Abstract
Due to the advantages such as low line cost, low transmission loss, and high power supply reliability, DC distribution networks have become the main development trend for future distribution networks. In this paper, a typical DC distribution network with multiple voltage levels is considered as a research object. It is proposed that the interface converters between DC buses with different voltage levels be implemented through the series-parallel combination of full-bridge LLC resonant converters. To realize the decentralized self-discipline control of DC voltage under various working conditions, different slack buses are prepared according to the voltage ranges of the DC buses, and the voltage regulation modes of the DC distribution network are divided into main voltage regulation mode, backup voltage regulation mode, and off-grid voltage droop regulation mode. By introducing a voltage coefficient related to DC voltage deviation as a basis for mode switching, the voltage fluctuations caused by slow switching between control modes in the method of traditional voltage margin control is reduced, facilitating fast and smooth switching between different voltage regulation modes. Finally, a simulation model for DC distribution networks is constructed utilizing MATLAB/Simulink. Simulation results verify the effectiveness and feasibility of the proposed voltage regulation modes and switching methods for DC distribution networks. Finally, an experimental platform is also constructed to verify the feasibility of the mode switching method proposed in this paper.
Keywords
DC distribution network; decentralized self-discipline control; voltage regulation mode; mode switching
BASED on the combined crises of environmental pollution and fossil energy shortages, renewable energy has become a major focus. Therefore, energy infrastructures will experience profound changes in the future. However, renewable energy sources such as wind power and solar energy, have the characteristics of indirectness, randomness, and volatility, meaning traditional AC power distribution systems encounter significant issues when large numbers of renewable energy sources are connected to the grid [
The key to the stable operation of DC distribution systems is the stability of DC bus voltage. The control objective is to coordinate power exchange between sources and loads effectively within a DC distribution system by implementing a reasonable coordination control mechanism so that the DC voltage can be stabilized within a certain range. The research on DC bus voltage control is relatively mature and various control schemes have been developed, including master-slave control [
Similar to AC distribution networks, future DC distribution systems must engage in mutual cooperation to realize multi-level DC distribution networks. In this paper, a typical DC distribution network with high, medium, and low voltage levels is considered as a research object. A novel mode switching method (NMSM) is proposed for the DC distribution network, which has many operation modes. The NMSM can realize automatic switching between different voltage regulation modes by introducing coefficients related to DC bus voltage deviation. Compared to traditional voltage margin control (TVMC), NMSM proposed in this paper makes switching between voltage regulation modes faster and reduces fluctuations in voltage and power during the transition process.
The remainder of this paper is organized as follows. Section II introduces the architecture of a typical DC distribution network and an interface converter for switching between different DC buses. Section III proposes three different voltage regulation modes for operating the DC distribution network to ensure the stability of DC bus voltage under any operation conditions. Section IV analyzes the deficiencies of TVMC. On the basis of this analysis, a fast mode switching method based on voltage coefficients is proposed to realize automatic switching between different voltage regulation modes. Section V presents simulations verifying the feasibility and effectiveness of the voltage regulation modes and NMSM. Section VI concludes this paper.
A typical ring DC distribution network with multi-stage bus interconnections is presented in

Fig. 1 Topology of a ring DC distribution network.
The system is mainly composed of the following four parts.
1) Main network converters. The main network converters include P1 and P8. P8, which is the voltage source converter (VSC), is the interface converter for the 110 kV high-voltage alternating current (HVAC) main network and ±10 kV medium-voltage direct current (MVDC) distribution network. P1 is the interface converter between the ±150 kV HVDC main grid and MVDC distribution network. Since the conversion of DC voltage cannot be realized through electromagnetic induction, unlike AC systems, a power converter based on power electronics technology must be utilized to realize voltage conversion and energy transfer. In the proposed system, DC/DC interface converters between the DC buses of different voltage levels are formed based on the series-parallel combination of full-bridge LLC resonant converters [

