Journal of Modern Power Systems and Clean Energy

ISSN 2196-5625 CN 32-1884/TK

网刊加载中。。。

使用Chrome浏览器效果最佳,继续浏览,你可能不会看到最佳的展示效果,

确定继续浏览么?

复制成功,请在其他浏览器进行阅读

Unified Residue Method for Design of Compact Wide-area Damping Controller Based on Power System Stabilizer  PDF

  • Jun Qi
  • Qian Wu
  • Youbing Zhang
  • Guoqing Weng
  • Dan Zhou
College of Information Engineering, Zhejiang University of Technology, Hangzhou 310023, China

Updated:2020-03-19

DOI:10.35833/MPCE.2018.000370

  • Full Text
  • Figs & Tabs
  • References
  • Authors
  • About
OUTLINE

Abstract

A wide-area damping controller (WADC) is effective in damping inter-area low-frequency oscillation (LFO), if the time delay in a wide-area control loop can be properly handled. In order to simplify the WADC design and enlarge the delay adaptation range, the classic power system stabilizer (PSS) is adopted, and a new unified residue (UR) method is proposed for compact WADC design. The strategy of control loop selection is also improved by modifying the relative residue index based on a few dominant oscillation modes. The designed PSS-based compact WADC is as simple as classic PSS with no more than two lead-lag phase compensation units. Case studies are carried out on an IEEE 16-machine 68-bus power system. Simulation results demonstrate that the control loop selection before the WADC design is necessary and that the proposed selection strategy can easily pick out the suitable candidate control loops. In addition, it is feasible for the UR method to design WADCs with different time delays in the selected control loops. All the designed WADCs are effective in damping inter-area LFO and robust to time delay variations under operation conditions. Comparisons among five design methods for PSS-based WADC show that the proposed UR method is superior in delay adaptation, the conciseness of WADC structure and computation speed of parameters.

I. Introduction

LOW-FREQUENCY oscillation has been a serious problem in the stabilization of inter-area connected power systems for a long time. The infrastructure construction and application development of the wide-area measurement system (WAMS) [

1] in a smart grid provide technical possibilities in damping inter-area low-frequency oscillation (LFO) [2], [3]. However, new problems like time delay in the WAMS have emerged, which may vary from tens to several hundred ms or even more [4], and will affect the damping control performance [5], [6].

In wide-area damping control, it is necessary to balance the processing of time delay and the enhancement of damping capability. This problem can be solved by directly adopting the time-delay control theory which is usually complex and obscure [7]-[11], or using the Pade approximation [12]-[14] or delay compensation [15]-[20] to simplify the controller design. Wide-area damping controllers (WADCs) can be classified into the following two categories according to the differences in WADC structure shown in Fig. 1.

Fig. 1 Structure comparison of two WADC types. (a) Compact WADC. (b) Combinatorial WADC.

1) Compact WADC. As shown in Fig. 1(a), the structure of a compact WADC is very concise. Since the transfer function of time delay in WAMS block is exponential, the design of a WADC is more difficult than it would be under delay-free conditions. Two ways have been formed for the compact design of WADC. One way is to draw the support from the latest findings on time-delay control theories, among which the most widely used are based on Lyapunov stability theory and linear matrix inequality (LMI) technology [8]-[11]. Simulation results in [

8], [9] report that these WADCs can tolerate time delay up to 300 ms. In [10], two H∞ control schemes are developed for time-varying multiple delayed systems, where the upper bound of time delay is set to 150 ms in the simulation. In [11], LMI-based methods are applied to design the WADC, and can tolerate slight time delays below 100 ms. Conservatism and complexity are still the two major disadvantages of these methods. Another way is to transform the exponential time-delay function into a normal rational function by the Pade approximation [12]-[14]. Then conventional delay-free control theory can be put into use again. However, there will be some irrelevant oscillation modes introduced into the object system model during the transformation, and the order of the Pade function has to increase with large-scale time delays. The time delay of power system simulations in [12]-[14] is around 500 ms.

2) Combinatorial WADC. When there is a delay compensation block in the WADC as shown in Fig. 1(b), the delay-free controller block can use conventional control methods like the residue-based approach, the pole placement method, H2/H∞ robust control strategy, etc. The delay compensation block can be a signal prediction module based on a linear polynomial [

15] or exponential function [16], [17], system models [18], [19], or a transfer function for lead-lag phase compensation [20]. The tolerance to a large-scale time delay above 1000 ms is reported in [18], [19], and most of the simulation cases in [15]-[17], [20] are carried out under a time delay around 500 ms. The performance of time-delay compensation has great influence on the damping performance. In addition, the error of signal prediction may be enlarged when the delay in a control loop becomes larger, and the additional transfer function for delay compensation may complicate the structure of WADC or even make the subsequent design of a delay-free controller sink into a dilemma.

For simplicity, understandability and robustness, the classic power system stabilizer (PSS) has been widely used in power systems all over the world in recent decades. It has been confirmed by practical engineering applications that the classic PSS is outstanding in damping LFO and can improve electro-mechanical transient stability in conventional power systems [21]-[23]. Many engineers and researchers have made great efforts to apply classic PSS structure to WADC. In [

13] and [24], the time-delay controller block of Fig. 1(a) is replaced by PSS, and the Pade approximation is used to assist the PSS parameter calculation. In [15], [20] and [25], the combinatorial structure of a WADC in Fig. 1(b) is adopted, and a delay compensation block is delicately designed to offset the delay effect on PSS performance. In this paper, the conventional residue method will be modified to adapt the classic PSS to the applications of compact WADC of Fig. 1(a), without Pade approximation or delay compensation.

