maintain the DC-link voltage. The outer loop will generate the reference signals for the inner current loop independently. The inner current control is carried out in rotational framework (d-q) with stator flux orientation with the help of the phase-locked-loop (PLL). Basic proportional-integral (PI) controller is adopted in those inner control loops [

20], [21]. Moreover, a group of static capacitor and filter is installed at the rectifier station to compensate for the reactive power consumption.

Fig. 1 Illustration of a sending-end AC system and HVRT control.

Under the overvoltage operation condition with the DC bipolar blocking described below, the following outer loops are designed and applied: ① two Q-V independent control loops are designed for the RSC power control and the GSC Q-V control, respectively [

22], [23]; ② a P-V de-loading loop is designed to generate the power reference for active power control. The details will be elaborated in the next section.

B. Effect of Active/Reactive Power Injection of WTG

When a transient overvoltage surge occurs at the sending-end AC system in Fig. 1, the terminal voltage at PCC Vp satisfies the following relationship:

aVp4+bVp2+c=0 (1)

where a=(1-GcXe)2, Gc is the admittance of HVDC capacitor banks; b=-1-2(1-GcXe)QDFIGXe, QDFIG is the total reactive power of DFIG; and c=(PDFIG2+QDFIG2)Xe2, PDFIG is the total active power of DFIG. The derivation of (1) can be found in Appendix A.

Accordingly, the sensitivity of Vp with respect to PDFIG and QDFIG can be formulated from (1) as:

VpPDFIG=-1VpPDFIGXe2b2-4ac (2)
VpQDFIG=(1-GcXe)Xe(1+b2-4ac)2aVpb2-4ac (3)

It is obvious that from (2) Vp/PDFIG<0 when PDFIG>0. If the sending-end AC system has SCR greater than 0.6, the following conclusions can be drawn from Appendix A:

1) Vp/QDFIG>0. In other words, when overvoltage at PCC occurs, the absorbing reactive power of wind farm (in inductive operation) can help suppress the transient overvoltage.

2) |Vp/QDFIG|>|Vp/PDFIG|, which means adjusting the inductive power absorption of DFIG has the better overvoltage suppression effect than adjusting the active power.

C. Inductive Reactive Power Limit

1) Reactive Power Evaluation

The inductive reactive power of wind farm comes from two resources: DFIG stator under RSC control and GSC itself. The stator reactive power limit is mainly determined by: ① the maximum rotor current constraint in (4) [

24]; ② the generator capacity constraint in (5) [25], [26]. The details can be found in Appendix B.

Ps2+Qs+3Vs22Xl23Xm2XlVsIrmax2 (4)
Ps2+Qs2Sn2 (5)

where Ps and Qs are the active power and reactive power from DFIG stator, respectively; Vs is the DFIG stator voltage; Xl=Xls+Xm is the stator inductance, Xls and Xm are the DFIG stator leakage and magnetizing reactance, respectively; Irmax is the maximum current limit of rotor; and Sn is the apparent power capacity of DFIG.

Therefore, the inductive reactive power limit of stator Qsmax can be determined by the less value between the reactive power corresponding to the maximum rotor current limit Qs1max and the maximum available reactive power Qs2max:

Qs1max=1.5Vs2/Xl+(1.5XmVsIrmax/Xl)2-Ps2Qs2max=Sn2-Ps2Qsmax=minQs1max,Qs2max (6)

An illustration of the relationship between Qsmax and its active power Ps is given in Fig. 2(a). It is clear that when Ps is less than P0, Qsmax=Qs1max; otherwise, Qsmax=Qs2max.

Fig. 2 Diagram of reactive power operation region of DFIG stator. (a) Reactive power limit curve of stator as its active power changes. (b) Qsmax(Ps,Vs). (c) Qsmax(v,Kde).

The characteristic diagram of the stator inductive reactive power operation region with respect to Ps and Vs at the rated wind speed is plotted in Fig. 2(b) and it can be observed that the rise of stator voltage and/or the decrease of DFIG active power can increase its reactive power limit.