Fig. 2 DC/DC interface converter. (a) Schematic diagram of LLC resonant converter circuit. (b) Interface converter between HVDC and MVDC buses. (c) PV grid-connected converter. (d) Interface converter between MVDC and LVDC buses.
2) Renewable energy generation unit. Wind farms and photovoltaic (PV) cells are connected to the DC side via the VSC (P3) and DC/DC converter (P6), respectively. Since the output voltage of the PV array is approximately 600 V, the PV grid-connected converter is implemented with a combined structure, as shown in
3) Energy storage (ES) unit. The ES unit is connected to the MVDC side through a bidirectional DC/DC converter (P5). However, supercapacitors face the issue of low-voltage levels. Therefore, in this study, by considering the LLC resonant converter as a standard module, the energy conversion scheme for the ES system presented in
4) Loads. Loads include both AC loads and DC loads. AC loads are connected to the MVDC bus through VSC (P2). DC loads and the ±750 V LVDC distribution network are connected to the MVDC distribution network through an input-series output-parallel structure, as shown in
In the proposed system, a large number of interface converters are utilized, which are combinations of series and parallel connections with LLC resonant converters as standard modules. This not only reduces the thermal and electrical stress on power devices and improves system reliability, but also shortens the development cycle for the system, thereby reducing the development costs.
Similar to an AC distribution network, the control technology in DC distribution networks can be divided into three levels: distribution network level, microgrid level, and unit level. The structure of a DC distribution network is illustrated in

Fig. 3 Control structure of a DC distribution network.
Based on various data such as distributed generation power predictions, load demands, ES operation status, and market information, and according to different optimal operation objectives and constraints, the purpose of control on the distribution network level is to formulate a DC grid operation scheduling strategy in real time so that safe and economical operation of the system can be guaranteed. Voltage drops along the main line and network loss are considered at this control level.
In a DC distribution network, there are many types of power supplies with different degrees of controllability, so there are many operation states in such a system. The control objective at the microgrid level is to ensure coordinated control of power supplies and loads in a DC distribution network. DC bus control tasks are assigned to converters according to various working conditions of the distribution network to maintain DC bus voltage stability and power balance of the system. The microgrid level is the main focus of this paper.
The unit level is responsible for the basic control of power electronic converters. Based on local information, the voltage, power, and current of each unit are regulated to ensure normal operation.
When the load power changes or the maximum power of distributed generation units changes according to the environmental conditions, or if the state of charge of the ES station changes or the main network converter fails, the DC bus voltage will rise or drop accordingly. In such cases, each unit must change its control strategy according to a preset state so the system can switch to the next operation mode.
In any operation mode, the system should have a corresponding converter station acting as a slack bus to maintain the stability of the DC bus voltage. In this paper, according to the range of DC bus voltage and the voltage regulation capability of the converter station, voltage regulation for a DC distribution network is divided into the main voltage regulation mode, backup voltage regulation mode, and off-grid voltage droop regulation mode. These regulation modes are defined as follows.
1) The main voltage regulation mode is the normal working mode of the system. In this mode, P8 acts as the slack bus for the DC distribution network and controls the DC bus voltage. P1 either provides constant DC power or stops running. Renewable energy generation units are controlled by a maximum power point tracking (MPPT) scheme to achieve maximum energy utilization. To ensure that the ES unit can supply energy to the system continuously in off-grid mode, ES unit P5 operates in a current-limiting charging or shutdown state in the main voltage regulation mode. A control block diagram for each converter in the main voltage regulation mode is presented in