The remainder of this paper is organized as follows. In Section II, the modified relative residue index for control loop selection is discussed and derived from eigenvalue analysis. The unified residue (UR) method for designing a PSS-based compact WADC is clarified in Section III. Section IV demonstrates the performance of the proposed WADC designed by the UR method applied on an IEEE 16-machine 68-bus test system compared to several residue-based WADC design methods. Finally, conclusions are presented in Section V.

II. Mode Analysis and Control Loop Selection

A. Power System Model

A power system is a typical multi-input and multi-output high-order system. The selection of control loops may determine whether the WADC design will be successful or not, and how strong the damping effect of the WADCs will be. The n-order dynamic model of a power system with I inputs and O outputs can be described by a set of differential-algebraic equations as:

x ˙ = A x + B u y = C x (1)

where x R n × 1 , y R O × 1 , and u R I × 1 are the vectors of state variables, output variables, and control variables, respectively; A R n × n is the state matrix; B R n × I is the input matrix; and C R O × n   is the output matrix.

In order to express the eigen properties of state matrix A , right eigenvector M and left eigenvector N are introduced, and the following equations hold for A :

A M = M Λ N T M = I (2)

where Λ is a diagonal matrix with the eigenvalues λ 1, λ 2,…, λ n of A as diagonal elements.

A new state vector z is defined by a linear transformation:

x = M z (3)

Substituting the above expression for x into the state-space (1), we have:

z ˙ = M - 1 A M z + M - 1 B u = Λ z + N T B u y = C M z (4)

Supposing that the o th system output yo is selected as the feedback signal for a WADC whose output is connected to the i th system input ui , the transfer function of the system corresponding to the control loop ui-yo can be written as:

y o u i = C o M ( s I - Λ ) - 1 M - 1 B i = j = 1 n O b s o j C o n j i s - λ j = j = 1 n R o j i s - λ j (5)

where C o and B i are the o th row of C and the i th column of B , respectively; Obsoj , Conji , and Roji are the observability of yo , controllability of ui , and residue of the loop from ui to yo , respectively, with respect to the j th mode λ j ; and s is a complex variable. In order to evaluate the comparative strength of a control loop against a given mode λ j , the relative residue index RI in [

24] is defined as:

R I = R o j i k = 1 ,   k j n R o k i (6)

The larger the RI of the selected control loop ui-yo is, the weaker the interaction between WADC and other modes is. However, the model order of a wide-area interconnected power system is usually very high, and there are a large number of dynamic modes. It is time-consuming for the small signal analysis method and difficult for system identification technology to obtain all the modes, while the modes with large residue and rapid decay may induce interference and misjudgment into RI. Therefore, a new simplified RI is proposed in the following sub-section, which only considers residues of the m dominant modes rather than all the n modes in (6).

B. Simplified RI Based on Dominant Oscillation Modes

For (4), if there is a WADC installed between yo and ui , the relationship between ui and yo can be defined as:

u i = K A ( s ) e - s τ y o = H ( s ) y o (7)

where K and A( ) are the feedback gain and the phase compensator of the WADC, respectively; τ is the total time delay aggregated in the control loop ui-yo ; and H(s) is the transfer function of the WADC with the time delay τ.

Put the feedback control (7) into (4), and divide all the n modes of (4) into two groups as m dominant modes ( z M =[ z 1 ,   z 2 , ,   z m ]) and nm non-dominant modes ( z L =[ z m+ 1, z m + 2, …, z n ]). The dominant modes contain all the LFO modes adjacent to the imaginary axis or even in the right s plane, while the rest of the modes are classified as the non-dominant modes. Then the close-loop state-space model of the power system can be decomposed as:

z ˙ M z ˙ L = A M M      A M L A L M      A L L z M z L A M M = λ 1 + R o 1 i H ( s ) O b s o j C o n 1 i H ( s ) O b s o m C o n 1 i H ( s ) O b s o 1 C o n j i H ( s ) λ j + R o j i H ( s ) O b s o m C o n j i H ( s ) O b s o 1 C o n m i H ( s ) O b s o j C o n m i H ( s ) λ m + R o m i H ( s ) A M L = O b s o ( m + 1 ) C o n 1 i H ( s ) O b s o n C o n 1 i H ( s ) O b s o ( m + 1 ) C o n m i H ( s ) O b s o n C o n m i H ( s ) A L M = O b s o 1 C o n ( m + 1 ) i H ( s ) O b s o m C o n ( m + 1 ) i H ( s ) O b s o 1 C o n n i H ( s ) O b s o m C o n n i H ( s ) A L L = λ m + 1 + R o ( m + 1 ) i H ( s ) O b s o n C o n ( m + 1 ) i H ( s ) O b s o ( m + 1 ) C o n n i H ( s ) λ n + R o n i H ( s )   (8)

If among the m dominant modes, the residue of the aimed critical oscillation mode λ j satisfies:

R o j i > > R o k i       k = 1,2 , , m , k j (9)

Among all the n modes, the observability of the selected feedback signal y o satisfies:

O b s o j > > O b s o k      k = 1,2 , , n , k j (10)

Then

A M M λ 1 O b s o j C o n 1 i H ( s ) 0 0 λ j + R o j i H ( s ) 0 0 O b s o j C o n m i H ( s ) λ m (11)
A M L 0 (12)

By substituting (11) and (12) into the decomposed system model (8), the eigenvalue deviation of dominant modes caused by the WADC in (7) can be approximated as:

Δ λ k 0      k = 1,2 , , m , k j Δ λ j = R o j i H ( s ) = R o j i K A ( s ) e - s τ (13)

In the WADC design, a damping ratio between 0.05 and 0.2 is often suitable for inhibiting oscillations [

21]. Since the value of Roji in the selected control loop is comparatively large, KA(s) does not have to be very large to achieve the eigenvalue shift Δ λ j of the j th mode. Although the eigenvalue shift of non-dominant modes may be non-negligible, it is hard for a WADC to change the stability of these fast decaying modes.

According to the prerequisites of (9) and (10) in the analysis of system mode, two indices are defined in (14) and (15) for choosing control loops suitable for damping the critical oscillation mode λ j .

R I = R o j i k = 1 m R o k i (14)
O I = O b s o j k = 1 n O b s o k (15)

Notice that the denominator of RI is the sum of all the residues of the m dominant modes, while the denominator of observability index OI is the sum of observability of all the modes in control loop ui-yo .

C. Procedure of Control Loop Selection

In practical power system, the procedure of control loop selection mainly includes five steps:

  Step 1:   determine the critical and dominant modes in the power system, and form the residue-type transfer functions for all the candidate control loops.

  Step 2:   calculate the simplified RI in (14) for every candidate loop.

  Step 3:   pick out control loops with relatively high value of RI from Step 2.

  Step 4:   calculate the value of OI in (15) for the selected candidate control loops from Step 3.

  Step 5:   choose the control loops with relatively high OI from Step 4 to install a WADC.

According to the analysis in Section II-B, it is hard for a WADC designed for the critical mode with usual gain value to move eigenvalues of the non-dominant modes to cause new instabilities. In addition, the selection indices in (14) and (15) ensure that only the eigenvalue of the critical mode will be changed significantly by the WADC among all dominant modes, as can be seen from (13). Therefore, the control loop selected above can guarantee an evident improvement in damping the critical oscillation mode and a limited influence on other mode dynamics. Since a larger RI usually means a relatively larger OI, the control loop selection procedure can sometimes be reduced to Steps 1-3 for simplification. This will be illustrated and verified by case studies in Section IV.

III. Proposed UR Method for WADC Design

The time-delay inherent in phasor measurement unit (PMU), communication and controller is inevitable in a WAMS, and all these delays in a control loop can be aggregated as a single delay, denoted as τ. The impact of time delay on damping control is mainly reflected in the phase lag of a feedback signal. For a designated mode, the larger the delay is, the bigger the phase lag is. Time delay has less influence on the magnitude of a feedback signal owing to the small damping ratio of an underdamped oscillation mode and the relatively limited range of aggregated delay in practical WAMS.

Figure 2 is the block diagram of the classic PSS, including blocks of washout, gain, phase compensation and limiter in series, which is the core module of many types of engineering applied PSSs [

21]. It is going to be applied in the compact WADC in Fig. 1(a) to damp LFO of the power system considering time delay in WAMS. For a selected control loop, the PSS-based WADC is going to push the eigenvalue of the critical mode λ j toward the left s plane horizontally. The change of λ j under time-delay feedback can be described as:

Δ λ j = e - λ j τ R j K A ( λ j ) (16)

Fig. 2 Block diagram of PSS-based compact WADC.

where σ j   a n d   ω j   are the real and imaginary part of λ j , respectively; and Rj is the corresponding residue of λ j .

The eigenvalue variation Δ λ j in (16) should be designed as a negative real value in order to enhance the damping ability with little frequency change. According to the conventional residue method [21]-[24], the gain K in (16) should be positive, and thus A ( λ j ) must try to adjust the right part of (16) to a phase of - 180 ° .

Figure 3 illustrates the principle of the proposed UR for the PSS-based compact WADC design. The phase shift of residue and time delay on the j th mode is marked as θ 1 and θ 2, respectively. There are four possibilities for the location of total phase shift θ. The equations for these phase shifts are defined in (17).

θ 1 = R j θ 2 = - 180 ° ω j τ π - 180 ° < θ = θ 1 + θ 2 ± k × 360 ° 180 ° (17)

Fig. 3 Principle diagram of UR method for PSS-based compact WADC design. (a) θ in the first quadrant. (b) θ in the second quadrant. (c) θ in the third quadrant. (d) θ in the fourth quadrant.

where k is an integer to adjust the total phase shift θ in the appointed range ( - 180 ° ,   + 180 ° ] .