On the other hand, the reactive power limit of GSC is determined by its apparent power capacity:

Qgmax=Sc2-(sPs)2 (7)

where Sc is GSC apparent power capacity; and s is the speed slip.

In general, GSC is controlled to maintain the DC voltage and its active power output sPs can be neglected. As a result, Qgmax can be approximated to be Sc [

18], [27] and the total inductive reactive power limit QGmax that a DFIG can absorb is determined by:

QGmax=Qsmax+Qgmax (8)

2) Active Power De-loading

From (6), it is clear that the reactive power limit can be extended by the decrease of DFIG active power, i.e., DFIG de-loading operation. The principle of DFIG de-loading is given in Fig. 3, in which initially DFIG is at the operation point a of MPPT, and then it actively traces some de-loading curves defined in (9) to point b so that part of available wind energy can be stored in form of rotating kinetic energy [

28], [29]. In Fig. 3, the corresponding active power after de-loading is as follows.

Ps=Pde=(1-Kde)PMPPT0Kde<Kdemax (9)

Fig. 3 Illustration of DFIG de-loading operation.

where PMPPT and Pde are the DFIG active power in MPPT and de-loading modes, respectively; and Kde and Kdemax are the de-loading coefficient and its maximum value, respectively. Kdemax limits the minimum active power output of DFIG in de-loading operation to avoid the rotor overspeed. As far as DFIG is concerned, Kdemax is about 0.1-0.2 [

29], [30] and Kdemax=0.2 is set in this paper.

Further, the inductive reactive power operation region of DFIG with different wind speeds v and de-loading coefficients is plotted in Fig. 2(c). It can be observed that: ① normally the reactive power limit will be reduced with the increase of wind speed; ② the limit can be enlarged by active power de-loading control, especially in high wind speed range (10-12 m/s). Thus, the power limits of the stator and DFIG under de-loading QsDmax, QGDmax can respectively be updated from (6)-(9) accordingly.

III. A P-Q Coordination Based HVRT Control

Since any DFIG converter capacity is limited, the main idea to capture additional reactive power capacity is by means of reactive power control and active power de-loading control coordinately, which will be elaborated below.

A. P-Q Coordination

The P-Q coordination includes two main logics: ① stator and GSC reactive power absorption by RSC and GSC reactive power control; ② reactive power capacity enlargement by de-loading control. The main procedure of the P-Q coordination based HVRT control is illustrated in Fig. 4.

Fig. 4 Flow chart of P-Q coordination.

When the overvoltage condition is detected, firstly the reactive power limit is evaluated and the outer loop parameters are determined according to the rules explained below; secondly, the reactive power controls of RSC and GSC are executed to absorb the surplus reactive power; thirdly, the de-loading of DFIG will be executed and the resultant reactive power capacity will be enlarged. The whole procedure will continue until the PCC voltage is satisfied or it reaches the maximum de-loading.

1) Q-V Control Logic

For the two reactive control logics, a Q-V piecewise control rule is adopted and illustrated in Fig. 5(a).

|QDFIG|=0                                       VpVOVminK1(Vp-VOVmin)                VOVmin<VpVOV1QGmax+K2(Vp-VOV1)    VOV1<VpVOVmaxQGDmax                                 Vp>VOVmax (10)

Fig. 5 P-Q coordination HVRT control. (a) Q-V piecewise control curve. (b) P-V power control curve. (c) A snapshot of de-loading P-V trajectory.

where VOVmin and VOVmax are the minimum and maximum voltages to activate HVRT, respectively; VOV1 is the de-loading triggering voltage in the HVRT curve; and QDFIG<0 means that DFIG will absorb reactive power.

As recommended by the test procedure of wind turbine HVRT capability in China [

31], VOVmin = 1.1 p.u. and VOVmax = 1.3 p.u. are set in the paper. Initially, VOV1 = 1.15 p.u. and its effect on the transient overvoltage will be discussed in next section. As of Q-V piecewise control in Fig. 5(a), the whole process corresponds to two stages.