Fig. 4 Control block diagrams of each converter in main voltage regulation mode. (a) Control block diagram of P8. (b) Control block diagram of P1. (c) Control block diagram of P3. (d) Control block diagram of P6.
In the main voltage regulation mode, the DC bus voltageUdc satisfies:
(1) |
whereUm1 andUn1 are the upper and lower limits of the DC bus voltage during normal operation of the system, respectively. When the renewable energy or load power changes, if the DC bus voltage fluctuation does not exceed this range, the system continues to run in the main voltage regulation mode.
2) When the output power of P8 reaches the limit or P8 fails, the system switches to backup voltage regulation mode. In this mode, P8 loses the ability to control DC voltage and P1 is utilized as a new slack bus to control DC voltage. Renewable energy generation units continue to operate in the MPPT state and the ES unit operates in a charging or discharging state according to the maximum power of the renewable energy generation units and the load power. The control strategy for each converter in the backup voltage regulation mode is similar to that in the main voltage regulation mode. The differences are that: ① P8 operates at limited power or does not exchange power with the DC network; ② P1 performs constant DC voltage control, which is also divided into two parts. The output voltage loop stabilizes the DC voltage and the power balance control maintains the power balance of each module. The final switching frequency of each module is a combination of the balance correction amount ∆f and basic switching frequencyfbs, which is regulated by the output voltage error signal.
In the backup voltage regulation mode, the DC bus voltage satisfies (2) or (3).
(2) |
(3) |
whereUm2 andUn2 are the upper and lower limits of the DC bus voltage in backup voltage regulation mode, respectively. When all converters connected to the upper public main network are out of operation, the DC bus voltage will increase or decrease. If the DC bus voltage is higher thanUm2 or lower thanUn2, the control of the renewable energy generation units is switched from MMPT control to voltage droop control.
3) When the circuit breakers connected to the two public main grids are disconnected, the system switches to off-grid voltage droop regulation mode. In this mode, there is no power exchange between the system and the public main network, and only the distributed generation and load systems are in operation. At this point, all renewable energy generation units switch to voltage droop control to maintain the stability of the DC bus voltage and the power balance of the system. If the distributed generation units cannot meet the power demands of the loads, then non-important loads should be removed to maintain an energy balance and stabilize the DC bus voltage. A control block diagram for each converter in the off-grid droop regulation mode is presented in

Fig. 5 Control block diagrams of each type of converter in off-grid voltage droop regulation mode. (a) Control block diagram of P3. (b) Control block diagram of P6.
In
Based on the analysis above, it can be seen that the proposed system has three different voltage regulation modes. When the power fluctuations of loads or renewable energy generation units are large or the main network equipment is out of control, the operation mode of the system changes. When the system operation mode changes, the control modes for some grid-connected converters may need to be adjusted accordingly to different voltage regulation modes to maintain the stability of the DC bus voltage. Therefore, it is necessary to develop appropriate criteria for switching between different voltage regulation modes and appropriate methods for coping with changes in the operation mode of the DC distribution system.
Mode switching under TVMC does not need to rely on rapid communication because one can preset the DC voltage margin value for each converter station and monitor local information, allowing each converter station to change control modes automatically according to the magnitude of the DC voltage. However, the system does not change control mode immediately under TVMC when the DC voltage exceeds a preset value. In this study, the main voltage regulation mode is switched to the backup voltage regulation mode as an example for detailed analysis. The control process of the converter station (P1) based on the TVMC strategy is presented in

Fig. 6 Process for TVMC. (a)Udc-Pdc characteristics of P1. (b) Controller structure of P1.
In
When a DC distribution system operates in the main voltage regulation mode, the DC bus voltage is controlled by the AC/DC converter P8, which is connected to the AC main grid. In this voltage regulation mode, the DC bus voltage range is:
(4) |
Therefore, the relative magnitudes of the basic switching frequencies output by each PI regulator can be written as follows:
(5) |
This means that P1 connected to the upper-level DC distribution network operates in constant DC power control mode with a basic switching frequency equal to the output of PI2.
When P8 is out of operation as a result of fault or maintenance, the DC bus voltageUdc increases or decreases based on system power imbalances. If P8 is in the state of injecting power into the DC power distribution system before its operation ends,Udc will drop after P8 stops the operation. WhenUdc falls below the minimum value of the voltage marginUn1,fbs3 will gradually decrease fromfs,max. After a period of adjustment, the relative magnitudes of the basic switching frequency output by each PI regulator will change as follows:
(6) |
At this time, based on the control structure in
(7) |
This indicates that the control of the converter P1 has changed from constant DC power to constant DC voltage, so the system switches to backup voltage regulation mode with the voltage reference valueUn1.
If P8 is in the state of absorbing power from the DC power distribution system before its operation ends,Udc will increase after P8 stops operating. WhenUdc increases to more thanUm1, the control mode of the converter P1 does not change immediately, but the outputfbs1 of the regulator PI1 gradually increases fromfs,min. Finally, the relative magnitudes of each PI regulator change as follows:
(8) |
At this point, P1 operates in constant DC voltage control mode with a voltage reference valueUm1 and the system switches to backup voltage regulation mode.
Based on the above analysis, one can conclude that under TVMC, even if the DC bus voltage exceeds the system preset value, the control of P1 will not immediately change from constant power control mode to constant voltage control mode. Based on the adjustments by the PI regulator, the control mode will only switch when the relative magnitudes of basic switching frequency of each PI regulator change, which makes the mode switching process slower and increases the overall voltage fluctuation time.
To overcome the limitations of TVMC in terms of mode switching, a fast mode switching method based on voltage coefficient is proposed. We determine the operation mode of the converter by introducing a voltage coefficientK, which is defined as:
(9) |
whereUdc,ref is the DC bus voltage reference value, which is considered to be constant at 20 kV; and Δu is a switching threshold of preseted control mode that defines how much the DC bus voltage is allowed to deviate from the reference value in the main voltage regulation mode. When the DC distribution system in
(9) |
When the DC bus voltage deviation exceeds ∆u, P1 first utilizes slope control to give the DC voltage a drooping characteristic, thereby reducing the impact of the converter P1 suddenly taking over DC voltage control. If the DC voltage changes too much, i.e., the output voltage of P1 is out of the range betweenUn1 andUm1, constant voltage control is utilized to prevent the DC voltage from continuously deviating from the rated value. A novel mode switching method that improves upon the TVMC is presented in