When θ is in the first or fourth quadrant, apparently a negative value of K is beneficial to reduce the order N of phase compensation function compared with a positive K. According to the design principle of UR, the compensation phase angle ∠A( λ j ) and K should be calculated for the four quadrants as:

A ( λ j ) = - θ      K = - Δ λ j / e - σ j τ R j A ( λ j )       0 ° < θ 90 ° (18)
A ( λ j ) = 180 ° - θ      K = Δ λ j / e - σ j τ R j A ( λ j )       90 ° < θ 180 ° (19)
A ( λ j ) = - 180 ° - θ      K = Δ λ j / e - σ j τ R j A ( λ j )       - 180 ° < θ - 90 ° (20)
A ( λ j ) = - θ      K = - Δ λ j / e - σ j τ R j A ( λ j )       - 90 ° < θ 0 ° (21)

It is worth noting that the |∠A( λ j )| is restricted within 90 °   as indicated by (18)-(21). For the phase compensation function A(s) in (22), every lead-lag unit is suitable for phase shift compensation up to 45 ° . Clearly, the number of lead-lag units needed by the WADC will be no more than two, that is N 2 , no matter how long the time delay is.

A ( s ) = 1 + T 1 s 1 + T 2 s N (22)

Drawing on the experience of the conventional residue method [21]-[24], the coefficients T 1, T 2 and N of (22) can be calculated similarly. The signal washout block serves as a high-pass filter with the time constant TW in the range of 1-20 s [

21]. The output limiter is employed to avoid excessive influence on the regulating device like excitation system or flexible AC transmission system (FACTS), and it is often set as ±0.05-0.10 p.u. [23]. In the following case study, TW and output limiter are set to 5 s and ±0.05 p.u., respectively.

The proposed UR method is used to compute parameters of the PSS-based compact WADC in Fig. 2, no matter whether there is time delay in the control loop. This method is also applicable in the design of other types of wide-area PSSs if they are based on the classic PSS structure of Fig. 2. In order to clarify the improvement of the proposed UR method, a comparison is illustrated in Table I, which contains the information on PSS parameters designed by the proposed UR and the conventional residue method with lead-lag delay compensation (CR+DC) [

24]. Abviously, compared with CR+DC, the WADC structure is dramatically simplified by adopting UR, especially when the time delay becomes large.

TABLE I Comparison of PSS Parameters Designed by UR and CR+DC
Design methodQuadrantA(λj ) K N
τ = 0 τ > 0
Proposed UR θ 1st θ <0 1-2 1-2
2nd 180°θ >0
3rd 180°θ >0
4th θ <0
CR+DC θ 1 1st 180°θ 1 >0 3-4 N | τ = 0 + - θ 2 / 45 °
2nd 1-2
3rd 180°θ 1 1-2
4th 3-4
NOTE:

θ and θ 1 are both between the range of (180°, +180°]; · imdicates the nearest integers greater than or equal to the value.

IV. Case Study

To investigate the feasibility of the proposed UR for WADC design in a relatively complex and realistic power system, the IEEE 16-machine 68-bus test system shown in Fig. 4 is studied in this section.

Fig. 4 IEEE 16-machine 68-bus test system.

This system is a simplified interconnected system of five areas including New England, New York, and Areas 3-5. It has been used to test the effectiveness of a WADC in [

8]. All generators are modeled as a 6-order model. The excitation system is adopted for generators G1-G15, and all loads are represented as constant impedance. In addition, PSS is equipped at G1-G12 to provide damping for local and some inter-area oscillation modes. The detailed description of this test system can be found in [26]. For this test system, bus 16 and bus 51 are equipped with a ±500 Mvar static var compensator (SVC) to maintain its voltage profile.

A. Control Loop Selection

There are 21 LFO modes in the IEEE 16-machine 68-bus test system as displayed in Table II. Mode 2 has the smallest damping ratio and lower oscillation frequency, so it is considered as the critical mode and should be damped first by WADC. Modes 1-4 are selected as the dominant modes as the real part of their eigenvalues is larger than the threshold set as 1. The smaller the threshold is, the more LFO modes the dominant-mode class contains. Nevertheless, over a certain threshold value, as the newly added LFO modes are relatively far away from the critical mode to be controlled, it is difficult for them to get near the imaginary axis after the WADC installation. In this study, 1 is sufficient for the threshold.

TABLE II LFO Modes in IEEE 16-machine 68-bus Test System Without WADC
ModeEigenvalueDamping ratioFrequency (Hz)
1 0.3037±2.4067j 0.1252 0.3830
2 0.0794±3.1885j 0.0249 0.5075
3 0.5617±4.1656j 0.1336 0.6630
4 0.2930±4.9611j 0.0590 0.7896
5 1.0235±6.9985j 0.1447 1.1139
6 1.1231±7.4883j 0.1483 1.1918
7 1.1127±8.0869j 0.1363 1.2871
8 1.1686±6.8031j 0.1693 1.0828
9 1.9061±7.3233j 0.2519 1.1655
10 1.4781±8.3750j 0.1738 1.3329
11 2.4333±9.0537j 0.2596 1.4409
12 2.6278±9.4493j 0.2679 1.5039
13 3.0382±10.1073j 0.2879 1.6086
14 2.4283±11.2345j 0.2113 1.7880
15 2.0119±11.7278j 0.1691 1.8665
16 15.5515±3.5896j 0.9744 0.5713
17 15.9409±7.7753j 0.8988 1.2375
18 16.1808±9.6267j 0.8594 1.5321
19 21.0274±11.2067j 0.8825 1.7836
20 21.7132±11.9978j 0.8753 1.9095
21 69.6504±1.7317j 0.9997 0.2756

Generally speaking, automatic voltage regulators (AVR) on generators [

21], FACTS equipment (e.g., SVC, static synchronous compensator) [8], HVDC [27], inverter-based power source (e.g., energy storage, doubly-fed induction generator, photovoltaic) [28], [29] all can be used for damping LFOs. Hence, the input signal of the power system model for a WADC design can be the corresponding auxiliary input of these above devices. They can be connected by a output port of WADC in series. For the IEEE 16-machine 68-bus power system with AVR and SVC, there are 17 potential system inputs including the reference voltage of AVR VR on G1-G15, and the reference voltage of SVC VS on SVC1 and SVC2. There are 326 potential system outputs including the active power P L on 86 transmission lines, and the relative machine angle δ and the relative machine speed ω between any two machines. Therefore, there are 5542 candidate control loops in this test system.