1) Stage 1: VOVmin<VpVOV1, the reactive power controls of RSC and GSC are activated and the stator and GSC will absorb reactive power proportional to their reactive power limits along line AB. This process continues until it reaches the reactive power limit of DFIG. The following reference reactive power setting is used:

|Qsref|=QsmaxQGmaxK1(Vp-VOVmin)    Qsref<0|Qgref|=QgmaxQGmaxK1(Vp-VOVmin)    Qgref<0 (11)

where Qsref and Qgref are the reference reactive power for DFIG stator and GSC, respectively.

2) Stage 2: VOV1<VpVOVmax, the reactive power limit of DFIG will be temporarily enlarged by active power de-loading control. This process continues until it reaches the maximum de-loading. The reference power is set as follows:

|Qsref|=Qsmax+K2(Vp-VOV1)Qsref<0|Qgref|=Qgmax      Qgref<0 (12)

2) Logic of P-V De-loading Control

For the logic of de-loading control in Fig. 5(b), where Pdemax is the maximum active power of DFIG in de-loading mode, a P-V piecewise control rule is used:

PDFIG=PMPPT                     VpVOV1Pde                         VOV1<VpVOVmax(1-Kdemax)PMPPT    Vp>VOVmax (13)

Normally, DFIG will operate at MPPT state when VpVOV1. Otherwise, the de-loading control will be activated and DFIG will trace the de-loading curve DE until it reaches the maximum limit.

The power outer loops corresponding to the above mentioned Q-V control and P-V de-loading control logics are illustrated in Fig. 6, in which the outer loop parameters are discussed below.

Fig. 6 Outer loops of HVRT control. (a) Q-V control outer loop of RSC. (b) Q-V control outer loop of GSC. (c) P-V de-loading outer loop.

B. Determination of Outer Loop Parameters

1) Q-V Control Coefficients K1 and K2

As the control coefficients represent slopes of Q-V piecewise curve in Fig. 5(a), they can be easily obtained as:

K1=QGmax/(VOV1-VOVmin)K2=(QGDmax-QGmax)/(VOVmax-VOV1) (14)

2) De-loading Coefficient Kde

The de-loading logic in the power outer loop is illustrated in Fig. 6(c). Once Qsref is given in (11) and (13), the reference active power of de-loading Psref can be determined by:

Psref=min{Psrmax,Psmax} (15)
Psrmax=(1.5XmVsIrmax/Xl)2-(Qsref-1.5Vs2/Xl)2 (16)
Psmax=Sn2-(Qsref)2 (17)

where Psrmax is the active power corresponding to the maximum rotor current limit; and Psmax is the maximum stator power limit.

Accordingly, the de-loading coefficient Kde is:

Kde=1-Pde/PMPPT (18)

An example of the de-loading P-V trajectory Psref in Fig. 5(b) is plotted in Fig. 5(c) with the typical parameters in the next section. It can be found in Fig. 5(c) that the Psmax will dominate during the whole overvoltage process.

IV. Case Studies

A. System Description

Figure 7 shows that the wind power of a DFIG-based wind farm in the sending-end system is transferred to AC grid 2 by means of HVDC transmission. The wind farm is operating at the unit power factor under rated wind speed 12 m/s initially and the block occurs at t=0.5 s. Parameters of the system and PI controllers of DFIG are given in Tables I and II. Simulations are conducted in MATLAB/Simulink.

Fig. 7 Diagram of HVDC system with wind farms.

