Abstract:The transformer-less configuration is regarded as a preferred solution for soft-open-point (SOP)-based flexible interconnected distribution networks (FIDNs). This study proposes a reliable and cost-effective method for handling single-line-to-ground (SLG) faults in transformer-less SOP-based FIDNs. Firstly, the zero-sequence fault equivalent circuit of FIDNs is established, and the fault propagation characteristics between the grids interconnected by the SOP are analyzed. Secondly, a zero-sequence current isolation strategy based on proportional-resonant control is proposed to prevent fault propagation toward the healthy-side grid. An active injection-based grounding parameter identification (GPI) approach is then proposed, enabling accurate calculation of the compensation current for arc suppression. Finally, the selection of injected signal parameters is discussed, and the complete timing flow of the SLG fault handling method is presented. A 10 kV SOP-based FIDN model configured with a transformer-less topology is developed in PSCAD/EMTDC. The performance of the SLG fault handling method is verified under transition resistances ranging from 10 Ω to 10 kΩ. The results reveal that the average relative error in GPI is less than 4%. Furthermore, the compensated currents of faulty branch remain below 10 A across various fault conditions.