RI in (14) for all these loops is calculated and sorted in descending order. The control loops of the top 10 RI value are given in Table III as No. 1-10. For comparison, control loop No. 11 with medium RI value is also listed in Table III.

TABLE III Selection Indices and WADC Parameters for 11 Control Loops Without Time Delay
Control loopSelection indexWADC parameter
No. y u RI OI N T 1 (s) T 2 (s) K
1 δ 14-16 VS 2 0.91 0.41 2 0.14 0.70 1.680
2 ω 14-16 VS 2 0.89 0.44 1 0.34 0.29 36.300
3 δ 14-16 VR 14 0.80 0.41 2 0.15 0.68 0.438
4 P L52-68 VS 2 0.75 0.26 2 0.14 0.73 0.147
5 ω 14-16 VR 14 0.74 0.44 1 0.36 0.27 9.660
6 δ 15-16 VS 2 0.72 0.17 2 0.14 0.69 2.670
7 P L1-31 VS 2 0.72 0.23 2 0.14 0.68 0.989
8 P L52-42 VS 2 0.72 0.22 2 0.14 0.71 0.205
9 P L31-38 VS 2 0.67 0.31 2 0.14 0.72 0.850
10 P L1-31 VR 14 0.67 0.23 2 0.15 0.66 0.259
11 ω 5-7 VS 2 0.27 0.41 2 0.56 0.18 0.877

B. Test of WADC Under Delay-free Condition

WADCs are designed for all the control loops in Table III in order to increase the damping ratio of Mode 2 to 0.1. The eigenvalue shift Δ λ 2 of Mode 2 is calculated, which is approximately equal to 0.2395. According to the principle of UR, the WADC parameters when τ = 0 s are calculated and displayed in Table III. It can be seen that K in some control loops may be negative, but only one or two lead-lag compensation units are needed by all the loops as N shown in Table III.

Then these WADCs are put into the corresponding control loops. The damping ratio histogram of Modes 1-4 is presented in Fig. 5. Compared with the open loop marked as No.0, the damping ratios of Mode 2 in the closed loops No.1 to No.10 have been increased to the expected level of 0.1, while there is no evident change in the damping ratio of other dominant modes that are still larger than the acceptable level 0.05. For closed loop No.11, although there is obvious improvement in the damping ratio of Modes 1-2, Mode 3 almost halves and becomes the new underdamped oscillation mode. This is caused by the interference between the WADC and Mode 3 in the control loop with relatively small RI of Mode 2, which is further discussed based on the root loci of Fig. 6(b).

Fig. 5 Damping ratio histogram of Modes 1-4 when WADC is installed in control loops No. 1-11 compared with open loop No. 0.

Fig. 6 Root loci comparison. (a) CL2. (b) CL11.

Figure 6 is the root loci for the open control loops No. 2 (CL2) and No. 11 (CL11) with the washout and phase compensation blocks in series. The negative K on the root locus decreases along with the expected damping ratio of Mode 2 (M2), rising from the initial value 0.0249 to 0.2. The major differences between the two root loci lie in Modes 1-3 (M1-3). For CL2, accompanying the decrease of K, the damping ratio of M2 has been enhanced continuously, while six other oscillation modes that have been mentioned in Table II almost remain the same. By contrast, it is not possible to raise the damping ratio of M2 in CL11 to 0.2. Instead, the damping ratio will turn around to decrease when it has reached 0.16 following the decrease of K. In addition, M1 and M3 in CL11 are dramatically affected by the feedback control of the WADC. The eigenvalue of M3 moves towards the imaginary axis quickly, and this is a non-negligible threat to system stability. Therefore, CL2 is more suitable for WADC installation than CL11. For comparison, another three modes (Modes 5-7) whose damping ratio ranks second only to Modes 1-4 are displayed in Fig.6. They are relatively far away from the imaginary axis, and they move little during the change of K value.

It can be concluded from Figs. 5 and 6 that control loop selection is very crucial to a successful design and a good performance of the WADC, and there is little damping difference among WADCs in the control loops with comparably large values of RI as large RI usually means large OI.

The damping effect of the above WADCs is tested through time-domain simulation on nonlinear and time-varying IEEE 16-machine 68-bus test system. A three-phase short-circuit fault is applied on one of the tie lines between Bus 1 and Bus 2. The fault occurs at t = 1 s and is cleared by disconnecting the fault line 0.2 s later. After the disturbance, the open loop system will oscillate for more than 20 s, which is reflected in the oscillations of the relative rotor speed ω 14 - 16 and the active power P L68-52 on line 68-52 shown in Fig.7. When one of the control loops No. 1-3 (CL1-3) is equipped with the designed WADC, the oscillation of system dynamics is well inhibited within about 10 s. In fact, all the WADCs of control loop No. 1-10 in Table III have a similar damping effect.