Table I Test System Parameters
ParameterSymbolValue
Rated stator voltage VsN 690 V
Base frequency fB 50 Hz
Rated DFIG active power Pn 150 MW
Rated DFIG power factor cos φ 0.9
Apparent power capacity of GSC Sc 50 MVA
Mutual inductance Xm 2.06 Ω
Stator inductance Xl 2.24 Ω
Maximum current limit of RSC Irmax 1600 A
Rated wind speed vrate 12 m/s
Rated voltage of HVDC VDC 500 kV
Rated DC current of HVDC IDC 2 kA
Reactive power compensation of rectifier station Qc 1000 Mvar
Table II Parameters of DFIG PI Controllers
PI controllerKpKi
RSC active power control 2.00 20
RSC reactive power control 1.00 20
RSC current control 0.60 100
GSC DC voltage control 8.00 400
GSC reactive power control 2.00 20
GSC current control 0.83 100

With system parameters available in Table I, the control parameters of DFIG under the initial steady-state condition where Vp=1.0 p.u. can be obtained as listed in Table III.

Table III Control Parameters of DFIG Under Initial Condition
ParameterValue (p.u.)
Qsmax 0.48
QGmax 0.73
VOV1 1.15
Qgmax 0.25
QGDmax 1.02
K1 9.60
K2 3.60

B. Study of Method Comparison

In this section, a comparison study is conducted among the following four methods: ① method 1, the unit power factor control without reactive control; ② method 2, the automatic voltage control at PCC [

19]; ③ method 3, the demagnetizing current control [16]; ④ method 4, the proposed P-Q coordination control. The resultant curves including the transient voltages at PCC and DC-link capacitor, the RSC voltage and current, the DFIG active power and reactive power are illustrated in Fig. 8.

Fig. 8 Transient response of PCC terminal voltage and power output of DFIG. (a) Transient voltage at PCC. (b) Voltage of DC-link capacitor. (c) RSC voltage. (d) RSC current with method 4. (e) Active power of DFIG. (f) Reactive power of DFIG.

It can be observed from Fig. 8 that: ① both RSC voltage/current and voltage of DC-link capacitor are within their limits in methods 2, 3, 4; ② methods 2, 3, 4 can better reduce the overvoltage peak value compared with method 1, which can make the PCC voltage below 1.3 p.u. to avoid further islanding risk; ③ method 4 has the best performance on overvoltage suppression compared with methods 2 and 3, e.g., the former has less peak/steady-state voltage and faster voltage recovery at PCC, because more reactive power can be absorbed with method 4. In summary, method 4 can effectively suppress transient overvoltage to help DFIG ride through the high voltage process after DC blocking and has the best performance compared with methods 2 and 3.

C. Study of Parameter Effect

Firstly, the effect of wind speed on transient overvoltage with method 4 is studied. Simulations with three typical wind speeds (8, 10 and 12 m/s) are compared in Fig. 9(a). It shows that method 4 has better overvoltage suppression effect at lower speed because DFIG has larger reactive power capacity and thus can absorb more reactive power.

Fig. 9 Transient PCC voltage with different parameters. (a) Different wind speeds. (b) Different de-loading triggering voltages.

Further, the effect of de-loading triggering voltage VOV1 on transient overvoltage with method 4 is investigated and the result is given in Fig. 9(b). It is found that less VOV1 can achieve less steady-state voltage at PCC, because less VOV1 means that earlier de-loading control will be taken and more reactive power will be absorbed by DFIG.

V. Conclusion

This paper studies the effect of the active/reactive power injection of WTG on transient overvoltage and proposes a P-Q coordination based HVRT control strategy for DFIG by means of a combined Q-V control and de-loading control to suppress PCC overvoltage. In the strategy, the reactive power operation region of DFIG considering its active power de-loading control is firstly evaluated and the outer loop parameters are determined according to the rules explained. Then, the reactive power controls of RSC and GSC are executed to absorb the surplus reactive power. The reactive power capacity of DFIG can be flexibly enlarged to absorb more reactive power in coordination with rapid active power control of DFIG to achieve de-loading operation. Finally, the simulations verify that the proposed HVRT strategy outperforms on PCC overvoltage suppression to avoid DFIG islanding compared with other two control methods.

