DOI:10.35833/MPCE.2019.000085 |
| |
| |
Response Time of Reactive Power Based on Different Definitions and Algorithms |
| |
|
| |
Page view: 111
Net amount: 599 |
| |
Author:
Taixun Fang1,2,Qiwen Zhou1,Fengfeng Ding1,Xiaodan Wu1,Zhao Li1,Houjun Tang2
|
Author Affiliation:
1.NR Electric Co., Ltd., Nanjing, China;2.Key Laboratory of Control of Power Transmission and Transformation, Ministry of Education, Shanghai Jiao Tong University, Shanghai, China
|
Foundation: |
|
|
|
Abstract: |
Dynamic reactive power compensation equipment typically requires a fast response to output the necessary reactive power. The term “dynamic response time of reactive power” is often used but has never been clearly defined. This paper summarizes the reactive power calculations under different definitions and algorithms and considers these calculations in terms of signal processing to simulate and analyze the step response. This paper subsequently focuses on the widely used instantaneous reactive power algorithm and finally concludes that the dynamic reactive power response time closely depends on the reactive power calculation method itself. The single-phase instantaneous reactive power algorithm has the fastest response time. The reactive power response time of dynamic reactive devices in power systems is a minimum of a quarter of one cycle time for the well-known and widely used single-phase reactive power algorithms. |
Keywords: |
Response time ; reactive power ; instantaneous reactive power ; Hilbert transform ; phase shift ; synchronous reference frame |
| |
Received:February 12, 2019
Online Time:2021/03/22 |
| |
|
|
View Full Text