Fig. 7 Comparison of system dynamics before and after WADC equipped in different CLs. (a) CL1. (b) CL2. (c) CL3.

C. Test of WADCs Under Time-Delay Condition

Taking control loop CL1 as an example, the WADC is designed with different time delays. By close loop eigenvalue analysis, the damping ratios of the dominant modes Modes 1-4 are shown in the histogram of Fig. 8(a). In the time-delay range of 0-2 s, the damping ratio of Mode 2 is approximately equal to or larger than the expected value of 0.1. There is no evident deterioration in the damping ratios of other modes.

Fig. 8 WADC in CL1. (a) Damping ratios under different time delays. (b) Power system dynamics under different time delays.

The key parameters of the WADC in CL1 with time delay 0.5 s, 1.0 s, 1.5 s and 2.0 s are listed in Table IV. The system dynamics under different time delays are given in Fig. 8(b) when the corresponding control parameters are set for the WADC in CL1. The results show that the performance of the WADC with time delay is as good as that under the delay-free condition in Fig. 7, even when the time delay rises up to one oscillation cycle (about 2.0 s) of Mode 2 in Table II. As well as CL1, other control loops No. 2-10 listed in Table III have also been tested in this study, and this confirms that the proposed UR is feasible for WADC design in the selected control loops with relatively large RI value.

TABLE IV Parameters of WADCs in CL1 with Different Time Delays
τ (s) K N T 1 (s) T 2 (s)
0.5 0.281 1 0.36 0.28
1.0 1.450 2 0.14 0.68
1.5 .248 1 0.37 0.26
2.0 1.260 2 0.15 0.66

According to the principle of the UR method, the deviation of the actual time delay will cause phase mismatch. Fortunately, only when the phase mismatch is very large will the damping performance be strikingly affected. The WADCs in Table IV designed with time delay 0.5 s and 1.5 s have been taken to test the robustness of WADC to delay deviations. It confirms that after the line fault disturbance, the rotor speed ω 14-16 and active power P L68-52 can return to steady state in about 10-15 s with the actual delay deviation Δ τ up to ±0.2 s.

Other simulation results obtained during our research verify that only when | Δ τ | reaches up to about 400 ms will the WADC start to deteriorate the power system damping ability.

For most of the time, it is common that the real-time delay randomly changes within a narrow range, and the robustness of WADC can ensure the damping effect. If there are signal congestions or communication faults in the WAMS, the time delay of the current control loop may exceed a reasonable range. In this case, an adaptive WADC system has been conceived in some studies such as [

23], [24], [30] and [31]. A fast switching to a control loop with normal delay accompanied by a fast update of the controller’s parameters can ensure the stability and reliability of power systems with a wide range of time-varying delays.

C. Comparison of Design Methods of PSS-based WADC

To further show the advantage of the proposed UR method, three other types of residue-based method are tested in the normal IEEE 16-machine 68-bus test system to design the PSS-based compact WADC in CL1 for the same expected damping value of 0.1.

1) Conventional residue (CR) method in [

21];

2) CR method with first- and second-order Pade approximation (CR+1st Pade, CR+2nd Pade);

3) Conventional residue method with LMI technology (CR+LMI) in [

8].

Since the residue phase of Mode 2 in CL1 is 96.14° in the third quadrant, the WADCs designed by these methods when τ = 0 s are the same as that with the UR method. As the time delay increases, Fig. 9(a) presents the damping ratios of Mode 2 when the WADC is designed by different methods. For CR, the damping ratio is relatively high when the time delay is near 0 s or 2 s, but it becomes negative during time delays of 0.5-1.5 s. For CR+LMI, the damping ratio cannot reach the expected value of 0.1 in most delay cases, and the worst case is that the damping ratio is equal to the value of 0.0249 for the open loop in Table II. CR+1st Pade is satisfactory in damping control for time delays less than 0.9 s. By increasing the order of the Pade approximation, the delay adaptation range of the CR+Pade method can be expanded, while there will be more irrelevant oscillation modes. From the comparison, it can be seen that the proposed UR can guarantee a satisfactory damping ratio for time delays from 0 s to 2 s.

Fig. 9 WADC in CL1 designed by different methods. (a) Comparison of the damping ratio of Mode 2. (b) Damping ratio histogram of Modes 1-4 with time delay of 1.5 s.

Figure 9(b) shows another perspective to compare the damping ratio of Modes 1-4 when the WADC in CL1 is designed by different methods with a time delay of 1.5 s. The damping ratios of Modes 1, 3 and 4 change little after the installation of WADC, which is consistent with the conclusion of control-loop selection strategy in Section II-C. For a time delay of 1.5 s, only the proposed UR method is able to raise the damping ratio of Mode 2 to the expected value of 0.1.

The parameters of WADCs designed with a time delay of 1.0 s by the four methods are displayed in Table V, accompanied by the relative computation time (RCT). Supposing that the RCT for CR method is considered as 100%, the proposed UR method is only a little longer than that of CR. However, the RCTs of CR+Pade and CR+LMI methods are larger than 300% and 1000%, respectively. The CR+LMI method is especially vulnerable to the system model order. In current research on the design of LMI-based WADC, it is a common technique to apply system model reduction to get a feasible LMI solution. By contrast, system model order has little influence on the application of the CR and UR methods.