Appendix

Appendix A

A. Sensitivity Analysis

An illustration of the voltage relationship between V˙p and V˙e is presented in Fig. A1(a) and is obtained as:

V˙p=V˙e-ΔV˙=V˙e-jXeI˙pPac+jQac=V˙pI˙p* (A1)

where V˙e=Veθe is the equivalent voltage of the sending-end AC system; V˙p=Vpθp is the terminal voltage at PCC; ΔV˙ is the line voltage drop; Pac and Qac are the active power and reactive power of the sending-end AC system, respectively; and I˙p and I˙p* are the branch current and its conjugate that injected into PCC by the AC system, respectively.

Fig. A1 Phasor diagram of sending-end AC voltage. (a) Normal case. (b) Overvoltage case.

Under normal condition where V˙p is at its rated voltage in Fig. A1(a), the AC system will inject reactive power for HVDC reactive power consumption. When the HVDC system converter is blocked due to some malfunctions such as the continuous commutation failure, the surplus reactive power will be reversely injected into the sending-end, resulting in a transient overvoltage surge at PCC, i.e., V˙p will be increased to even greater than V˙e, as illustrated in Fig. A1(b), in this case we have:

Pac=-PDFIGQac=-QDFIG-Qc=-QDFIG-Vp2Gc (A2)

V˙p can further become (A3) by combining (A1) and (A2):

Vp=(Ve+ΔVP)2+δVP2δVP=PDFIGXe/VeΔVp=-Ve+(Vp2-QDFIGXe-Vp2GcXe)/Ve (A3)

When Ve=1 is set in (A3). Equation (1) can be easily obtained from (A3).

Considering the real voltage profile, Vp can be deduced:

Vp=-b+b2-4ac2a (A4)

Accordingly, Vp/QDFIG and Vp/PDFIG can be obtained as (2) and (3).

The sign of Vp/QDFIG is analyzed below. The SCR of the sending-end AC system is defined as:

SCR=SscPdN=VpN2XePdN=1Xe (A5)

where Ssc is the short circuit capacity of the AC system; VpN and PdN are the base voltage and base power specified in per-unit analysis, respectively; and PdN is the rated HVDC power.

The reactive compensation capacity Qc at an HVDC converter station can concisely be expressed as:

Qc=VpN2Gc (A6)

For HVDC, Qc usually approximates from 0.4PdN to 0.6PdN, thus Gc0.6.

B. Effect of Power Control

Further, Vp/QDFIG and Vp/PDFIG are compared and analyzed as below.

VpQDFIG-VpPDFIG=(1+b2-4ac-2aPDFIGXe)Xe2aVpb2-4ac=k[1+b2-4ac-4ac-(b+1)2] (A7)

where k=Xe/(2aVpb2-4ac)>0.

Given the condition GcXe<1 and QDFIG<0, then b>-1.

Further, |Vp/QDFIG|>|Vp/PDFIG| can be deduced. In other words, adding reactive power absorption of DFIG has better effect than adding active power on overvoltage suppression.

In summary, when Vp>Ve and SCR>0.6, the following statement can be concluded: increasing inductive power absorption of DFIG can suppress the transient overvoltage and even has better effect than adjusting its active power.

Appendix B

The constraint of the reactive power limit of the stator side of DFIG considering the maximum rotor current limit is calculated as below.

The voltage, flux and power equations at the stator are listed as (B1)-(B3) by means of decoupling control with d-q axis.

vsd=Rsisd-ω1ψsq+ddtψsdvsq=Rsisq-ω1ψsd+ddtψsq (B1)
ψsd=Lsisd+Lmirdψsq=Lsisq+Lmirq (B2)
Ps=32(vsdisd+vsqisq)Qs=32(vsqisd-vsdisq) (B3)

Adopting the stator flux d-axis directional control and neglecting the voltage drop in the stator winding, there is:

ψsd=ψsψsq=0 (B4)
vsd=0vsq=Vs=ω1ψs (B5)

Consider the maximum endurable current of RSC as:

ird2+irq2(Irmax)2 (B6)

From (B1)-(B6), the constraint (4) of the reactive power limit at the stator side of DFIG is obtained.