Fig. 7 Control strategy for the proposed fast mode switching method based on a voltage coefficient. (a)Udc-Pdc characteristics of P1. (b) Controller structure of P1.
In
(10) |
When,
(11) |
When,
(12) |
whereG is a constant based on the output voltage, which ensures that the output of PI2 quickly matches that of PI1 in the main voltage regulation mode, i.e., the output of the voltage regulator PI2 can effectively avoid slow adjustments based on the limit value after changing control modes, thereby accelerating the adjustment process; Δu1 is the switching threshold of P1 control mode;Id is the DC current based on local information detection; andIdc,ref1 andIdc,ref2 are the reference values for DC current.
By introducing the voltage coefficientK to trigger switching between control modes, once the DC bus voltage is out of range, a converter P1 with the NMSM immediately switches to voltage control mode. The process of changing the relative magnitudes of each PI regulator output under TVMC is omitted, which accelerates the switching process and makes the system recover more quickly.
The controller structures of PV stations under TVMC and NMSM are presented in

Fig. 8 Controller structures of PV stations. (a) Controller structure of a PV station under TVMC. (b) Controller structure of a PV station under NMSM.
To verify the effectiveness of the proposed voltage regulation modes and the related switching control strategy, the DC distribution system in
Under normal working conditions, the system adopts the main voltage regulation mode. P8 operates in constant DC voltage control mode with a voltage reference value of 20 kV. P1 performs constant DC power control with a power command value of 5 MW. P3 and P6 have maximum power values of 8 MW and 9 MW, respectively, prior tot = 1 s, which change to 5 MW and 6 MW, respectively, whent = 1 s. The simulation results are presented in

Fig. 9 Simulation waveforms under normal working conditions. (a) Output voltage waveforms. (b) Output power waveforms.

Fig. 10 Simulation waveforms in backup voltage regulation mode. (a) Output voltage waveforms. (b) Output power waveforms.
When P1 and P8 are both out of operation, the system switches to off-grid voltage droop operation mode and the reference value of voltage command in the off-grid droop mode is determined by the output power of the wind farm or PV station in the previous stage.

Fig. 11 Simulation waveforms in off-grid voltage droop regulation mode. (a) Output voltage waveforms. (b) Output power waveforms.
Since the output power of the wind farm or PV station can change at any time, the off-grid voltage droop mode is only suitable for the short-term operation. In
As shown in Figs. 9, 10, and 11, the system can operate stably in all three voltage regulation modes. When the maximum power of the wind farm or PV station changes, the power level or flow direction of the converter that controls the DC voltage changes in both the main voltage regulation mode and backup voltage regulation mode, but the system power balance can still be maintained. During this process, voltage fluctuations are small and the switching threshold is not exceeded, so the voltage regulation mode is not switched.
To ensure the fairness of our comparisons, the control parameters of the regulators in NMSM are set to be consistent with those in TVMC. In TVMC, three PI regulators (PI1, PI2, and PI3) are utilized to control a converter station with a voltage margin controller, as shown in