TABLE V Parameters of PSS-based Compact WADCs Designed with Time Delay 1.0 s and Comparison of RCT
Designe method K N T 1 T 2 RCT
CR 1.680 2 0.14 0.70 100%
CR+Pade 0.181 1 0.57 0.17 >300%
CR+LMI 0.000 2 0.14 0.70 >1000% a
UR 1.450 2 0.14 0.68 119%
NOTE:

a For a set of PSS parameters and 7-order system model.

Putting these WADCs into the control loop CL1, the comparison of system dynamics after line fault is presented in Fig. 10. It is clear that the WADC designed by UR has comfortably damped out the system oscillation, while the WADC designed by CR has unexpectedly caused system instability, and WADCs designed by CR+Pade and CR+LMI have little effect on damping enhancement.

Fig. 10 Comparison of damping performance of WADCs designed by different methods with time delay of 1.0 s.

Finally, five design methods for PSS-based WADC are compared from the following four aspects: ① consideration of delay; ② WADC order; ③ computation time; ④ delay adaptation range. From the comparison in Table VI, it can be concluded that:

1) The CR method cannot deal with time delay, and the designed WADC cannot adapt to evident delays.

2) The CR+DC method is used to design a PSS-based combinatorial WADC, and the structure of the WADC will complicate as the delay arises.

3) The ability of CR+Pade method to handle time delay largely relies on the order of Pade approximation, and it is relatively more time-consuming than CR and UR.

4) The greatest defect of CR+LMI method lies in the long computation time but narrow range of delay adaptation.

5) The proposed UR method wins on all four aspects. It can deal with time delay over a large range, its computation time is comparable with CR, and the designed WADC structure is the most concise.

TABLE VI Comparison of Design Methods for PSS-based WADC
Design methodDelay considered?WADC orderComputation timeDelay adaptation range
CR No 1-4 Short Narrow
CR+DC Yes High for large delays Short Wide
CR+Pade Yes 1-4 Medium Medium-wide a
CR+LMI Yes 1-4 Long b Narrow
UR Yes 1-2 Short Wide
NOTE:

a It depends on the order of Pade approximation; b This computation time increases faster than the rise of system model order.

V. Conclusion

This paper adopts a classic PSS structure for the design of compact WADC, and proposes the UR method for PSS parameter calculation considering the time delay in WAMS. A control loop selection index based on dominant oscillation modes is suggested for simplicity. Results from eigenvalue analysis and time-domain simulations carried out on the IEEE 16-machine 68-bus test system have verified that:

1) Control loop selection is an indispensable step in the design of WADC, and the proposed relative residue index based on dominant oscillation modes is succinct and effective in loop selection. In the selected loops, the effort of feedback control is primarily concentrated on the critical mode.

2) The structure of WADC is greatly simplified. While at the same time, the time-delay adaptability and robustness of WADC is dramatically improved by the proposed UR method.

3) A considerably large percentage of control loops are suitable for WADC equipment, and the designed PSS-based compact WADC is effective to damp out low-frequency power oscillations with different time delays.

Owing to its simplicity in design and effectiveness in damping performance, the proposed PSS-based compact WADC designed by the UR method has great potential for engineering applications in wide-area interconnected power systems.

REFERENCES

1

R. B. Sharma and G.M. Dhole, “Wide area measurement technology in power systems,” Procedia Technology, vol. 25, pp. 718-725, Sept. 2016. [百度学术

2

S. M. Ali, M. Jawad, B. Khan et al., “Wide area smart grid architectural model and control: a survey,” Renewable & Sustainable Energy Review, vol. 64, pp. 311-328, Oct. 2016. [百度学术

3

Y. Chompoobutrgool, L. Vanfretti, and M. Ghandhari, “Survey on power system stabilizers control and their prospective applications for power system damping using synchrophasor-based wide-area systems,” European Transactions on Electrical Power, vol. 21, no. 8, pp. 2098-2111, Nov. 2011. [百度学术

4

H. Wu, S. T. Konstantinos, and T. H. Gerald, “Evaluation of time delay effects to wide-area power system stabilizer design,” IEEE Transactions on Power Systems, vol. 19, no. 4, pp. 1935-1941, Nov. 2004. [百度学术

5

J. He, C. Lu, X. Wu et al., “Design and experiment of wide area HVDC supplementary damping controller considering time delay in China southern power grid,” IET Generation, Transmission & Distribution, vol. 3, no. 1, pp. 17-25, Jan. 2009. [百度学术

6

F. Wilches-Bernal, B. J. Pierre, R. T. Elliott et al., “Time delay definitions and characterization in the pacific DC intertie wide area damping controller,” in Proceedings of IEEE PES General Meeting, Chicago, USA, Jul. 2017, pp. 1-5. [百度学术

7

X. Zhang, C. Lu, S. Liu et al., “A review on wide-area damping control to restrain inter-area low frequency oscillation for large-scale power systems with increasing renewable generation,” Renewable & Sustainable Energy Reviews, vol. 57, pp. 45-58, May 2016. [百度学术

8

W. Yao, L. Jiang, J. Wen et al., “Wide-area damping controller of FACTS devices for inter-area oscillations considering communication time delays,” IEEE Transactions on Power Systems, vol. 29, no. 1, pp. 310-329, Jan. 2014. [百度学术