References

1

Global Wind Energy Council. (2017, Dec.). Global wind report 2009-2016. [Online]. Available: http://gwec.net/publications/global-wind-report-2/. [百度学术

2

R. Piwko, P. Meibom, H. Holttinen et al., “Penetrating insights: lessons learned from large-scale wind power integration,” IEEE Power and Energy Magazine, vol. 10, no. 2, pp. 44-52, Mar. 2012. [百度学术

3

S. Wang, J. Hu, and X. Yuan, “Virtual synchronous control for grid-connected DFIG-based wind turbines,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 3, no. 4, pp. 932-944, Dec. 2015. [百度学术

4

J. Arrillaga, High Voltage Direct Current Transmission. London, UK: The Institution of Electrical Engineers, 1998. [百度学术

5

C. Rong, A. Mats, and X. Hailian, “Methods for transient AC overvoltage reduction at wind farm terminal,” in Proceedings of the 2016 China International Conference on Electricity Distribution (CICED), Xi’an, China, Aug. 2016, pp. 1-6. [百度学术

6

I. Erlich, B. Paz, M. K. Zadeh et al., “Overvoltage phenomena in offshore wind farms following blocking of the HVDC converter,” in Proceedings of the 2016 IEEE PES General Meeting, Boston, USA, Jul. 2016, pp. 1-5. [百度学术

7

Q. Guo, M. Yoon, C. Kim et al., “Commutation failure and voltage sensitivity analysis in a hybrid multi-infeed HVDC system containing modular multilevel converter,” International Transactions on Electrical Energy Systems, vol. 26, no. 10, pp. 2259-2271, Mar. 2016. [百度学术

8

C. Wessels and F. W. Fuchs, “High voltage ride through with FACTS for DFIG based wind turbines,” in Proceedings of 13th European Conference on Power Electronics and Applications, Barcelona, Spain, Sept. 2009, pp. 1-10. [百度学术

9

Z. Li, W. Li, and T. Pan, “An optimized compensation strategy of DVR for micro-grid voltage sag,” Protection and Control of Modern Power Systems, vol. 1, no. 1, pp. 1-10, Dec. 2016. [百度学术

10

I. Ngamroo and T. Karaipoom, “Cooperative control of SFCL and SMES for enhancing fault ride through capability and smoothing power fluctuation of DFIG wind farm,” IEEE Transactions on Applied Superconductivity, vol. 24, no. 5, pp. 1-4, Oct. 2014. [百度学术

11

R. Ou, X. Xiao, Z. Zou et al., “Cooperative control of SFCL and reactive power for improving the transient voltage stability of grid-connected wind farm with DFIGs,” IEEE Transactions on Applied Superconductivity, vol. 26, no. 7, pp. 1-6, Oct. 2016. [百度学术

12

J. Chang, J. Huang, L. Chen et al., “Discussion of doubly-fed wind turbines technical solutions on high voltage ride-through,” Advanced Materials Research, vol. 953, p. 565, Jul. 2014. [百度学术

13

H. Yu, “Overview of HVRT technical measures for DFIG,” IOP Conference Series: Earth and Environmental Science, vol. 64, no. 1, pp. 1-7, May 2017. [百度学术

14

X. Yan, G. Venkataramanan, Y. Wang et al., “Grid-fault tolerant operation of a DFIG wind turbine generator using a passive resistance network,” IEEE Transactions on Power Electronics, vol. 26, no. 10, pp. 2896-2905, Nov. 2011. [百度学术

15

D. Zhou, Y. Song, and F. Blaabjerg, “Modeling and stress analysis of doubly-fed induction generator during grid voltage swell,” in Proceedings of 42nd Annual Conference of the IEEE Industrial Electronics Society, Florence, Italy, Oct. 2016, pp. 4175-4180. [百度学术

16

J. Lopez, E. Gubia, E. Olea et al., “Ride through of wind turbines with doubly fed induction generator under symmetrical voltage dips,” IEEE Transactions on Industrial Electronics, vol. 56, no. 10, pp. 4246-4254, Jul. 2005. [百度学术