Fig. 12 Simulation waveforms when switching between different voltage regulation modes. (a) Output voltage waveforms. (b) Output power waveforms.
In the simulation waveforms in
To demonstrate the superiority of NMSM based on a voltage coefficient proposed in this paper, comparisons between TVMC and NMSM are provided below based on simulations.
For the sake of simplicity, only the voltage waveform at a single point in the DC distribution network is considered. When the range of DC bus voltage is between and, the NMSM utilizes droop control, which makes the transient process of switching noticeably smoother. To keep the system at the same steady-state operation point following transient processes under the control strategies of NMSM and TVMC, the switching of NMSM in the simulation presented in this paper occurs slightly earlier than that of TVMC. For the sake of fairness, we also present a secondary comparative simulation in which switching occurs at the same time. For the sake of distinction, the TVMC that is switched at the same time as the NMSM strategy is called TVMC1, while the other is called TVMC2. The main parameters of the simulation system under NMSM and TVMC are listed in Table II.
The waveforms of the DC bus voltage and output power values of some converters under TVMC and NMSM are presented in

Fig. 13 Transient simulation waveforms when switching from main voltage regulation mode to backup voltage regulation mode. (a) DC bus voltage waveforms. (b) Output power waveforms.
Since the NMSM avoids waiting for the relative magnitudes of the outputs of PI regulators to change, the proposed system allows other converters to take over voltage control more quickly when voltage control is lost, i.e., the fluctuations of DC bus voltage and power are smaller and the system can also be stabilized more rapidly. Comparisons of different values for TVMC and NMSM are listed in Table III. NMSM provides the advantages of fast and smooth transitions between operation modes.
To verify the correctness of NMSM, we construct a low-voltage low-power DC distribution system in a dynamic simulation experimental platform. The schematic diagram of the platform is presented in

Fig. 14 Schematic diagram of experimental platform.
Figures

Fig. 15 Transient experimental waveforms when switching from main voltage regulation mode to backup voltage regulation mode under condition 1. (a) DC voltage waveforms. (b) DC current waveforms.