9

Y. Li, Y. Zhou, F. Liu et al., “Design and implementation of delay-dependent wide-area damping control for stability enhancement of power systems,” IEEE Transactions on Smart Grid, vol. 8, no. 4, pp. 1831-1842, Jul. 2017. [百度学术

10

J. Li, Z. Chen, D. Cai et al., “Delay-dependent stability control for power system with multiple time-delays,” IEEE Transactions on Power Systems, vol. 31, no. 3, pp. 2316-2326, May 2016. [百度学术

11

S. Wang, X. Meng, and T. Chen, “Wide-area control of power systems through delayed network communication,” IEEE Transactions on Control Systems and Technology, vol. 20, no. 2, pp. 495-503, Mar. 2012. [百度学术

12

J. Qi, Q. Jiang, G. Wang et al., “Wide-area time-delay robust damping control for power system,” European Transactions on Electrical Power, vol. 19, no. 7, pp. 899-910, Oct. 2009. [百度学术

13

M. R. Shakarami and I. F. Davoudkhani, “Wide-area power system stabilizer design based on grey wolf optimization algorithm considering the time delay,” Electric Power Systems Research, vol. 133, pp. 149-159, Apr. 2016. [百度学术

14

P. Saraf, K. Balasubramaniam, R. Hadidi et al., “Design of a wide area damping controller based on partial right eigenstructure assignment,” Electric Power Systems Research, vol. 134, pp. 134-144, May 2016. [百度学术

15

Y. Liu, X. Li, Z. Liu et al., “A compensation design for wide-area power system stabilizer distributed time delay based on grey prediction,” Automation of Electric Power Systems, vol. 39, no. 12, pp. 44-49, Jun. 2015. [百度学术

16

B. Yang, Y. Li, Q. Jiang et al., “A compensation method for time delay of wide area measurement signals applying improved prony algorithm,” Power Systems Technology, vol. 40, no. 6, pp. 1778-1784, Jun. 2016. [百度学术

17

M. Beiraghi and A. M. Ranjbar, “Adaptive delay compensator for the robust wide-area damping controller design,” IEEE Transactions on Power Systems, vol. 31, no. 6, pp. 4966-4976, Nov. 2016. [百度学术

18

W. Yao, L. Jiang, J. Wen et al., “Wide-area damping controller for power system interarea oscillations: a networked predictive control approach,” IEEE Transactions on Control System Technology, vol. 23, no. 1, pp. 27-36, Jan. 2015. [百度学术

19

B. P. Padhy, S. C. Srivastava, and N. K. Verma, “A wide-area damping controller considering network input and output delays and packet drop,” IEEE Transactions on Power Systems, vol. 32, no. 1, pp. 166-176, Jan. 2017. [百度学术

20

F. Bai, L. Zhu, Y. Liu et al., “Design and implementation of a measurement-based adaptive wide-area damping controller considering time delays,” Electric Power Systems Research, vol. 130, pp. 1-9, Jan. 2016. [百度学术

21

P. Kundur, Power System Stability and Control. New York: McGraw-Hill, 1994. [百度学术

22

Q. Liu, Power System Stability and Generator Excitation Control. Beijing: China Electric Power Press, 2007. [百度学术

23

J. Zhang, C. Y. Chung, C. Lu et al., “A novel adaptive wide area PSS based on output-only modal analysis,” IEEE Transactions on Power Systems, vol. 30, no. 5, pp. 2633-2642, Sept. 2015. [百度学术

24

C. Lu, J. Zhang, and Y. Han, Wide-area Dynamic Stability Identification and Control of Power System. Beijing: Science Press, 2015. [百度学术

25

X. Zhang, C. Lu, X. Xie et al., “Stability analysis and controller design of a wide-area time-delay system based on the expectation model method,” IEEE Transactions on Smart Grid, vol. 7, no. 1, pp. 520-529, Jan. 2016. [百度学术

26

G. Rogers, Power System Oscillations. Norwell: Kluwer, 2000. [百度学术

27

Y. Cao, W. Wang, Y. Li et al., “A virtual synchronous generator control strategy for VSC-MTDC systems,” IEEE Transactions on Energy Conversion, vol. 33, no. 2, pp. 750-761, Jun. 2018. [百度学术

28

L. Wang, Q. S. Vo, and A. V. Prokhorov, “Stability improvement of a multimachine power system connected with a large-scale hybrid wind-photovoltaic farm using a supercapacitor,” IEEE Transactions on Industrial Applications, vol. 54, no. 1, pp. 50-60, Jan. 2018. [百度学术

29

Y. Zhu, C. Liu, B. Wang et al., “Damping control for a target oscillation mode using battery energy storage,” Journal of Modern Power Systems and Clean Energy, vol. 6, no. 4, pp. 833-845, Jul. 2018. [百度学术

30

C. Lu, Y. Zhao, K. Men et al., “Wide-area power system stabiliser based on model-free adaptive control,” IET Control Theory & Applications, vol. 9, no. 13, pp. 1996-2007, Aug. 2015. [百度学术

31

S. Zhang and V. Vittal, “Wide-area control resiliency using redundant communication paths,” IEEE Transactions on Power Systems, vol. 29, no. 5, pp. 2189-2199, Sept. 2014. [百度学术