17

Z. Zheng, G. Yang, and H. Geng, “High voltage ride-through control strategy of grid-side converter for DFIG-based WECS,” in Proceedings of the 39th Annual Conference of the IEEE Industrial Electronics Society, Vienna, Austria, Nov. 2013, pp. 5282-5287. [百度学术

18

Y. Cui, L. Peng, W. Zhong et al., “Coordination strategy of reactive power control on wind farms based doubly fed induction generator,” Proceedings of the CSEE, vol. 35, no. 17, pp. 4300-4307, Sept. 2015. [百度学术

19

N. R. Ullah, T. Thiringer, and D. Karlsson, “Voltage and transient stability support by wind farms complying with the E.ON Netz grid code,” IEEE Transactions on Power Systems, vol. 22, no. 4, pp. 1647-1656, Dec. 2007. [百度学术

20

J. Kim, E. Muljadi, J. Park et al., “Adaptive hierarchical voltage control of a DFIG-based wind power plant for a grid fault,” IEEE Transactions on Smart Grid, vol. 7, no. 6, pp. 2980-2990, Nov. 2016. [百度学术

21

M. S. Marhaba, S. Farhangi, H. Iman-Eini et al., “Reactive power sharing improvement of droop-controlled DFIG wind turbines in a microgrid,” IET Generation, Transmission & Distribution, vol. 12, no. 4, pp. 842-849, Oct. 2017. [百度学术

22

J. Kim, J. Seok, E. Muljadi et al., “Adaptive Q-V scheme for the voltage control of a DFIG-based wind power plant,” IEEE Transactions on Power Electronics, vol. 31, no. 5, pp. 3586-3599, Jan. 2015. [百度学术

23

J. Kim, E. Muljadi, J. Park et al., “Flexible IQ-V scheme of a DFIG for rapid voltage regulation of a wind power plant,” IEEE Transactions on Industrial Electronics, vol. 64, no. 11, pp. 8832-8842, Apr. 2017. [百度学术

24

X. Zou, D. Zhu, J. Hu et al., “Mechanism analysis of the required rotor current and voltage for DFIG-based WTs to ride-through severe symmetrical grid faults,” IEEE Transactions on Power Electronics, vol. 33, no. 9, pp. 7300-7304, Sept. 2018. [百度学术

25

M. Z. Sujod, I. Erlich, and S. Engelhardt, “Improving the reactive power capability of the DFIG-based wind turbine during operation around the synchronous speed,” IEEE Transactions on Energy Conversion, vol. 28, no. 3, pp. 736-745, Sept. 2013. [百度学术

26

S. Mondal and D. Kastha, “Maximum active and reactive power capability of a matrix converter-fed DFIG-based wind energy conversion system,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 5, no. 3, pp. 1322-1333, Apr. 2017. [百度学术

27

M. Rahimi, “Coordinated control of rotor and grid sides converters in DFIG based wind turbines for providing optimal reactive power support and voltage regulation,” Sustainable Energy Technologies and Assessments, vol. 20, no. 1, pp. 47-57, Apr. 2017. [百度学术

28

Z. Lu, Z. Wang, H. Xin et al., “Small signal stability analysis of a synchronized control-based microgrid under multiple operating conditions,” Journal of Modern Power Systems and Clean Energy, vol. 2, no. 3, pp. 244-255, Sept. 2014. [百度学术

29

M. Wang-Hansen, R. Josefsson, and H. Mehmedovic, “Frequency controlling wind power modeling of control strategies,” IEEE Transactions on Sustainable Energy, vol. 4, no. 4, pp. 954-959, Oct. 2013. [百度学术

30

F. Lin, Z. Wang, G. Wang et al., “Robust reserve scheduling model of electric power system considering WTG de-loading capability,” Automation of Electric Power Systems, vol. 42, no. 1, pp. 64-70, Oct. 2018. [百度学术

31

Test Procedure of Wind Turbine High Voltage Ride Through Capability, NB/T 31111-2017. [百度学术