Fig. 16 Transient experimental waveforms when switching from main voltage regulation mode to backup voltage regulation mode under condition 2. (a) DC voltage waveforms. (b) DC current waveforms.
From the experimental results shown in
In
Figures 15 and 16 shows that, during the transient processes, NMSM can achieve fast and smooth voltage takeover in the event of converter station faults.
In this paper, a fast mode switching method based on a voltage coefficient is proposed for a typical ring DC distribution system with multiple voltage levels. The main contributions of this paper are stated below.
1) According to the voltage regulation capability of the converter station and the DC bus voltage range, different voltage regulation modes are implemented to ensure that the DC bus voltage stability and power balance are maintained under different operation conditions.
2) The disadvantages of long transition time and large fluctuations in voltage and power during mode switching under TVMC are analyzed theoretically. Based on the results, the NMSM based on a voltage coefficient is proposed. By introducing a voltage coefficient associated with DC bus voltage deviations, different voltage regulation modes can realize automatic switching based on local information without the communication between devices.
3) The effectiveness of three voltage regulation modes and NMSM is verified utilizing a simulation platform. The fast mode switching method based on a voltage coefficient proposed in this paper is compared to TVMC based on simulations. The simulation results reveal that compared to TVMC, NMSM based on a voltage coefficient has less DC voltage overshoot and lower power impulses during the switching process of the voltage regulation mode. Additionally, the proposed system can reach a new stable operation point more quickly.
4) An experimental platform is constructed to verify the validity and feasibility of the NMSM.
The control strategy proposed in this paper can effectively solve the complex switching problems of converter station working modes related to switching between operation modes in a DC power distribution system. The generation of overcurrent in the line is reduced, and the steady-state and transient operation characteristics of a multi-terminal flexible DC distribution system can be improved. The proposed method has wide adaptability and scalability.
References
K. Tan, P. So, Y. Chuet al., “Coordinated control and energy management of distributed generation inverters in a microgrid,”IEEE Transactions on Power Delivery, vol.28, no.2, pp.704-713, Apr. 2013. [百度学术]
A. Gomez-Exposito, J. M. Mauricio, and J. M. Maza-Ortega, “VSC-based MVDC railway electrification system,”IEEE Transactions on Power Delivery, vol.29, no.1, pp.422-431, Feb. 2014. [百度学术]
P. Kankanala, S. C. Srivastava, A. K. Srivastavaet al., “Optimal control of voltage and power in a multi-zonal MVDC shipboard power system,”IEEE Transactions on Power Systems, vol.27, no.2, pp.642-650, May 2012. [百度学术]
A. Huang, M. L. Crow, G. T. Heydtet al., “The future renewable electric energy delivery and management (FREEDM) system: the energy internet,”Proceedings of the IEEE, vol.99, no.1, pp.133-148, Feb. 2011. [百度学术]
M. Stieneker, J. Butz, S. Rabieeet al., “Medium-voltage DC research grid aachen,” inProceedings of the 2015 International ETG Congress, Bonn, Germany, Nov. 2015, pp. 549-555. [百度学术]
D. Boroyevich, I. Cvetković, D. Donget al., “Future electronic power distribution systems a contemplative view,” inProceedings of the 2010 12th International Conference on Optimization of Electrical and Electronic Equipment, Basov, Romania, May 2010, pp. 1369-1380. [百度学术]
C. Long, J. Wu, K. Smithet al., “MVDC link in a 33 kV distribution network,” inProceedings of CIRED, Beijing, China, Jun. 2017, pp. 1308-1312. [百度学术]
K. Rudion, A. G. Orths, and P. B. Eriksen, “Offshore power system operation planning considering energy market schedules,”IEEE Transactions on Sustainable Energy, vol.4, no.3, pp.725-733, Jul. 2013. [百度学术]
W. Lu and B. T. Ooi, “Optimal acquisition and aggregation of offshore wind power by multiterminal voltage-source HVDC,”IEEE Power Engineering Review, vol.18, no.1, pp.201-206, Feb. 2003. [百度学术]
T. Nakajima and S. Irokawa, “A control system for HVDC transmission by voltage sourced converters,” inProceedings of the 1999 IEEE PES Summer Meeting, Edmonton, Canada, Jul. 1999, pp. 1113-1119. [百度学术]
W. Wang and M. Barnes, “Power flow algorithms for multi-terminal VSC-HVDC with droop control,”IEEE Transactions on Power Systems, vol.29, no.4, pp.1721-1730, Jul. 2014. [百度学术]
T. M. Haileselassie and K. Uhlen, “Impact of DC line voltage drops on power flow of MTDC using droop control,”IEEE Transactions on Power Systems, vol.27, no.3, pp.1441-1449, Aug. 2012. [百度学术]
L. Xu and L.Yao, “DC voltage control and power dispatch of a multi-terminal HVDC system for integrating large offshore wind farms,”IET Renewable Power Generation, vol.5, no.3, pp.223-233, Jun. 2011 [百度学术]
Z. Wang, K. Li, J. Renet al., “A coordination control strategy of voltage-source-converter-based MTDC for offshore wind farms,”IEEE Transactions on Industry Applications, vol.51, no.4, pp.2743-2752, Jul. 2015. [百度学术]
M. Li, X. Liu, and P. Chen, “Fast voltage margin control strategy for VSC-MTDC systems,”Power System Technology, vol.40, no.10, pp.3045-3051, Oct. 2016. [百度学术]
F. Gao, R. Kang, J. Caoet al., “Primary and secondary control in DC microgrids: a review,”Journal of Modern Power Systems and Clean Energy, vol.7, no.2, pp.227-242, Mar. 2019. [百度学术]
L. Qiao, X. Li, D. Huanget al., “Coordinated control for medium voltage DC distribution centers with flexibly interlinked multiple microgrids,”Journal of Modern Power Systems and Clean Energy, vol.7, no.3, pp.599-611, May 2019. [百度学术]
J. Zhang, J. Liu, J. Yanget al., “An LLC-LC type bidirectional control strategy for LLC resonant converter in power electronic traction transformer,”IEEE Transactions on Industrial Electronics, vol.65, no.11, Nov. 2018, pp. 8595-8604. [百度学术]
J. Xu and J. Xie, “LCL-resonance damping strategies for grid-connected inverters with LCL filters: a comprehensive review,”Journal of Modern Power Systems and Clean Energy, vol.6, no.2, pp.292-305, Mar. 2018. [百度学术]